ATCP 73.13 HistoryHistory: Cr. Register, June, 1985, No. 354, eff. 7-1-85; CR 08-073: renum. from HFS 197.08 Register January 2009 No. 637, eff. 2-1-09; correction in (4) (b) made under s. 13.92 (4) (b) 7., Stats., Register January 2009 No. 637; renum. from DHS 197.13 Register June 2016 No. 726.
ATCP 73.14ATCP 73.14Building safety.
ATCP 73.14(1)(1)Ventilation with space heaters.
ATCP 73.14(1)(a)(a) Any room where a gas space heater is located shall have a constant supply of fresh air through a permanent opening which shall not be closed. The size of the opening shall be at least one square inch for each 1,000 BTU per hour of the rated heating capacity of the heater, with a minimum of 10 square inches (65 square cm), or be so constructed that the air used in the combustion of the fuel is taken directly from the outside.
ATCP 73.14(1)(b)(b) The use of unvented gas, kerosene, oil or other fossil fuel space heaters is prohibited.
ATCP 73.14(2)(2)Smoke detection. Each bed and breakfast establishment shall be provided with an approved, listed, labeled, and operable smoke detector located inside each sleeping room and at the top of each stairway in a manner consistent with the manufacturer’s recommendations.
ATCP 73.14(3)(3)Window screens. All windows that can be opened in sleeping rooms shall be screened, using 16 mesh or finer material. Unless sleeping rooms are effectively air-conditioned, doors opening to the outside shall be similarly screened.
ATCP 73.14(4)(4)Fire extinguishers. Each bed and breakfast establishment shall be provided with at least one approved, listed and labeled fire extinguisher located near the sleeping rooms.
ATCP 73.14(5)(5)Ventilation and lighting. Rooms and areas used in conjunction with bed and breakfast establishments shall be ventilated and lighted as needed. The ventilation and lighting shall be effective under actual use conditions. Ventilating equipment and lighting fixtures shall be kept clean and in good repair.
ATCP 73.14(6)(6)Cooking in sleeping rooms. Cooking in sleeping rooms is prohibited.
ATCP 73.14 HistoryHistory: Cr. Register, June, 1985, No. 354, eff. 7-1-85; CR 08-073: renum. from HFS 197.09 Register January 2009 No. 637, eff. 2-1-09; renum. from DHS 197.14 Register June 2016 No. 726.
ATCP 73.145ATCP 73.145Carbon monoxide detectors.
ATCP 73.145(1)(1)Purpose. The purpose of this section is to implement the requirements of s. 97.625 (1) (am) and (1g), Stats., with respect to bed and breakfast establishments in a manner consistent with the standards in s. 101.149, Stats., and ss. SPS 321.097 and 362.0915.
ATCP 73.145 NoteNote: Section 97.625 (1) (am), Stats., was repealed by 2017 a. 330.
ATCP 73.145(2)(2)Definitions. In this section:
ATCP 73.145(2)(a)(a) “Carbon monoxide detector” means an electronic or battery-operated device that sounds an alarm when an unsafe level of carbon monoxide is in the air. A carbon monoxide detector is referred to as a “carbon monoxide alarm” by the Underwriters Laboratories, Inc., standards and ss. SPS 320.24 (2), 321.097 and 362.0915.
ATCP 73.145(2)(b)(b) “Fuel-burning appliance” means a device that is used or intended to be used in a residential building and burns fossil fuel or carbon based fuel where carbon monoxide is a combustion by-product. “Fuel-burning appliance” includes stoves, ovens, grills, clothes dryers, furnaces, boilers, water heaters, heaters, and fireplaces.
ATCP 73.145(2)(c)(c) “Inspection agent” means an individual holding certification under s. SPS 305.71 as an HVAC qualifier, who has been retained by the department or its agent to conduct the inspections of sealed combustion units required under this section and ss. 101.149 (5) (c) and 97.625 (1) (am), Stats.
ATCP 73.145 NoteNote: Sections 97.625 (1) (am) and 101.149 (5) (c), Stats., were repealed by 2017 a. 330.
ATCP 73.145(2)(d)(d) “Listed” means equipment that is tested by an independent testing agency and accepted by the department of safety and professional services.
ATCP 73.145(2)(e)(e) “Residential building” means a bed and breakfast establishment.
ATCP 73.145(2)(f)(f) “Sealed combustion appliance” means a listed fuel-burning appliance that acquires all air for combustion through a dedicated sealed passage from the outside to a sealed combustion chamber and for which all combustion products are vented to the outside through a separate dedicated sealed vent.
ATCP 73.145(2)(g)(g) “Sleeping area” means the area of the unit in which the bedrooms or sleeping rooms are located. Bedrooms or sleeping rooms separated by another use area such as a kitchen or living room are separate sleeping areas but bedrooms or sleeping rooms separated by a bathroom are not separate sleeping areas.
ATCP 73.145(2)(h)(h) “Unit” means a part of a residential building that is offered for pay as a sleeping place or sleeping accommodations to an individual or a group of individuals maintaining a common household to the exclusion of others. Every room or set of rooms that is rented out separately is a “unit.”
ATCP 73.145(3)(3)Installation requirements. The operator shall install carbon monoxide detectors in compliance with the requirements of s. 101.149 (2), Stats., and s. SPS 321.097 or 362.0915, as follows:
ATCP 73.145(3)(a)(a) Except as provided in par. (b) or in sub. (6), the operator shall install a carbon monoxide detector in each residential building in all of the following places not later than the date specified under par. (c):
ATCP 73.145(3)(a)1.1. In the basement of the building if the basement has a fuel-burning appliance.
ATCP 73.145(3)(a)2.2. Within 15 feet of each sleeping area of a unit that has a fuel-burning appliance.
ATCP 73.145(3)(a)3.3. Within 15 feet of each sleeping area of a unit that is immediately adjacent to a unit, located on the same floor level, that has a fuel-burning appliance.
ATCP 73.145(3)(a)4.4. In each room that has a fuel-burning appliance and that is not used as a sleeping area, not more than 75 feet from the fuel-burning appliance.
ATCP 73.145(3)(a)5.5. In each hallway leading from a unit that has a fuel-burning appliance, in a location that is within 75 feet from the unit, measured from the door of the unit along the hallway leading from the unit, except that, if there is no electrical outlet within this distance, the operator shall place the carbon monoxide detector at the closest available electrical outlet in the hallway.
ATCP 73.145(3)(b)(b) If a unit is not part of a multiunit building, the operator need not install more than one carbon monoxide detector in the unit.
ATCP 73.145(3)(c)1.1. Except as provided under subd. 2., the operator shall comply with the requirements of this subsection before a residential building is occupied.
ATCP 73.145(3)(c)2.2. The operator shall comply with the requirements of this subsection not later than April 1, 2010, if construction of the residential building was initiated before October 1, 2008, or if the department of safety and professional services approved the plans for the construction of the building under s. 101.12, Stats., before October 1, 2008.
ATCP 73.145(3)(d)(d) A carbon monoxide detector shall conform to UL 2034 and shall be listed and labeled identifying conformance to UL 2034. Carbon monoxide detectors and sensors as part of a gas detection or emergency signaling system shall conform to UL 2075 and shall be listed and labeled identifying conformance to UL 2075.
ATCP 73.145(3)(e)(e) The operator shall install every carbon monoxide detector required under this section according to the directions and specifications of the manufacturer of the carbon monoxide detector.
ATCP 73.145(3)(f)(f) Installation shall conform to the applicable requirements of s. SPS 321.097 or 362.0915.
ATCP 73.145(4)(4)Maintenance requirements. The operator shall maintain carbon monoxide detectors in compliance with the requirements of s. 101.149 (3), Stats., as follows:
ATCP 73.145(4)(a)(a) The operator shall reasonably maintain every carbon monoxide detector in the residential building in the manner specified in the instructions for the carbon monoxide detector.
ATCP 73.145(4)(b)(b) An occupant of a unit in a residential building may give the operator written notice that a carbon monoxide detector in the residential building is not functional or has been removed by a person other than the occupant. The operator shall repair or replace the nonfunctional or missing carbon monoxide detector within 5 days after receipt of the notice.
ATCP 73.145(5)(5)Tampering prohibited. Pursuant to s. 101.149 (4), Stats., no person may tamper with, remove, destroy, disconnect, or remove batteries from an installed carbon monoxide detector, except in the course of inspection, maintenance, or replacement of the detector.
ATCP 73.145(6)(6)Exception to installation requirements. The installation of carbon monoxide detectors is not required in a residential building if construction of the building was initiated before October 1, 2008, or if the department of safety and professional services approved the plans for the construction of the building under s. 101.12, Stats., and s. SPS 361.30, provided the building does not have an attached garage and any one of the following circumstances applies:
ATCP 73.145(6)(a)(a) The building does not have any fuel-burning appliances.
ATCP 73.145(6)(b)(b) All of the fuel-burning appliances in the building are of a sealed-combustion type and are covered by the manufacturers’ warranties against defects.
ATCP 73.145(6)(c)(c) All the fuel-burning appliances in the building are of a sealed-combustion type and are inspected in accordance with sub. (7) or (8) (b).
ATCP 73.145(7)(7)Inspection of sealed combustion appliances.
ATCP 73.145(7)(a)(a) The operator shall arrange for the inspection of every sealed combustion appliance and the vents and chimneys serving the appliances in any residential building where a carbon monoxide detector has not been installed.
ATCP 73.145(7)(b)(b) The inspection of a sealed combustion appliance, vents and chimneys shall satisfy the following requirements:
ATCP 73.145(7)(b)1.1. The inspection of the sealed combustion appliance, vents and chimneys shall be for the purpose of determining carbon monoxide emission levels.
ATCP 73.145(7)(b)2.2. The inspection shall be performed at least once a year.
ATCP 73.145(7)(b)3.3. The inspection shall be performed by an individual who holds certification issued under s. SPS 305.71 as an HVAC qualifier.
ATCP 73.145(7)(b)4.4. If upon inspection the carbon monoxide emissions from a fuel burning appliance, vent or chimney are not within the manufacturer’s specifications, the appliance may not be operated until it is repaired. If the appliance is repaired, it shall be inspected again before it is used.
ATCP 73.145(7)(b)5.5. The individual inspecting the sealed combustion appliance shall prepare a written, dated, and signed report identifying the level of carbon monoxide emissions and certifying whether or not carbon monoxide emissions are within the manufacturer’s specifications, which the operator shall retain for review by the department or its agent.
ATCP 73.145(8)(8)Inspections and enforcement by department.
ATCP 73.145(8)(a)(a) The department or its agent shall conduct regular inspections of facilities to ensure compliance with s. 101.149 (2) and (3), Stats., and this section.
ATCP 73.145(8)(b)(b) If, upon inspection, the department or its agent determines that a sealed combustion appliance has not been inspected and certified as meeting the manufacturer’s specifications for carbon monoxide emissions, as required under sub. (7), the department or agent shall order the operator to have an inspection conducted within 30 days. If the department or its agent has not received an inspection report as required under sub. (7) (b) 5. within 30 days, the department or agent shall arrange for an inspection agent to conduct an inspection that satisfies the requirements under sub. (7) (b), and the operator shall pay all of the costs associated with the inspection.
ATCP 73.145(8)(c)(c) Pursuant to s. 101.149 (8) (a), Stats., if the department determines after an inspection of a residential building that the operator has violated the installation requirements under sub. (3) or the maintenance requirements under sub. (4), the department shall issue an order requiring the operator to correct the violation within 5 days or within such shorter period as the department determines is necessary to protect public health and safety. As required under s. 101.149 (8) (a), Stats., if the operator does not correct the violation within the time required, the operator shall forfeit $50 for each day of violation occurring after the date on which the department finds that the violation was not corrected. Pursuant to s. 101.149 (8) (b), Stats., if a person is charged with more than one violation of sub. (3) or (4) arising out of an inspection of a single residential building, those violations shall be counted as a single violation for the purpose of determining the amount of a forfeiture.
ATCP 73.145(8)(d)(d) A person who violates sub. (5) is subject to criminal penalties under s. 101.149 (8) (c), Stats.
ATCP 73.145 HistoryHistory: EmR1004: emerg. cr. eff. 4-1-10; CR 10-015: cr. Register August 2010 No. 656, eff. 9-1-10; corrections in (1), (2) (a), (c), (d), (3) (intro.), (c) 2., (f), (6) (intro.), (7) (b) 3. made under s. 13.92 (4) (b) 6., 7., Stats., Register January 2012 No. 673; renum. from DHS 197.145 Register June 2016 No. 726; correction in (1), (2) (c) made under s. 13.92 (4) (b) 7., Stats., Register June 2016 No. 726; correction in (1), (2) (a), (3) (intro.), (f) Register November 2018 No. 755.
ATCP 73.15ATCP 73.15Maintenance.
ATCP 73.15(1)(1)General. Every bed and breakfast establishment shall be maintained and equipped in a manner conducive to the health, comfort, and safety of its guests.
ATCP 73.15(2)(2)Rooms. The floors, walls and ceilings of all rooms shall be maintained in a clean and sanitary condition and in a good state of repair.
ATCP 73.15(3)(3)Buildings and grounds. Buildings and grounds shall be maintained in a clean, neat condition, free from refuse and other objectionable conditions or hazards. The exterior of all buildings shall be well-maintained and kept in good repair.
ATCP 73.15(4)(4)Insect and rodent control. Effective measures intended to minimize the presence of rodents, flies, cockroaches, and other insects on the premises shall be employed. The premises shall be kept in a condition which will prevent the harborage or feeding of insects or rodents.
ATCP 73.15 HistoryHistory: Cr. Register, June, 1985, No. 354, eff. 7-1-85; CR 08-073: renum. from HFS 197.10 Register January 2009 No. 637, eff. 2-1-09; renum. from DHS 197.15 Register June 2016 No. 726.
Loading...
Loading...
Published under s. 35.93, Stats. Updated on the first day of each month. Entire code is always current. The Register date on each page is the date the chapter was last published.