SPS 332.24(5)(c)2. 2. Kilns may be located in boiler or furnace rooms if adequate combustion air is maintained for the boiler or furnace and the kiln under all operating conditions.
SPS 332.24(5)(c)3. 3. Fuel-fired kilns located outside of buildings shall be exempt from the ventilation requirements of this subsection. They shall be located to minimize the products of combustion from entering the building, but in no case shall the distance be less than 10 feet measured in any direction from a wall opening or air intake.
SPS 332.24(5)(c)4. 4. Kilns shall be installed in accordance with the manufacturer's specifications for distance to walls.
SPS 332.24 Note Note: Wall-to-kiln distance may vary from 12 to 18 inches, depending on the type of kiln.
SPS 332.24(5)(c)5. 5. Kilns shall be located to minimize the possibility of burns.
SPS 332.24 Note Note: The outside temperature of kilns may vary from approximately 250 to 450º F, depending on the type of kiln.
SPS 332.24(5)(d) (d) Downdraft ventilation. Electric kilns with downdraft ventilation may have the ventilation ductwork maintained at a positive pressure through occupied areas provided the ductwork is sealed to prevent any leakage.
SPS 332.24(6) (6)Ventilation for laboratory fume hoods.
SPS 332.24(6)(a)(a) General.
SPS 332.24(6)(a)1.1. Except as provided in par. (b), laboratory fume hoods during use shall be operated with a minimum average 100 feet per minute face velocity at full open sash or sash stop position. When determining the minimum flow rate through the fume hood, the sash stop position may not be lower than 18 inches above the work surface.
SPS 332.24 Note Note: When operating the fume hood, the sash should be positioned to maximize the protection to the user.
SPS 332.24(6)(a)2. 2. Vertical sash fume hoods operated at sash stop positions shall have an alarm that gives a warning when the sash is raised above the sash stop position. Combination vertical/horizontal sash fume hoods shall have an alarm that gives a warning when the sash is vertically raised from the fully lowered position.
SPS 332.24(6)(b) (b) Alternate operation.
SPS 332.24(6)(b)1.1. Fume hoods operating at minimum average face velocities less than 100 feet per minute shall achieve a spillage rate less than 0.1 ppm at 4.0 liters per minute gas release for an "as used" condition in accordance with the American Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE) standard 110 - Method of Testing Laboratory Fume Hoods. The minimum allowable average face velocity for fume hoods achieving the ASHRAE 110 containment criteria shall be 40 feet per minute at full open sash.
SPS 332.24(6)(b)2. 2. Fume hoods operating at minimum average face velocities less than 100 feet per minute shall have a continuous flow meter with an alarm.
SPS 332.24 Note Note: For further information regarding fume hood operation, see ANSI/AIHA standard Z9.5 - Laboratory Ventilation.
SPS 332.24(6)(c) (c) Testing. Operable fume hoods shall be tested annually for minimum average face velocity.
SPS 332.24 History History: Cr. Register, February, 1999, No. 518, eff. 3-1-99; am. (2) (a), (4) (c), (5) (a) and (c) 2., r. (2) (b) and Figure 32.24, renum. (2) (c) and (d) to be (2) (b) and (c) and am. (c), cr. (5) (d) and (6), Register, June, 2000, No. 534, eff. 7-1-00; CR 01-139: am. (5) (c) 1. Register June 2002 No. 558, eff. 7-1-02; correction in (5) (a) 3., (c) 1. made under s. 13.92 (4) (b) 7., Stats., Register December 2011 No. 672.
SPS 332.25 SPS 332.25 Compressed gases [29 CFR 1910.101]. This department rule is in addition to 29 CFR 1910.101:
SPS 332.25(1) (1) All compressed gas cylinders shall be secured around the body of the cylinder to prevent falling.
SPS 332.25 History History: Cr. Register, February, 1999, No. 518, eff. 3-1-99.
SPS 332.26 SPS 332.26 Spray finishing using flammable and combustible materials [29 CFR 1910.107]. This department rule is in addition to 29 CFR 1910.107:
SPS 332.26(1) (1)Plan submittal. Plans in quadruplicate and one set of specifications shall be submitted to the department for approval before installing any spray booth under this chapter.
SPS 332.26 Note Note: See chs. SPS 361 to 366 for complete plan submittal and ventilation requirements.
SPS 332.26 History History: Cr. Register, February, 1999, No. 518, eff. 3-1-99.
SPS 332.28 SPS 332.28 Permit-required confined spaces [29 CFR 1910.146]. These department rules are in addition to 29 CFR 1910.146 for permit-required confined spaces:
SPS 332.28(1) (1)Sampling device.
SPS 332.28(1)(a)(a) The sampling device shall be calibrated relative to the oxygen content of the ambient air at the time of sampling. Calibration of the sampling device relative to the oxygen content shall be performed where the 20.9% natural content of oxygen in the air is most likely to occur.
SPS 332.28 Note Note: Oxygen calibration should not be performed near a confined space opening.
SPS 332.28(1)(b) (b) A sampling device which has a zero set shall be zeroed in a clean atmosphere before each sampling. Calibration of a sampling device shall be conducted as often as recommended by the manufacturer, but at least once every 6 months.
SPS 332.28(1)(c) (c) The sampling device or a non-sparking probe attached to the sampling device shall be used to sample the atmosphere of a confined space. When entry to a confined space is by means of a manhole, a probe shall be inserted through the pick-hole of the manhole cover, or the manhole cover shall be pried open on the downwind side to allow just enough room for insertion of the probe or device.
SPS 332.28(2) (2)Air monitoring. The atmosphere in a confined space within the authorized entrant's immediate area shall be continuously monitored for oxygen, hydrogen sulfide or carbon monoxide, combustible gas and any other hazardous substance which the employer has reason to believe may be present in the confined space.
SPS 332.28(3) (3)Training. An employer shall provide training in basic first aid and adult cardiopulmonary resuscitation for all authorized entrants and attendants.
SPS 332.28 History History: Cr. Register, February, 1999, No. 518, eff. 3-1-99.
SPS 332.29 SPS 332.29 Confined spaces. These are department rules for all confined spaces:
SPS 332.29(1) (1)Entry prohibited. A confined space with an atmosphere which has a combustible gas content of 10% or more of the lower explosive limit shall not be entered even if a breathing apparatus or respirator is used.
SPS 332.29(2) (2)Smoking and open flames. Smoking and open flames shall not be allowed within 10 feet of a confined space.
SPS 332.29(3) (3)Working in streets. Work at confined spaces which are located in streets shall be performed in accordance with the following:
SPS 332.29(3)(a) (a) A vehicle's beacon and 4-way flashers shall be activated upon approach to an entrance of a confined space.
SPS 332.29(3)(b) (b) A vehicle shall be parked to permit traffic to flow in an unobstructed manner and, where possible, to provide protection for the employees.
SPS 332.29(3)(c) (c) A vehicle shall be parked so vehicle exhaust cannot accumulate in the confined space. If this is not possible, the vehicle's exhaust pipe shall be extended away from the confined space.
SPS 332.29 Note Note: See also s. SPS 332.39.
SPS 332.29 History History: Cr. Register, February, 1999, No. 518, eff. 3-1-99.
SPS 332.30 SPS 332.30 Medical services and first aid [29 CFR 1910.151]. Substitute the following wording for 29 CFR 1910.151 (c):
SPS 332.30(1) (1) Whenever the eyes or body of any person may be exposed to materials that are corrosive or can cause irreversible eye or bodily injury, suitable facilities for quick drenching or flushing of the eyes and body shall be provided within the work area for immediate emergency use.
SPS 332.30 Note Note: The department will accept facilities that comply with ANSI standard Z358.1, Emergency Eyewash and Shower Equipment.
SPS 332.30 History History: Cr. Register, February, 1999, No. 518, eff. 3-1-99.
SPS 332.31 SPS 332.31 Fire brigades [29 CFR 1910.156]. Section 29 CFR 1910.156 is not included as part of this chapter.
SPS 332.31 Note Note: See ch. SPS 330 for fire department safety and health requirements.
SPS 332.31 History History: Cr. Register, February, 1999, No. 518, eff. 3-1-99.
SPS 332.32 SPS 332.32 Handling materials, general [29 CFR 1910.176]. These department rules are in addition to 29 CFR 1910.176:
SPS 332.32(1) (1)Conveyors. Conveyor systems passing through more than one room, or from one working level to another, shall be provided in each room, or working level, where exposed to contact, with means to disconnect the power.
SPS 332.32(2) (2)Incompatible materials. Incompatible materials shall be segregated to prevent accidental contact with each other that may result in fire, explosion or toxic gas emission.
SPS 332.32 Note Note: Guidance in the storage of incompatible materials can be obtained in publications from the National Fire Protection Association, such as NFPA 49 and 491M.
SPS 332.32 History History: Cr. Register, February, 1999, No. 518, eff. 3-1-99.
SPS 332.33 SPS 332.33 General requirements for all machines [29 CFR 1910.212]. These department rules are in addition to 29 CFR 1910.212:
SPS 332.33(1) (1)Disconnection from source of power.
SPS 332.33(1)(a)(a) Every machine shall be equipped with a loose pulley, clutch, switch or other adequate means within reaching distance of the normal operating positions of the operator for the purpose of disconnecting the machine from the source of power.
SPS 332.33(1)(b) (b) Machines on which 2 or more persons work shall be equipped with one or more controls so located that more than one of these persons can quickly disconnect the machine from the source of power.
SPS 332.33(2) (2)Counterweights, tension weights and springs.
SPS 332.33(2)(a)(a) Every counterweight, where exposed to contact, shall be enclosed or be equipped with a safety device attached independent of the counterweight support, that shall prevent the weight from falling to a point of less than 7 feet from the floor or working level.
SPS 332.33(2)(b) (b) Every tension weight exposed to contact shall be enclosed or securely fastened to the tension bar.
SPS 332.33(2)(c) (c) All springs shall be guarded or otherwise equipped to eliminate any hazard due to breakage of the spring or failure of the mounting.
SPS 332.33(3) (3)Guarding of hot pipes. All pipes carrying steam or other hot materials within 7 feet of the floor or working platform, that are exposed to contact, shall be covered with an insulating material, or guarded so that contact will not cause personal injury.
SPS 332.33(4) (4)Prevention of automatic restarting. On applications where injury to the operator might result if motors were to restart after power failures, machines shall be prevented from automatically restarting upon restoration of power.
SPS 332.33(5) (5)Maintenance. All equipment, machine tools, guards and power-driven machinery shall be operated and maintained in safe condition.
SPS 332.33 Note Note: For information regarding operation and maintenance of hoists, see ANSI/ASME standard B30.16 - Overhead Hoists (Underhung).
SPS 332.33 History History: Cr. Register, February, 1999, No. 518, eff. 3-1-99; cr. (4) and (5), Register, June, 2000, No. 534, eff. 7-1-00.
SPS 332.34 SPS 332.34 Woodworking machinery requirements [29 CFR 1910.213]. These department rules are in addition to 29 CFR 1910.213 (h):
SPS 332.34(1) (1)Limit stop. A stop shall be provided to prevent the forward travel of the blade beyond the front of the table.
SPS 332.34(2) (2)Return means. Every radial arm saw shall be equipped with a means to return the saw automatically to the back of the table when released at any point of its travel; the means shall prevent the saw from rebounding and shall not depend on fiber rope or cord for this function.
SPS 332.34 History History: Cr. Register, February, 1999, No. 518, eff. 3-1-99.
SPS 332.345 SPS 332.345 Commercial diving operations [29 CFR 1910.401]. Section 29 CFR 1910.401 (a) (2) (ii) is not included as part of this chapter.
SPS 332.345 History History: CR 01-062: cr. Register June 2002 No. 558, eff. 7-1-02.
SPS 332.35 SPS 332.35 Air contaminants [29 CFR 1910.1000].
SPS 332.35(1)(1) Substitution. In lieu of 29 CFR 1910.1000, July 1, 2003 edition, an employee's exposure to air contaminants shall be in accordance with the requirements of 29 CFR 1910.1000, July 1, 1992 edition.
SPS 332.35 Note Note: The requirements of 29 CFR 1910.1000, July 1, 1992 edition were first adopted by OSHA in 1989. Those requirements have been in effect under this chapter since April 1, 1991.
SPS 332.35 Note Note: Copies of the July 1, 1992, edition of 29 CFR 1910.1000 may be obtained from the Division of Industry Services at P.O. Box 7302, Madison, WI 53707-7302 or at telephone 608/266-3151 or 877/617-1565 or 411 (Telecommunications Relay).
SPS 332.35(2) (2)Addition. In addition to the requirements of 29 CFR 1910.1000, the employer shall implement the monitoring or measuring of any substance listed in Table Z-1-A where exposure at or above the time weighted average, short term exposure limit or ceiling limit is reasonably likely to occur.
SPS 332.35 History History: Cr. Register, February, 1999, No. 518, eff. 3-1-99; CR 04-009: am. (1) Register August 2004 No. 584, eff. 9-1-04.
SPS 332.36 SPS 332.36 General safety and health provisions [29 CFR 1926.20]. This department rule is in addition to 29 CFR 1926.20:
SPS 332.36(1) (1) No person may work on the surface of any structural member, floor, or other working platform which has become slippery from ice, snow, frost, paint or other cause, unless the surface is cleaned, sprinkled with sand or made nonslippery insofar as the nature of the work will permit.
SPS 332.36 History History: Cr. Register, February, 1999, No. 518, eff. 3-1-99.
SPS 332.37 SPS 332.37 Motor vehicles [29 CFR 1926.601]. Substitute the following wording for 29 CFR 1926.601 (b) (10):
SPS 332.37(1) (1) Trucks with dump bodies shall be equipped with positive means of support, permanently attached, and capable of being locked in position to prevent accidental lowering of the body while maintenance or inspection work is being done or when the vehicle is left unattended.
SPS 332.37 History History: Cr. Register, February, 1999, No. 518, eff. 3-1-99.
SPS 332.38 SPS 332.38 Specific excavation requirements [29 CFR 1926.651]. These department rules are in addition to 29 CFR 1926.651:
SPS 332.38(1) (1)Guarding. A standard railing as specified in 29 CFR 1926.502 (b) or other approved guard or barricade shall be provided at or near the edge of an excavation as soon as possible, except where the installation of the safeguard will interfere with the excavation or other work.
SPS 332.38(2) (2)Night guarding. All excavations to which persons may be exposed at night shall be provided with yellow warning lights placed at unbarricaded points and along the exposed side where the excavation adjoins a public thoroughfare or sidewalk.