SPS 364.0701 SPS 364.0701Combustible air. Barometric dampers may not be used for combustion air as allowed by IFC section 304.3 and NFPA 54-2015 section 9.3.1.4.
SPS 364.0701 History History: CR 16-094: cr. Register April 2018 No. 748, eff. 5-1-18.
SPS 364.0801 SPS 364.0801Chimneys and vents.
SPS 364.0801(1) (1) This is a department informational note to be used under IMC chapter 8: Note: For DHS licensed healthcare facilities as specified in chs. DHS 124, 132, and 134, also refer to NFPA 211 as adopted in these chapters.
SPS 364.0801(2) (2) This is a department rule in addition to the requirements in IMC section 801.2: Portable or permanently installed, fuel-fired, unvented heating appliances may not be installed except during construction or demolition of a building if the appliances are provided in accordance with ch. SPS 314.
SPS 364.0801 Note Note: See s. SPS 365.0621 for use of portable or permanently installed, fuel-fired, unvented heating appliances.
SPS 364.0801 History History: CR 00-179: cr. Register December 2001 No. 552, eff. 7-1-02; CR 04-016: am. (2) Register December 2004 No. 588, eff. 1-1-05; CR 06-120: am. (2), cr. (3) Register February 2008 No. 626, eff. 3-1-08; CR 10-103: r. (3) Register August 2011 No. 668, eff. 9-1-11; correction in (2) made under s. 13.92 (4) (b) 7., Stats., Register December 2011 No. 672; CR 16-094: am. (2) Register April 2018 No. 748, eff. 5-1-18.
SPS 364.0802 SPS 364.0802Door swing. The requirements in IMC section 802.9 are not included as part of chs. SPS 361 to 366.
SPS 364.0802 History History: CR 16-094: cr. Register April 2018 No. 748, eff. 5-1-18.
SPS 364.0918 SPS 364.0918Forced-air warm-air furnaces.
SPS 364.0918(1)(1) This is a department rule in addition to the requirements in IMC section 918.6: The outside air intake openings shall be located at least 12 inches vertical from the adjoining grade level.
SPS 364.0918(2) (2) Substitute the following wording for the requirements in IMC section 918.6 item 2: Where located less than 10 feet above the surface of any abutting public way or driveway, or at grade level by a sidewalk, street, alley or driveway.
SPS 364.0918 History History: CR 00-179: cr. Register December 2001 No. 552, eff. 7-1-02; CR 10-103: r. (2), renum. (3) to be (2) Register August 2011 No. 668, eff. 9-1-11.
SPS 364.1001 SPS 364.1001Boilers, water heaters and pressure vessels. Substitute the following wording for the requirements and exceptions in IMC chapter 10:
SPS 364.1001(1) (1) The provisions of ch. SPS 341 shall govern the installation, alteration and repair of boilers and pressure vessels. The provisions of chs. SPS 381 to 386 shall govern the installation, alteration and repair of water heaters.
SPS 364.1001(2) (2) Water heaters utilized both to supply potable hot water and provide hot water for space-heating applications shall be listed and labeled by the manufacturer and shall be installed in accordance with the manufacturer's installation instructions and applicable provisions in chs. SPS 381 to 386.
SPS 364.1001(3) (3) Water heaters utilized for both potable water heating and space-heating applications shall be sized to prevent the space-heating load from diminishing the required water-heating capacity.
SPS 364.1001 History History: CR 00-179: cr. Register December 2001 No. 552, eff. 7-1-02; CR 06-120: r. (4) Register February 2008 No. 626, eff. 3-1-08; correction in (1), (2) made under s. 13.92 (4) (b) 7., Stats., Register December 2011 No. 672.
SPS 364.1101 SPS 364.1101Refrigeration. Substitute the following wording for the requirements and exceptions in IMC chapter 11: Mechanical refrigerating systems installed in public buildings and places of employment shall comply with ch. SPS 345.
SPS 364.1101 History History: CR 00-179: cr. Register December 2001 No. 552, eff. 7-1-02; correction made under s. 13.92 (4) (b) 7., Stats., Register December 2011 No. 672.
SPS 364.1500 SPS 364.1500Referenced standards. This is a department rule in addition to the requirements in IMC chapter 15: The following standards are incorporated by reference into chs. SPS 361 to 366:
SPS 364.1500(1m) (1m) FGI Guidelines for Design and Construction of Hospitals and Outpatient Facilities, 2014.
SPS 364.1500(2m) (2m) FGI Guidelines for Design and Construction of Residential Health, Care, and Support Facilities, 2014.
SPS 364.1500 Note Note: FGI guidelines may be purchased at fgiguidelines.org or AHA Services Inc. P.O. Box 933283, Atlanta, GA, 31193-3283.
SPS 364.1500(3) (3) NFPA 45-2015, Standard on Fire Protection for Laboratories Using Chemicals.
SPS 364.1500 Note Note: NFPA standards may be viewed online free of charge at NFPA.org or purchased from the National Fire Protection Association, 1 Batterymarch Park, P.O. Box 9101, Quincy, MA 02269-9101.
SPS 364.1500 Note Note: Copies of the standards adopted under this section are on file in the offices of the department and the legislative reference bureau.
SPS 364.1500 History History: CR 00-179: cr. Register December 2001 No. 552, eff. 7-1-02; CR 01-139: am. Register June 2002 No. 558, eff. 7-1-02; correction in (1) made under s. 13.93 (2m) (b) 7., Stats., Register April 2003 No. 568; CR 04-016: r. and recr. (2) Register December 2004 No. 588, eff. 1-1-05; CR 06-120: r. (1), am. (2) (a), cr. (2) (c) Register February 2008 No. 626, eff. 3-1-08; CR 10-103: am. (2) (a) Register August 2011 No. 668, eff. 9-1-11; CR 16-094: renum. (2) (intro.), (a) to 364.1500 (intro.), (1m) and am., r. (2) (b), (c), cr. (2m), (3) Register April 2018 No. 748, eff. 5-1-18.
SPS 364.1600 SPS 364.1600Appendices. IMC Appendices A and B are not included as part of this chapter.
SPS 364.1600 History History: CR 00-179: cr. Register December 2001 No. 552, eff. 7-1-02.