SPS 366.0901(1)
(1)
Change in occupancy with no occupancy classification. Substitute the following wording for the requirements in IEBC section 901.2: A change in occupancy, as defined in IEBC section 202, with no change of occupancy classification may not be made to any structure that will subject the structure to any special provisions of this code, including the provisions of IEBC sections 902 through 911, without the approval of the code official.
SPS 366.0901(2)
(2) Change of occupancy classification. This is a department rule in addition to the requirements in IEBC section 901.3: Buildings undergoing a change in occupancy that would result in an increase in demand for either fossil fuel or electrical energy shall comply with IECC.
SPS 366.0901(3)
(3) Certification of occupancy required. The requirements in IEBC section 901.4 are not included as part of this code.
SPS 366.0901(4)
(4) Standpipe systems. This is a department rule in addition to the requirements in IEBC section 912.2: Standpipe systems shall be provided in existing buildings and structures or portions of existing buildings and structures in accordance with chapter 9 of the IBC when existing buildings or structures that are greater than 60 feet in height are changed to include a Group R-1 or R-2 occupancy.
SPS 366.0911(1)(1)
Elevator recall. This is a department rule in addition to the requirements in IEBC section 911: At least one existing elevator shall be provided with emergency recall operation and emergency in-car operation complying with
ch. SPS 318 when an existing building or structure that is greater than 60 feet in height is changed to include a Group R-1 or R-2 occupancy.
SPS 366.0911(2)
(2) Carbon monoxide alarms. This is a department rule in addition to the requirements in IEBC section 911: A building or a portion of a building changed to be or include a residential building as defined under s.
101.149 (1) (b), Stats., shall be provided with carbon monoxide alarms or detectors in accordance with
s. SPS 362.1200.
SPS 366.0911 History
History:
CR 06-120: cr.
Register February 2008 No. 626, eff. 3-1-08;
EmR0826: emerg. renum. to be (1), cr. (1) (title) and (2), eff. 10-1-08;
CR 08-085: renum. to be (1), cr. (1) (title) and (2)
Register May 2009 No. 641, eff. 6-1-09;
correction in (1), (2) made under s.
13.92 (4) (b) 7., Stats.,
Register December 2011 No. 672.
SPS 366.0912
SPS 366.0912
Plumbing. Substitute the following wording for the requirements in IEBC section 910: Where the occupant load of a story is increased by more than 20 percent, plumbing fixtures for the story shall be provided in quantities specified in the IBC based on the increased occupant load.
SPS 366.0912 History
History:
CR 06-120: cr.
Register February 2008 No. 626, eff. 3-1-08;
CR 10-103: renum. from Comm 66.0910
Register August 2011 No. 668, eff. 9-1-11.
SPS 366.1002
SPS 366.1002 Fire Protection Systems. This is a department exception to the requirements in IEBC section 1002.3: An automatic sprinkler system is not required for additions to individual dwelling units within existing townhouses that are not already protected with an automatic sprinkler system.
SPS 366.1002 History
History:
CR 10-103: cr.
Register August 2011 No. 668, eff. 9-1-11.
SPS 366.1101(1)(1)
Scope. This is a department rule in addition to the requirements in IEBC section 1101.1: Any historic building is exempt from the energy requirements of this code.
SPS 366.1101(2)
(2) Report. The requirements in IEBC section 1101.2 are not included as part of this code.
SPS 366.1101 History
History:
CR 06-120: cr.
Register February 2008 No. 626, eff. 3-1-08;
CR 10-103: renum. (1) to be (2), (2) to be Comm 66.1105 and am. (2) (title), cr. (1)
Register August 2011 No. 668, eff. 9-1-11.
SPS 366.1105
SPS 366.1105
Exhibit buildings. These are department rules in addition to the requirements in IEBC section 1105: Historic buildings to be used as exhibit buildings shall comply with all of the following requirements:
SPS 366.1105(1)
(1) The building shall be open to the public only under the supervision of a tour guide.
SPS 366.1105(2)
(2) The building may not be lived in, slept in or worked in, except for the purpose of demonstrating to the public how people lived in a particular era.
SPS 366.1105(4)
(4) Open flame equipment may not be used in the building, except for fire places and other mechanical equipment original to the building.
SPS 366.1105(5)
(5) Fire extinguishers shall be installed in exhibit buildings and may be located in a nonconspicuous location but accessible to the occupants.
SPS 366.1105(6)(a)(a) At least one smoke detector shall be provided for each 1,200 square feet of floor area with a minimum of one smoke detector per floor level.
SPS 366.1105(6)(b)1.1. Except as specified in
subd. 2., where electricity is provided in the exhibit building, the smoke detectors shall be connected to the electrical power.
SPS 366.1105(6)(b)2.
2. Where no electrical power is provided to an exhibit building, the smoke detectors shall be of a battery type.
SPS 366.1105(7)
(7) Exhibit buildings provided with only one means of egress shall be restricted to a total capacity of 12 people, and not more than 6 people may be located above or below the first floor at any one time.
SPS 366.1105(8)
(8) Stairways without 6-foot, 4-inch vertical headroom clearance shall have signs posted warning occupants of the headroom clearance available.
SPS 366.1105(9)
(9) Exit signs shall be provided in accordance with the prevailing code in exhibit buildings occupied prior to ½-hour before sunrise and ½-hour after sunset and in all areas not provided with natural lighting.
SPS 366.1105 History
History:
CR 10-103: renum. from Comm 66.1101 (2)
Register August 2011 No. 668, eff. 9-1-11; correction in (b) 1. made under s.
13.92 (4) (b) 7., Stats.,
Register August 2011 No. 668.
SPS 366.1301(1)(1) Substitute the following wording for the requirements in IEBC section 1301.2: The provisions of sections 1301.2.1 through 1301.2.5 shall apply to existing occupancies that will continue to be, or are proposed to be, in Groups A, B, E, F, M, R and S. These provisions shall not apply to buildings with occupancies in Group H or Group I.
SPS 366.1301(2)
(2) Accessibility Requirements. Substitute the following wording for the requirements in IEBC section 1301.2.5: All portions of the buildings proposed for change of occupancy or being altered shall conform to the accessibility provisions of IEBC section 310.
SPS 366.1301(3)
(3) The requirements in IEBC section 1301.3.2 are not included as part of this code.
SPS 366.1301 History
History:
CR 06-120: cr.
Register February 2008 No. 626, eff. 3-1-08;
CR 10-103: am. (title), renum. (2) to be (3), cr. (2)
Register August 2011 No. 668, eff. 9-1-11.
SPS 366.1400
SPS 366.1400
Construction safeguards. The requirements in IEBC chapter 14 are not included as part of this code.
SPS 366.1400 History
History:
CR 10-103: cr.
Register August 2011 No. 668, eff. 9-1-11.