SPS 366.0901(3) (3)Certification of occupancy required. The requirements in IEBC section 901.4 are not included as part of this code.
SPS 366.0901(4) (4)Standpipe systems. This is a department rule in addition to the requirements in IEBC section 912.2: Standpipe systems shall be provided in existing buildings and structures or portions of existing buildings and structures in accordance with chapter 9 of the IBC when existing buildings or structures that are greater than 60 feet in height are changed to include a Group R-1 or R-2 occupancy.
SPS 366.0901 History History: CR 06-120: cr. Register February 2008 No. 626, eff. 3-1-08; CR 10-103: am. (1) Register August 2011 No. 668, eff. 9-1-11.
SPS 366.0911 SPS 366.0911 Other requirements.
SPS 366.0911(1)(1)Elevator recall. This is a department rule in addition to the requirements in IEBC section 911: At least one existing elevator shall be provided with emergency recall operation and emergency in-car operation complying with ch. SPS 318 when an existing building or structure that is greater than 60 feet in height is changed to include a Group R-1 or R-2 occupancy.
SPS 366.0911(2) (2)Carbon monoxide alarms. This is a department rule in addition to the requirements in IEBC section 911: A building or a portion of a building changed to be or include a residential building as defined under s. 101.149 (1) (b), Stats., shall be provided with carbon monoxide alarms or detectors in accordance with s. SPS 362.1200.
SPS 366.0911 History History: CR 06-120: cr. Register February 2008 No. 626, eff. 3-1-08; EmR0826: emerg. renum. to be (1), cr. (1) (title) and (2), eff. 10-1-08; CR 08-085: renum. to be (1), cr. (1) (title) and (2) Register May 2009 No. 641, eff. 6-1-09; correction in (1), (2) made under s. 13.92 (4) (b) 7., Stats., Register December 2011 No. 672.
SPS 366.0912 SPS 366.0912 Plumbing. Substitute the following wording for the requirements in IEBC section 910: Where the occupant load of a story is increased by more than 20 percent, plumbing fixtures for the story shall be provided in quantities specified in the IBC based on the increased occupant load.
SPS 366.0912 History History: CR 06-120: cr. Register February 2008 No. 626, eff. 3-1-08; CR 10-103: renum. from Comm 66.0910 Register August 2011 No. 668, eff. 9-1-11.
SPS 366.1002 SPS 366.1002Fire Protection Systems. This is a department exception to the requirements in IEBC section 1002.3: An automatic sprinkler system is not required for additions to individual dwelling units within existing townhouses that are not already protected with an automatic sprinkler system.
SPS 366.1002 History History: CR 10-103: cr. Register August 2011 No. 668, eff. 9-1-11.
SPS 366.1101 SPS 366.1101 Historic buildings.
SPS 366.1101(1)(1)Scope. This is a department rule in addition to the requirements in IEBC section 1101.1: Any historic building is exempt from the energy requirements of this code.
SPS 366.1101(2) (2)Report. The requirements in IEBC section 1101.2 are not included as part of this code.
SPS 366.1101 History History: CR 06-120: cr. Register February 2008 No. 626, eff. 3-1-08; CR 10-103: renum. (1) to be (2), (2) to be Comm 66.1105 and am. (2) (title), cr. (1) Register August 2011 No. 668, eff. 9-1-11.
SPS 366.1105 SPS 366.1105 Exhibit buildings. These are department rules in addition to the requirements in IEBC section 1105: Historic buildings to be used as exhibit buildings shall comply with all of the following requirements:
SPS 366.1105(1) (1) The building shall be open to the public only under the supervision of a tour guide.
SPS 366.1105(2) (2) The building may not be lived in, slept in or worked in, except for the purpose of demonstrating to the public how people lived in a particular era.
SPS 366.1105(3) (3) Smoking is prohibited in the building.
SPS 366.1105(4) (4) Open flame equipment may not be used in the building, except for fire places and other mechanical equipment original to the building.
SPS 366.1105(5) (5) Fire extinguishers shall be installed in exhibit buildings and may be located in a nonconspicuous location but accessible to the occupants.
SPS 366.1105(6)(a)(a) At least one smoke detector shall be provided for each 1,200 square feet of floor area with a minimum of one smoke detector per floor level.
SPS 366.1105(6)(b)1.1. Except as specified in subd. 2., where electricity is provided in the exhibit building, the smoke detectors shall be connected to the electrical power.
SPS 366.1105(6)(b)2. 2. Where no electrical power is provided to an exhibit building, the smoke detectors shall be of a battery type.
SPS 366.1105(6)(b)3. 3. Smoke detectors shall be tested weekly.
SPS 366.1105(7) (7) Exhibit buildings provided with only one means of egress shall be restricted to a total capacity of 12 people, and not more than 6 people may be located above or below the first floor at any one time.
SPS 366.1105(8) (8) Stairways without 6-foot, 4-inch vertical headroom clearance shall have signs posted warning occupants of the headroom clearance available.
SPS 366.1105(9) (9) Exit signs shall be provided in accordance with the prevailing code in exhibit buildings occupied prior to ½-hour before sunrise and ½-hour after sunset and in all areas not provided with natural lighting.
SPS 366.1105 History History: CR 10-103: renum. from Comm 66.1101 (2) Register August 2011 No. 668, eff. 9-1-11; correction in (b) 1. made under s. 13.92 (4) (b) 7., Stats., Register August 2011 No. 668.
SPS 366.1301 SPS 366.1301 Applicability.
SPS 366.1301(1)(1) Substitute the following wording for the requirements in IEBC section 1301.2: The provisions of sections 1301.2.1 through 1301.2.5 shall apply to existing occupancies that will continue to be, or are proposed to be, in Groups A, B, E, F, M, R and S. These provisions shall not apply to buildings with occupancies in Group H or Group I.
SPS 366.1301(2) (2)Accessibility Requirements. Substitute the following wording for the requirements in IEBC section 1301.2.5: All portions of the buildings proposed for change of occupancy or being altered shall conform to the accessibility provisions of IEBC section 310.
SPS 366.1301(3) (3) The requirements in IEBC section 1301.3.2 are not included as part of this code.
SPS 366.1301 History History: CR 06-120: cr. Register February 2008 No. 626, eff. 3-1-08; CR 10-103: am. (title), renum. (2) to be (3), cr. (2) Register August 2011 No. 668, eff. 9-1-11.
SPS 366.1400 SPS 366.1400 Construction safeguards. The requirements in IEBC chapter 14 are not included as part of this code.
SPS 366.1400 History History: CR 10-103: cr. Register August 2011 No. 668, eff. 9-1-11.