ATCP 93.630 HistoryHistory: CR 17-092: cr. Register October 2019 No. 766, eff. 11-1-19; correction in (3) (h) made under s. 35.17, Stats., Register October 2019 No. 766. ATCP 93.640ATCP 93.640 Watercraft, snowmobile and ATV fueling. ATCP 93.640(1)(a)(a) General. Use of aboveground storage tank systems and fueling operations for watercraft, snowmobiles, and ATVs shall comply with NFPA 30A chapter 11, the requirements for dispensing systems in s. ATCP 93.615, and the requirements of this section, except as otherwise approved under this chapter. ATCP 93.640(1)(b)1.1. Aboveground tanks located on land shall be set back at least 10 feet from the ordinary high water mark of a navigable body of water. ATCP 93.640 NoteNote: The ordinary high water mark is determined by the county zoning department or the department of natural resources.
ATCP 93.640 NoteNote: The municipality in which the tank is located may have additional requirements for the siting of the tank.
ATCP 93.640(1)(b)2.2. Tanks shall follow the setback requirements of Table 93.615-A, except that there is no required separation between the tank and the dispenser if the tank is used exclusively for watercraft, snowmobile, or ATV fueling. ATCP 93.640(1)(c)1.1. Any dispenser used for a fueling operation above or within 100 feet of navigable water shall use a dry-break connection or a listed no-drip nozzle with automatic shutoff. ATCP 93.640(1)(c)2.2. A nozzle latch-open device may not be installed or used above or within 100 feet of navigable water. ATCP 93.640(1)(d)(d) Hose. Hose lengths more than 18 feet long, used for dispensing fuel, shall be reeled, racked, or otherwise protected from damage. ATCP 93.640(2)(2) Public access watercraft fueling. All piping systems and tank systems that are installed on or after November 1, 2019, for watercraft beyond the scope of sub. (4) shall comply with PEI RP1000 and sub. (3). ATCP 93.640 NoteNote: See s. ATCP 93.400 (3) for requirements relating to secondary containment for any underground piping, including any transition between aboveground and underground piping. ATCP 93.640(3)(3) Seasonal installation of a fueling system on a pier. ATCP 93.640(3)(a)(a) Plan requirements. Before installing a fueling system on a pier, plans shall be submitted for review and shall specify the requirements of this subsection. ATCP 93.640(3)(b)1.1. All connections that are broken shall use dry-break couplings listed for use with petroleum products. ATCP 93.640(3)(c)1.1. The owner shall develop and maintain on-site a written plan for safely draining the tank and pipe system before disassembly. ATCP 93.640(4)(a)(a) Aboveground tanks for watercraft fueling for noncommercial purposes at a private residence shall comply with the requirements for aboveground tanks in ss. ATCP 93.400 to 93.420, and this subsection.