SPS 327.41(4)(c)1.1. Where all appliances drawing air for combustion and dilution from the room are gas appliances, air may be provided via a single opening to connect the room to the outdoors in accordance with this paragraph.
SPS 327.41(4)(c)2.a.a. The opening shall be located within one foot of the ceiling of the room.
SPS 327.41(4)(c)2.b. b. The opening may connect directly to the outdoors, may connect to the outdoors through a horizontal duct, or may connect to the outdoors through a vertical duct.
SPS 327.41(4)(c)2.c. c. The net free area of the opening shall be calculated in accordance with sub. (5).
SPS 327.41(4)(c)3.a.a. The net free area of the opening shall be a minimum of one square inch per 3000 Btu/h of combined input rating of the fuel-burning appliances drawing combustion and dilution air from the room, and not less than the combined cross-sectional flow areas of the appliance flue collars or draft hood outlets.
SPS 327.41(4)(c)3.b. b. The cross-sectional area of the duct shall be equal to or greater than the required size of the opening.
SPS 327.41(4)(c)4. 4. The appliances shall have a minimum clearance to the surfaces of the room of one inch at the sides and back of the appliance and 6 inches at the front of the appliance.
SPS 327.41(4)(d)1.1. A combination of openings to the outside and openings to other rooms may be used in accordance with this paragraph.
SPS 327.41(4)(d)2.a.a. One opening shall connect directly to the outdoors, connect to the outdoors through a horizontal duct, or connect to the outdoors through a vertical duct.
SPS 327.41(4)(d)2.b. b. The net free area of the openings shall be calculated in accordance with sub. (5).
SPS 327.41(4)(d)2.c. c. The net free area of the opening shall be a minimum of one square inch per 5000 Btu/h of combined input rating of the fuel burning appliances drawing combustion and dilution air from the room.
SPS 327.41(4)(d)2.d. d. The cross-sectional area of a duct, if used, shall be equal to or greater than the required size of the opening.
SPS 327.41(4)(d)3.a.a. The equipment shall be located in a space with a volume not less than 50 cubic feet per 1000 Btu/h of the combined input rating of all fuel-burning appliances installed in that space.
SPS 327.41(4)(d)3.b. b. The space may be made up of more than one room if the rooms are connected through openings without doors or connected through sets of openings described in subd. 4.
SPS 327.41(4)(d)4.a.a. When needed to connect rooms, two openings shall be provided, one within one foot of the ceiling of the room and one within one foot of the floor.
SPS 327.41(4)(d)4.b. b. The net free area of openings shall be calculated in accordance with sub. (5).
SPS 327.41(4)(d)4.c. c. The net free area of each opening shall be a minimum of one square inch per 1000 Btu/h of combined input rating of the fuel burning appliances drawing combustion and dilution air from the communicating rooms, but shall be not less than 100 square inches.
SPS 327.41(5) (5)Net free area calculation.
SPS 327.41(5)(a)(a) The required size of openings for combustion and dilution air shall be based on the net free area of each opening.
SPS 327.41(5)(b) (b) The net free area of an opening shall be that specified by the manufacturer of the opening covering or by a source approved by the department.
SPS 327.41(5)(c) (c) In the absence of such information, openings covered with metal louvers shall be deemed to have a net free area of 75 percent of the area of the opening, and openings covered with wood louvers shall be deemed to have a net free area of 25 percent of the area of the opening.
SPS 327.41 History History: EmR1703: emerg. cr., eff. 2-6-17; CR 17-017: cr. Register March 2018 No. 747, eff. 4-1-18.
SPS 327.42 SPS 327.42Mechanical draft systems. Where a mechanical draft system, such as a fan is used, provision shall be made to prevent the flow of gas to the main burners when the draft system is not performing so as to satisfy the operating requirements of the system for safe performance.
SPS 327.42 History History: EmR1703: emerg. cr., eff. 2-6-17; CR 17-017: cr. Register March 2018 No. 747, eff. 4-1-18.
SPS 327.43 SPS 327.43Equipment maintenance information. Required regular maintenance actions for equipment shall be clearly stated and incorporated on a readily accessible label. The label may be limited to identifying, by title or publication number, the operation and maintenance manual for that particular model and type of equipment. Maintenance instructions shall be furnished for equipment which requires preventive maintenance for efficient operation. Manufacturer's manuals for all installed heating and cooling equipment and service water heating equipment shall be provided.
SPS 327.43 History History: EmR1703: emerg. cr., eff. 2-6-17; CR 17-017: cr. Register March 2018 No. 747, eff. 4-1-18.
SPS 327.44 SPS 327.44Ductwork.
SPS 327.44(1) (1)Duct use. Ducts designed for the transmission of air shall be used for no other purpose.
SPS 327.44(2) (2)Interior ducts. All interior ducts shall be constructed in accordance with the following:
SPS 327.44(2)(a) (a) Supply and return air ducts. Supply and return air ducts shall comply with this paragraph except that ducts attached to appliances may be constructed of materials specified in the appliance listing.
SPS 327.44(2)(a)1. 1. Kitchen exhaust ducts and ducts for air exceeding 250 degrees Fahrenheit shall be constructed of sheet metal or lined with sheet metal or constructed of other noncombustible noncorrugated materials.
SPS 327.44(2)(a)2. 2. Ducts connected to furnaces shall be constructed of sheet metal for at least 6 feet from the furnace.
SPS 327.44(2)(a)3. 3. Spaces formed by unlined wood joists, studs or wood I-joists with solid webs may be used as return air ducts. Spaces used as return air ducts shall be cut off from all remaining unused portions of the space by tight-fitting stops of sheet metal or of wood joist material. Bridging shall be removed from the joist space.
SPS 327.44(2)(b) (b) Under-floor plenums. An under-floor space may be used as a plenum in a camping unit in accordance with this section.
SPS 327.44(2)(b)1. 1. Except for the floor immediately above the under-floor plenum, supply ducts shall be provided extending from the plenum to registers or other floor levels.
SPS 327.44(2)(b)2. 2. The under-floor spaces shall not be used for storage, shall be cleaned of all loose scrap material and shall be tightly and substantially enclosed.
SPS 327.44(2)(b)3. 3. The enclosing material of the under-floor space, including the side wall insulation and vapor barriers, shall not be more flammable than one-inch wood boards.
SPS 327.44(2)(b)4. 4. Access shall be through an opening in the floor which shall be 18 inches by 24 inches.
SPS 327.44(2)(b)5. 5. The furnace supplying warm air to the under-floor space shall be equipped with an automatic control which will start the air circulating fan when the air in the furnace bonnet reaches a temperature not higher than 150 degrees Fahrenheit. The control shall be one that cannot be set higher than 150 degrees Fahrenheit.
SPS 327.44(2)(b)6. 6. The furnace supplying warm air to the under-floor space shall be equipped with an approved temperature limit control that will limit outlet air temperature to 200 degrees Fahrenheit.
SPS 327.44(2)(b)7. 7. A noncombustible receptacle shall be placed below each floor opening into the air chamber. The receptacle shall be securely suspended from the floor members and shall be not more than 18 inches below the floor opening. The area of the receptacle shall extend 3 inches beyond the opening on all sides. The perimeter of the receptacle shall have a vertical lip at least one inch high at the open sides if it is at the level of the bottom of the joist, or 3 inches high if the receptacle is suspended.
SPS 327.44(2)(b)8. 8. Floor registers shall be designed for easy removal to permit access for cleaning the receptacles.
SPS 327.44(2)(b)9. 9. Exterior walls and interior stud partitions shall be firestopped at the floor.
SPS 327.44(2)(b)10. 10. Each wall register shall be connected to the air chamber by a register box or boot.
SPS 327.44(2)(b)11. 11. A duct conforming to par. (a) shall extend from the furnace supply outlet at least 6 inches below combustible framing.
SPS 327.44(2)(b)12. 12. The entire ground surface and enclosing exterior walls of the under-floor space shall be covered with a vapor barrier having a vapor permeability rating of one perm or less and a flame spread rating of 200 or less.
SPS 327.44(2)(b)13. 13. Fuel gas lines may not be located within the under-floor space.
SPS 327.44 History History: EmR1703: emerg. cr., eff. 2-6-17; CR 17-017: cr. Register March 2018 No. 747, eff. 4-1-18.
SPS 327.45 SPS 327.45Dampers, registers, and grilles.
SPS 327.45(1)(1)Volume and backdraft dampers.
SPS 327.45(1)(a)(a) Volume duct dampers shall be provided to permit balancing of the system.
SPS 327.45(1)(b) (b) Volume dampers shall be provided with access.
SPS 327.45 Note Note: Acceptable means of access include a manufactured access panel, an air grille used as a cover, a plastic ceiling cap, or a damper accessible through an air diffuser or grille.
SPS 327.45(2) (2)Air registers and grilles.
SPS 327.45(2)(a)(a) Supply air registers. All supply air outlets shall be provided with registers or devices which will provide a uniform distribution of air.
SPS 327.45(2)(b) (b) Return air grilles. Return air grilles shall not be located in bathrooms, kitchens, utility spaces, or a confined space in which a draft diverter or draft regulator is located. All other habitable spaces shall have permanent openings to a return air grille equal in area to the supply outlet serving those areas. At least one return air opening shall be provided for each floor.
SPS 327.45 History History: EmR1703: emerg. cr., eff. 2-6-17; CR 17-017: cr. Register March 2018 No. 747, eff. 4-1-18.
SPS 327.46 SPS 327.46Piping.
SPS 327.46(1) (1)Pipe sizes and arrangement. All steam and hot water supply and return piping, air-line piping and auxiliary equipment shall be of appropriate sizes, elevations and arrangements to accomplish the calculated results without stress or other detriment.
SPS 327.46 Note Note: The sizes of pipe to be used for mains and risers may be selected from the ASHRAE Guide and Data Book, published by the American Society of Heating, Refrigerating and Air Conditioning Engineers; or the manuals published by the Institute of Boiler and Radiator Manufacturers or the Mechanical Contractors Association of America.
SPS 327.46(2) (2)Expansion and contraction. The piping for the heating system shall be equipped with anchors, expansion swings, or joints, supports and similar devices to relieve stress and strain caused by temperature change of the pipe material.
SPS 327.46(3) (3)Pipe insulation. Unguarded steam, hot water supply and return piping shall be covered with insulating material where the pipes pass through occupied areas and the surface temperature exceeds 180 degrees Fahrenheit.
SPS 327.46(4) (4)Steam and hot water pipes. No pipe carrying hot water or steam at a surface temperature exceeding 250 degrees Fahrenheit shall be placed within one inch of any combustible material, pass through a combustible floor, ceiling, or partition unless the pipe is protected by a metal sleeve one inch larger in diameter than the pipe or with approved pipe covering.
SPS 327.46(5) (5)Balancing. Balancing cocks shall be provided in each circuit of a hot water distribution system.
SPS 327.46 History History: EmR1703: emerg. cr., eff. 2-6-17; CR 17-017: cr. Register March 2018 No. 747, eff. 4-1-18.
SPS 327.47 SPS 327.47Venting system location. A venting system shall terminate at least 3 feet above any forced air inlet located within 10 feet horizontally. This provision does not apply to the combustion air intake of a direct-vent appliance.
SPS 327.47 History History: EmR1703: emerg. cr., eff. 2-6-17; CR 17-017: cr. Register March 2018 No. 747, eff. 4-1-18.
SPS 327.48 SPS 327.48Multiple appliance venting. Two or more listed gas-or liquid-fueled appliances may be connected to a common gravity-type flue provided the appliances are equipped with listed primary safety controls and listed shutoff devices and comply with the following requirements:
SPS 327.48(1) (1) The appliances shall be located in the same story, except for engineered venting systems.
SPS 327.48(2) (2) The appliances shall be joined at a manifold or Y-type fitting as close to the chimney as possible, unless the connector from each appliance enters a separate chimney inlet and the inlets are offset at least 12 inches vertically or the separate inlets occur at right angles to each other.
SPS 327.48 History History: EmR1703: emerg. cr., eff. 2-6-17; CR 17-017: cr. Register March 2018 No. 747, eff. 4-1-18.
SPS 327.49 SPS 327.49Fuel storage.
SPS 327.49(1) (1)LP gas storage tanks.
SPS 327.49(1)(a)(a) All LP gas storage tanks shall be constructed, installed, and maintained to conform with the applicable sections of ch. SPS 340.
SPS 327.49(1)(b) (b) LP gas tanks may not be located inside camping units.
SPS 327.49(1)(c) (c) LP gas tanks shall have welded steel supports and be permanently installed on concrete pads or foundations.
SPS 327.49(2) (2)Oil storage tanks.
SPS 327.49(2)(a)(a) The total oil storage capacity inside any camping unit shall be limited to 550 gallons in one tank, or not more than 275 gallons in each of 2 tanks cross-connected to a single burner.
SPS 327.49(2)(b) (b) Oil storage tanks on the inside of any camping unit shall be located at the same level as the burner it serves.
SPS 327.49 Note Note: Except as provided in pars. (a) and (b), the installation of oil storage tanks is regulated under ch. ATCP 93, Flammable, Combustible, and Hazardous Liquids.
SPS 327.49(3) (3)Gas piping systems. Gas piping systems, extending from the point of delivery to the connection with each gas-fired appliance or device, shall be installed to conform with NFPA 54, National Fuel Gas Code.
SPS 327.49(4) (4)Shutoff and control devices.
Loading...
Loading...
Published under s. 35.93, Stats. Updated on the first day of each month. Entire code is always current. The Register date on each page is the date the chapter was last published.