SPS 316.090 NoteNote: This section is shown as amended eff. 9-1-26 by CR 26-016. Prior to 9-1-1-26 it reads:
SPS 316.090 NoteSPS 316.090 Introduction. The requirements specified in 2011 and 2017 NEC 90.1, NEC 90.2, and NEC 90.4 are not included as part of this chapter.
SPS 316.090 HistoryHistory: CR 08-047: cr. Register February 2009 No. 638, eff. 3-1-09; CR 13-042: am. (title) Register November 2013 No. 695, eff. 12-1-13; CR 16-093: am. Register June 2018 No. 750, eff. 8-1-18; CR 26-016: am. Register June 2026 No. 846, eff. 9-1-26.
SPS 316.100SPS 316.100Definitions.
SPS 316.100(1)(1)Additions. The following are department definitions in addition to the definitions in NEC 100:
SPS 316.100(1)(a)(a) “Floors” means stories as specified in chs. SPS 361 to 366.
SPS 316.100(1)(b)(b) “Nonrated construction” means Types III, IV and V construction in accordance with chs. SPS 361 to 366 and is considered to be nonfire-rated for the purposes of this chapter.
SPS 316.100(1)(c)(c) “Private sewage system” has the meaning specified under s. 145.01 (12), Stats.
SPS 316.100 NoteNote: Under s. 145.01 (12), Stats., “private sewage system” means a sewage treatment and disposal system serving a single structure with a septic tank and soil absorption field located on the same parcel as the structure. This term also means an alternative sewage system approved by the department including a substitute for the septic tank or soil absorption field, a holding tank, a system serving more than one structure or a system located on a different parcel than the structure. A private sewage system may be owned by the property owner or a special purpose district.
SPS 316.100(2)(2)Substitutions. The following department definition is a substitution for the respective definition in NEC 100: “Special permission” means a petition for variance in accordance with s. SPS 316.005.
SPS 316.100 NoteNote: Sub. (2) is shown as amended eff. 9-1-26 by CR 26-016. Prior to 9-1-26 it reads:
SPS 316.100 Note(2) Substitutions. The following department definition is a substitution for the respective definition in 2011 and 2017 NEC 100: “Special permission”means a petition for variance in accordance with s. SPS 316.005.
SPS 316.100 NoteNote: See chs. SPS 361 to 366 for fire-resistance standards.
SPS 316.100 HistoryHistory: CR 08-047: cr. Register February 2009 No. 638, eff. 3-1-09; correction in (1) (a), (b), (c), (2) (b) made under s. 13.92 (4) (b) 6., 7., Stats., Register December 2011 No. 672; CR 16-093: r. (1) (a), renum. (1) (b) to (d) to (1) (a) to (c), (2) (intro.), (b) consolidated and renum. to (2) and am., r. (2) (a) Register June 2018 No. 750, eff. 8-1-18; CR 26-016: am. (2) Register June 2026 No. 846, eff. 9-1-26.
SPS 316.110SPS 316.110Examination, identification, installation, use, and listing of equipment.
SPS 316.110(1)(1)Substitute the following wording for the requirements in NEC 110.3 (B): Equipment that is listed, labeled, or both, or identified for a use shall be installed and used in accordance with any instructions included in the listing, labeling, or identification provided the instructions, listing, or labeling do not conflict with this chapter.
SPS 316.110 NoteNote: Sub. (1) is shown as amended eff. 9-1-26 by CR 26-016. Prior to 9-1-26 it reads:
SPS 316.110 Note(1) Substitute the following wording for the requirements in 2011 NEC 110.3 (B): Listed or labeled equipment shall be installed or used, or both, in accordance with any instructions included in the listing or labeling, provided the instructions, listing, or labeling do not conflict with this chapter.
SPS 316.110(2)(2)This is a department exception to the requirements of NEC 110.3 (C): Exception: As provided under s. SPS 316.022 (1), product testing and evaluation may be conducted by a qualified independent third party, including a nationally recognized testing laboratory or a professional engineer registered in the state of Wisconsin.
SPS 316.110 NoteNote: Sub. (2) is shown as amended eff. 9-1-26 by CR 26-016. Prior to 9-1--26 it reads:
SPS 316.110 Note(2) This is a department exception to the requirements of 2017 NEC 110.3 (C): Exception: As provided under s. SPS 316.022 (1), product testing and evaluation may be conducted by a qualified independent third party, including a nationally recognized testing laboratory or a professional engineer.
SPS 316.110 HistoryHistory: CR 08-047: cr. Register February 2009 No. 638, eff. 3-1-09; CR 13-042: am. Register November 2013 No. 695, eff. 12-1-13; CR 16-093: r. and recr. Register June 2018 No. 750, eff. 8-1-18; correction in numbering made under s. 13.92 (4) (b) 1. Register June 2018 No. 750; CR 26-016: am. (1), (2) Register June 2026 No. 846, eff. 9-1-26.
SPS 316.210SPS 316.210Branch circuits.
SPS 316.210(1)(1)Ground-fault circuit-interrupter protection for personnel.
SPS 316.210(1)(a)(a) Substitute the following wording for NEC 210.8 (A): All 125−volt, single−phase, 15− and 20−ampere receptacles installed in the following locations shall have ground−fault circuit interrupter protection for personnel:
SPS 316.210(1)(b)(b) Substitute the following wording for NEC 210.8 (A) (5): Unfinished portions or areas of the basement not intended as habitable rooms.
SPS 316.210(1)(c)(c) The requirements in NEC 210.8 (A) (7) are not included as part of this chapter.
SPS 316.210(1)(d)(d) The requirements in NEC 210.8 (D) (8), (9), (10), and (11) are not included as part of this chapter.
SPS 316.210(1)(e)(e) The requirements in NEC 210.8 (F) are not included as part of this chapter.
SPS 316.210(2)(2)Arc-fault circuit-interrupter protection. The requirements in NEC 210.12 (E) are not included as part of this chapter.
SPS 316.210(3)(3)Dwelling unit receptacle outlets.
SPS 316.210(3)(a)(a) Substitute the following wording for NEC 210.52 (C) (2): At least one receptacle shall be installed at each island and peninsular countertop space with a long dimension of 600 millimeters (24 inches) or greater and a short dimension of 300 millimeters (12 inches) or greater. A peninsular countertop is measured from the connected perpendicular wall.
SPS 316.210(3)(b)(b) The following are department exceptions to the requirements of NEC 210.52 (C) (3):
SPS 316.210(3)(b)1.1. In construction for the physically impaired receptacles may be mounted below the countertop or work surface. Receptacles mounted below a countertop or work surface shall be mounted not more than 300 millimeters (12 inches) below the countertop or work surface and may not be located where the countertop or work surface extends more than 150 millimeters (6 inches) beyond its support base.
SPS 316.210(3)(b)2.2. On island and peninsular countertops or work surface where the surface is flat across its entire surface (no backsplashes, dividers, etc.) and there are no means to mount a receptacle within 500 millimeters (20 inches) above the countertop or work surface, such as an overhead cabinet receptacles may be mounted below the countertop or work surface. Receptacles mounted below a countertop or work surface shall be mounted not more than 300 millimeters (12 inches) below the countertop or work surface and may not be located where the countertop or work surface extends more than 150 millimeters (6 inches) beyond its support base.
SPS 316.210 NoteNote: This section is shown as repealed and recreated eff. 9-1-26 by CR 26-016. Prior to 9-1-26 it reads:
SPS 316.210 NoteSPS 316.210 Branch circuits. (1) Ground-fault circuit-interrupter protection for personnel. (a) The requirements in 2017 NEC 210.8 (A) (7) do not apply to sinks located in kitchens.
SPS 316.210 Note(b) The requirements in 2017 NEC 210.8 (A) (9) and (10) are not included as part of this chapter.
SPS 316.210 Note(c) Substitute the following wording for 2017 NEC 210.8 (B): All 125-volt, single-phase, 15- and 20-ampre receptacles installed in the following locations shall have ground-fault circuit interrupter protection for personnel.
SPS 316.210 Note(d) This is a department exception to the requirements in 2011 NEC 210.8 (A) and 2017 NEC 210.8 (A) and (B): Exception: Ground-fault circuit-interrupter protection shall not be required for a single receptacle providing power for sump, sewage, or condensate pumps where an accessible ground-fault circuit-interrupter protected receptacle is located within 900 mm (3 ft) of the non-GFCI protected receptacle.
SPS 316.210 Note(2) Branch circuits required. (a) This is a department rule in addition to the requirements of 2011 NEC 210.11: Where an air conditioner sleeve is provided in a building wall, a receptacle outlet shall be located within 4 feet of the sleeve. If a circuit is not run to the outlet, a raceway shall be provided. When the air conditioner is installed in the sleeve, it shall be supplied by an individual branch circuit. A receptacle outlet installed for an air conditioner may not be counted as one of the receptacles required by NEC 210.52 (A).
SPS 316.210 Note(b) The requirements in 2017 NEC 210.11 (C) (4) are not included as part of this chapter.
SPS 316.210 Note(3) Arc-fault circuit-interrupter protection. The requirements in 2017 NEC 210.12 (A) do not apply to kitchens.
SPS 316.210 Note(4) Branch circuit extensions or modifications — dwelling units and dormitory units. The requirements in 2011 NEC 210.12 (B) and 2017 NEC 210.12 (D) are not included as part of this chapter.
SPS 316.210 Note(5) Lighting outlets required. Substitute the following wording for 2011 NEC 210.70 (A) (1): At least one wall switch-controlled lighting outlet shall be installed in every habitable room, kitchen, and bathroom.
SPS 316.210 Note(6) Countertop receptacles. The requirements in 2011 NEC 210.52 (A) (4) are not included as part of this chapter.
SPS 316.210 Note(7) Garages. Substitute the following wording for 2017 NEC 210.52 (G) (1): In each attached garage and in each detached garage with electric power.
SPS 316.210 Note(8) Meeting rooms. The requirements in 2017 NEC 210.71 do not apply to this chapter.
SPS 316.210 HistoryHistory: CR 08-047: cr. Register February 2009 No. 638, eff. 3-1-09; CR 13-042: r. (2) (a), (c), renum. (2) (b) to (2), r. and recr. (4), renum. (6) to (5), cr. (6) Register November 2013 No. 695, eff. 12-1-13; CR 16-093: r. and recr. (1) to (6), cr. (7), (8) Register June 2018 No. 750, eff. 8-1-18; CR 26-016: r. and recr. Register June 2026 No. 846, eff. 9-1-26.
SPS 316.220SPS 316.220Branch-circuit, feeder and service calculations. Substitute the following wording for NEC 220.5 (C): The floor area for each floor shall be calculated from the outside dimensions of the building, dwelling unit, or other area involved. For dwelling units, the calculated floor area shall not include open porches, garages, or unfinished areas not adaptable for future use as a habitable room or occupiable space.
SPS 316.220 NoteNote: This section is shown as repealed and recreated eff. 9-1-26 by CR 26-016. Prior to 9-1-26 it reads:
SPS 316.220 NoteSPS 316.220 Branch-circuit, feeder and service calculations. (1) General. This is a department exception to the requirements in 2011 NEC 220.10: Circuit load calculations may use unit load values lower than those identified in NEC Table 220.12 for lighting loads calculated using the maximum electrical energy conservation values specified under ch. SPS 363 for public buildings and places of employment.
SPS 316.220 Note(2) Exception. This is a department exception to the requirements in 2011 and 2017 NEC 220.40: Exception: Under the supervision of a Wisconsin professional engineer, architect or designer of electrical systems, the feeder or service size may be computed using diversity factors or historical data of a similar type of building, other than one- and 2-family dwelling units.
SPS 316.220 HistoryHistory: CR 08-047: cr. Register February 2009 No. 638, eff. 3-1-09; CR 13-042: r. and recr. (1) Register November 2013 No. 695, eff. 12-1-13; CR 16-093: am. (1), (2) Register June 2018 No. 750, eff. 8-1-18; CR 26-016: r. and recr. Register June 2026 No. 846, eff. 9-1-26.
SPS 316.225SPS 316.225Outside branch circuits and feeders.
SPS 316.225(1)(1)Number of supplies. This is a department rule in addition to the requirements in NEC 225.30: Multi−occupancy buildings or structures may have one set of branch circuit conductors installed from a dwelling unit to the second building or structure’s respective occupied space.
SPS 316.225(2)(2)Location. The following are department rules in addition to the requirements of NEC 225.31:
SPS 316.225(2)(a)(a) This is a department rule in addition to the requirements of NEC 225.31 (B): Raceways containing feeder or branch circuit conductors, or feeder or branch circuit cables not contained within a raceway, may not extend longer than 8 feet into a building to the disconnect or the first disconnect of a group of disconnects as permitted by NEC 225.33. The raceways, cables, or conductors shall be considered to have entered the building at the point where they pass through the outer surface of the building exterior, except as permitted by NEC 230.6.
SPS 316.225(2)(b)(b) Where the disconnecting means is installed outside of a building or structure the disconnecting means shall be located not more than 30 feet from and within sight of the building or structure that the disconnect serves.
SPS 316.225(3)(3)Emergency disconnects. The requirements of NEC 225.41 are not included as part of this chapter.
SPS 316.225 NoteNote: This section is shown as repealed and recreated eff. 9-1-26 by CR 26-016. Prior to 9-1-26 it reads:
SPS 316.225 NoteSPS 316.225 Outside branch circuits and feeders. (1) Clearances from buildings for conductors not over 600 volts. Substitute the following wording for 2011 NEC 225.19 (A) Exception No. 4: The requirement for maintaining the vertical clearance 3 feet from the edge of the roof does not apply to the final conductor span to the building.
SPS 316.225 Note(2) Number of supplies. The following are department rules in addition to the requirements in 2011 and 2017 NEC 225.30:
SPS 316.225 Note(a) For the purpose of this section, multiple feeders that are supplied from the same distribution point, having a total rating of 300 amperes or more, and that supply not more than 6 disconnecting means grouped at the same location shall be considered as one supply.
SPS 316.225 Note(b) Multi-occupancy buildings or structures may have one set of branch circuit conductors installed from a dwelling unit to the second building or structure’s respective occupied space.
SPS 316.225 Note(3) Location. This is a department rule in addition to the requirements of 2011 and 2017 NEC 225.32: The building disconnect required by NEC 225.31 shall be located in accordance with s. SPS 316.230 (3).
SPS 316.225 NoteNote: See ch. PSC 114 regarding clearances of conductors of over 600 volts and for prohibition of constructing dwellings under or near overhead lines.
SPS 316.225 Note(4) Clearances over roadways, walkways, rail, water and open land. Substitute the following wording for the note to 2011 and 2017 NEC 225.60 (C): Note: For clearances of conductors of over 600 volts, see ch. PSC 114.
SPS 316.225 Note(6) Clearances over buildings and other structures. Substitute the following wording for the note to 2011 and 2017 NEC 225.61 (B): Note: See ch. PSC 114 regarding clearances of conductors of over 600 volts and for prohibition of constructing dwellings under or near overhead lines.
SPS 316.225 HistoryHistory: CR 08-047: cr. Register February 2009 No. 638, eff. 3-1-09; correction in (4) made under s. 13.92 (4) (b) 7., Stats., Register December 2011 No. 672; CR 13-042: r. (1), renum. (2) to (5) to (1) to (4) and am. (2) (a) Register November 2013 No. 695, eff. 12-1-13; CR 16-093: am. (1), (2) (intro.), (3), (4), (6) Register June 2018 No. 750, eff. 8-1-18; CR 26-016: r. and recr. Register June 2026 No. 846, eff. 9-1-26.
SPS 316.230SPS 316.230Services.
SPS 316.230(1)(1)Number of services.
SPS 316.230(1)(a)(a) This is a department informational note to be used under NEC 230.2 (intro.): Note: It is recommended that the electric utility or cooperative supplying electric current be contacted prior to service equipment installations for any special requirements.
SPS 316.230 NoteNote: Par. (a) is shown as amended eff. 9-1-26 by CR 26-016. Prior to 9-1-26 it reads:
SPS 316.230 Note(a) This is a department informational note to be used under 2011 and 2017 NEC 230.2 (intro.): Note: It is recommended that the electric utility or cooperative supplying electric current be contacted prior to service equipment installations for any special requirements.
SPS 316.230(1)(b)(b) Substitute the following wording for NEC 230.2 (B) (2): Two or more service drops or laterals for the same class of service if located more than 150 feet apart, measured in a straight line, and provided that all electrical wiring supplied by each service has no common raceway or connection with any other service.
SPS 316.230(1)(c)(c) This is a department rule in addition to the requirements of 2011 NEC 230.2 (B): For a building which is not more than 3 stories in height and which contains only 3 or more attached, vertically separated, side-by-side, or back-to-back dwelling units, with each dwelling unit served by an individual exterior exit within 6 feet of the exit discharge grade, a separate service drop or lateral shall be permitted for each 2 attached units.
SPS 316.230 NoteNote: Par. (c) is repealed eff. 9-1-26 by CR 26-016.
SPS 316.230(2)(2)Number of service-entrance conductor sets. The requirements specified in 2011 and 2017 NEC 230.40 Exception No. 3 are not included as part of this chapter.
SPS 316.230 NoteNote: Sub. (2) is repealed eff. 9-1-26 by CR 26-016.
SPS 316.230(3)(3)Service equipment — disconnecting means.
SPS 316.230(3)(a)(a) General. This is a department rule in addition to the requirements of 2011 and 2017 NEC 230.70: Disconnecting means shall be provided to disconnect the utility wiring from the premises wiring at any point where utility wiring terminates and premises wiring extends overhead or underground to more than one building or structure.
SPS 316.230 NoteNote: Par. (a) is repealed eff. 9-1-26 by CR 26-016.
SPS 316.230(3)(b)(b) Location. This is a department rule in addition to the requirements of NEC 230.70 (A): Raceways containing service conductors or cables, or service entrance cable not contained within a raceway, may not extend longer than 8 feet into a building to the service disconnect or the first service disconnect of a group of disconnects as permitted by NEC 230.71. The raceways or conductors shall be considered to have entered the building at the point where they pass through the outer surface of the building exterior, except as permitted by NEC 230.6.
SPS 316.230 NoteNote: Par. (b) is shown as amended eff. 9-1-26 by CR 26-016. Prior to 9-1-26 it reads:
SPS 316.230 Note(b) Location. This is a department rule in addition to the requirements of 2011 and 2017 NEC 230.70 (A): Raceways containing service conductors or cables, or service entrance cable not contained within a raceway, may not extend longer than 8 feet into a building to the service disconnect or the first service disconnect of a group of disconnects as permitted by NEC 230.71. The raceways or conductors shall be considered to have entered the building at the point where they pass through the outer surface of the building exterior, except as permitted by NEC 230.6.
SPS 316.230(3)(c)(c) Outside disconnects. Where the service disconnecting means is installed outside of a building or structure, the service disconnecting means shall be no more than 30 feet and within sight from the building or structure it serves.
SPS 316.230 NoteNote: Par. (c) is created eff. 9-1-26 by CR 26-016.
SPS 316.230(4)(4)Emergency disconnects. The requirements of NEC 230.85 are not included as part of this chapter.