SPS 316.225(2)(b)
(b) Multi-occupancy buildings or structures may have one set of branch circuit conductors installed from a dwelling unit to the second building or structure's respective occupied space.
SPS 316.225(3)
(3)
Location. This is a department rule in addition to the requirements of 2011 and 2017 NEC 225.32: The building disconnect required by NEC 225.31 shall be located in accordance with s.
SPS 316.230 (3).
SPS 316.225 Note
Note: See ch.
PSC 114 regarding clearances of conductors of over 600 volts and for prohibition of constructing dwellings under or near overhead lines.
SPS 316.225(4)
(4)
Clearances over roadways, walkways, rail, water and open land. Substitute the following wording for the note to 2011 and 2017 NEC 225.60 (C): Note: For clearances of conductors of over 600 volts, see ch.
PSC 114.
SPS 316.225(6)
(6)
Clearances over buildings and other structures. Substitute the following wording for the note to 2011 and 2017 NEC 225.61 (B): Note: See ch.
PSC 114 regarding clearances of conductors of over 600 volts and for prohibition of constructing dwellings under or near overhead lines.
SPS 316.225 History
History: CR 08-047: cr.
Register February 2009 No. 638, eff. 3-1-09; correction in (4) made under s.
13.92 (4) (b) 7., Stats.,
Register December 2011 No. 672;
CR 13-042: r. (1), renum. (2) to (5) to (1) to (4) and am. (2) (a)
Register November 2013 No. 695, eff. 12-1-13;
CR 16-093: am. (1), (2) (intro.), (3), (4), (6)
Register June 2018 No. 750, eff. 8-1-18
.
SPS 316.230(1)(a)
(a) This is a department informational note to be used under 2011 and 2017 NEC 230.2 (intro.): Note: It is recommended that the electric utility or cooperative supplying electric current be contacted prior to service equipment installations for any special requirements.
SPS 316.230(1)(b)
(b) Substitute the following wording for NEC 230.2 (B) (2): Two or more service drops or laterals for the same class of service if located more than 150 feet apart, measured in a straight line, and provided that all electrical wiring supplied by each service has no common raceway or connection with any other service.
SPS 316.230(1)(c)
(c) This is a department rule in addition to the requirements of 2011 NEC 230.2 (B): For a building which is not more than 3 stories in height and which contains only 3 or more attached, vertically separated, side-by-side, or back-to-back dwelling units, with each dwelling unit served by an individual exterior exit within 6 feet of the exit discharge grade, a separate service drop or lateral shall be permitted for each 2 attached units.
SPS 316.230(2)
(2)
Number of service-entrance conductor sets. The requirements specified in 2011 and 2017 NEC 230.40 Exception No. 3 are not included as part of this chapter.
SPS 316.230(3)(a)
(a)
General. This is a department rule in addition to the requirements of 2011 and 2017 NEC 230.70: Disconnecting means shall be provided to disconnect the utility wiring from the premises wiring at any point where utility wiring terminates and premises wiring extends overhead or underground to more than one building or structure.
SPS 316.230(3)(b)
(b)
Location. This is a department rule in addition to the requirements of 2011 and 2017 NEC 230.70 (A): Raceways containing service conductors or cables, or service entrance cable not contained within a raceway, may not extend longer than 8 feet into a building to the service disconnect or the first service disconnect of a group of disconnects as permitted by NEC 230.71. The raceways or conductors shall be considered to have entered the building at the point where they pass through the outer surface of the building exterior, except as permitted by NEC 230.6.
SPS 316.230(4)
(4)
Rating of service disconnecting means – 2011 NEC. This is a department rule in addition to the requirements of 2011 NEC 230.79:
SPS 316.230(4)(a)
(a) Two- or multi-family dwellings. Except as provided in par.
(b), for 2-family or multi-family dwellings, the service equipment shall have a rating of not less than 150 amperes, 3-wire or 4-wire. Where the combined rating of all service disconnecting means is 150 amperes or larger, the service or feeder equipment rating for each dwelling unit shall have a rating of not less than 60 amperes.
SPS 316.230(4)(b)
(b) Exception. Service equipment having a rating of not less than 100 amperes, 3-wire or 4-wire, may be installed in an existing 2-family dwelling only where both of the following conditions are complied with:
SPS 316.230(4)(b)1.
1. The load computed in accordance with NEC 220 does not exceed 80 amperes.
SPS 316.230(4)(b)2.
2. Specific written approval is granted by the municipal inspection department having jurisdiction.
SPS 316.230(5)
(5)
Rating of service disconnecting means — 2017 NEC. This is a department rule in addition to the requirements of 2017 NEC 230.79: For 2-family or multi-family dwellings, the service equipment shall have a rating of not less than 150 amperes, 3-wire or 4-wire.
SPS 316.230 History
History: CR 08-047: cr.
Register February 2009 No. 638, eff. 3-1-09;
CR 13-042: renum. (3) to (3) (b) and am. (3) (b) (title), renum. (4) to (3) (a) and am. (3) (title), (3) (a) (title), renum. (5) to (4)
Register November 2013 No. 695, eff. 12-1-13;
CR 16-093: am. (1) (a) (intro.), (c), (2), (3) (a), (b), (4) (intro.), cr. (5)
Register June 2018 No. 750, eff. 8-1-18.
SPS 316.240
SPS 316.240 Overcurrent protection. The requirements in 2017 NEC 240.67 do not apply to this chapter.
SPS 316.240 History
History: CR 16-093: cr.
Register June 2018 No. 750, eff. 8-1-18.
SPS 316.250(1)(1)
Supplemental electrode required. The exception in 2011 and 2017 NEC 250.53 (A) (2) is not included as part of this chapter.
SPS 316.250(2)
(2)
Supplemental electrode. This is a department rule in addition to the requirements in 2011 and 2017 NEC 250.53 (A) (3): A single electrode consisting of a rod, pipe or plate shall be augmented by one additional electrode of any of the types in NEC 250.52 (A) (4) to (A) (8).
SPS 316.250(3)
(3)
Types of equipment grounding conductors. This is a department rule in addition to the requirements of 2017 NEC 250.118: A metallic raceway installed in direct contact with earth, in concrete slabs or floors poured on earth, or in exterior concrete walls below grade shall be augmented with a supplemental equipment grounding conductor identified in NEC 250.118 (1). This supplemental conductor shall be sized in accordance with NEC 250.122. An aluminum equipment grounding conductor used for this purpose shall be insulated.
SPS 316.250 History
History: CR 08-047: cr.
Register February 2009 No. 638, eff. 3-1-09;
CR 13-042: r. and recr.
Register November 2013 No. 695, eff. 12-1-13;
CR 16-093: am. (1), (2), cr. (3)
Register June 2018 No. 750, eff. 8-1-18.
SPS 316.300(1)(1)
Electrical requirements for private onsite wastewater treatment systems. These department rules apply to private onsite wastewater treatment systems and are in addition to the requirements of 2011 and 2017 NEC 300:
SPS 316.300(1)(a)
(a) Wiring methods. All effluent pump circuit wiring shall comply with the approved wiring methods as specified in NEC 300 and all of the following requirements:
SPS 316.300(1)(a)1.
1. Effluent pumps shall be supplied by a separate branch circuit supplying no other loads.
SPS 316.300(1)(a)3.
3. All aboveground cables and flexible cords shall be enclosed to protect against physical damage.
SPS 316.300(1)(a)4.
4. The neutral conductor may not be common to both alarm and pump circuits.
SPS 316.300(1)(a)5.
5. Where the wiring enclosure for the alarm and pump circuit is located outside the pump chamber, any openings into the pump chamber for circuit wiring shall be sealed or plugged to prevent the passage of gas or vapor into the wiring enclosure.
SPS 316.300 Note
Note: This prohibits use of a multi-wire branch circuit to supply both the alarm and pump.
SPS 316.300 Note
Note: See NEC 430.102 for location of disconnects.
SPS 316.300(1)(b)
(b) Ground-fault circuit protection. A single receptacle located at the pump chamber that has an alarm or pump connected to it does not require ground-fault circuit-interrupter protection.
SPS 316.300(2)(a)
(a) The requirements specified in 2011 NEC 300.4 (D) are not included as part of this chapter.
SPS 316.300(2)(b)
(b) This is a department exception in addition to the exceptions under 2017 NEC 300.4 (D): Exception No. 4: This distance does not need to be maintained within 8 inches of a device, junction box, splice, or termination point.
SPS 316.300 History
History: CR 08-047: cr.
Register February 2009 No. 638, eff. 3-1-09:
CR 13-042: cr. (1) (a) 5.
Register November 2013 No. 695, eff. 12-1-13;
CR 16-093: am. (1) (title), (intro.), renum. (2) to (2) (a) and am., cr. (2) (b)
Register June 2018 No. 750, eff. 8-1-18.
SPS 316.310(1)(1)
This is a department rule in addition to the requirements in 2011 NEC 310.15 (B) (3) (a): The derating factors shown in NEC Table 310.15 (B) (3) (a) do not apply to branch circuits supplying an individual dwelling unit except under the following conditions: Exception No. 6: The derating factors shown in NEC Table 310.15 (B) (3) (a) do not apply to branch circuits supplying an individual dwelling unit except under the following conditions:
SPS 316.310(1)(a)
(a) Where more than two NM cables containing two or more current-carrying conductors are installed, without maintaining spacing between the cables, through the same opening in wood framing that is to be fire- or draft-stopped using thermal insulation, caulk or sealing foam, the allowable ampacity of each conductor shall be adjusted in accordance with Table 310.15 (B) (3) (a) and the provisions of 310.15 (A) (2) shall not apply.
SPS 316.310(1)(b)
(b) Where more than two NM cables containing two or more current-carrying conductors are installed in contact with thermal insulation without maintaining spacing between cables, the allowable ampacity of each conductor shall be adjusted in accordance with Table 310.15 (B) (3) (a).
SPS 316.310(2)
(2) This is a department rule in addition to the requirements in 2017 NEC 310.15 (B) (3) (a): The derating factors shown in NEC Table 310.15 (B) (3) (a) do not apply to branch circuits supplying an individual dwelling unit.
SPS 316.310 History
History: CR 08-047: cr.
Register February 2009 No. 638, eff. 3-1-09;
CR 13-042: am. (title), (intro.)
Register November 2013 No. 695, eff. 12-1-13; corrections in (intro.), (1), (2) under s.
13.92 (4) (b) 7. Register November 2013 No. 695;
CR 16-093: renum. (intro.) to (1) (intro.), cr. (2)
Register June 2018 No. 750, eff. 8-1-18.
SPS 316.312
SPS 316.312 Cabinets, cutout boxes and meter socket enclosures. SPS 316.312(1)(1)
Cables. Substitute the following wording for 2011 and 2017 NEC 312.5 (C) Exception (intro.): Exception: Cables with entirely nonmetallic sheaths may enter an enclosure through one or more nonflexible raceways of not less than 12 inches and not more than 10 feet in length, provided all of the following conditions are met:
SPS 316.312(2)
(2)
Omission. The requirements specified in 2011 NEC 312.5 (C) Exception paragraph (b) and 2017 NEC 312.5 (C) Exception number 2 are not included as part of this chapter.
SPS 316.312(3)
(3)
Fitting
. Substitute the following wording for 2011 NEC 312.5 (C) Exception paragraph (c) and 2017 NEC 312.5 (C) Exception number 3: A fitting is provided on each end of the raceway to protect the cable from abrasion.
SPS 316.314
SPS 316.314 Outlet, device, pull and junction boxes; conduit bodies; fittings; and handhole enclosures. SPS 316.314(1)(1)
Conductors entering boxes, conduit bodies, or fittings. This is a department exception to the requirements of 2011 and 2017 NEC 314.17 (B) and (C): Exception: Nonmetallic sheathed cable is not required to be secured to the box or conduit body where it is installed in accordance with the wiring method specified in s.
SPS 316.312.
SPS 316.314(2)
(2)
Outlet boxes. This is a department rule in addition to the requirements of 2011 NEC 314.27 (A): In a dwelling unit, a ceiling outlet box installed for use as a lighting fixture outlet in a habitable room or kitchen and located where a ceiling fan could be installed shall be a type listed for ceiling fan support.
SPS 316.334
SPS 316.334 Nonmetallic-sheathed cable: Types NM, NMC and NMS. SPS 316.334(1)(1)
Uses permitted. Substitute the following wording for 2011 and 2017 NEC 334.10 (3): Other structures permitted to be of Types III, IV, and V construction except as prohibited in NEC 334.12.
SPS 316.334(2)
(2)
Types NM, NMC, and NMS. The requirements specified in 2011 and 2017 NEC 334.12 (A) (2) are not included as part of this chapter.
SPS 316.358
SPS 316.358 Uses permitted. This is a department rule in addition to the requirements of 2011 and 2017 NEC 358.12: Electrical metallic tubing may not be used in direct contact with earth, in concrete slabs or floors poured on earth, or in exterior concrete walls below grade.
SPS 316.400(1)(1)
This is a department exception in addition to the exception in 2011 NEC 400.8 (4): Exception No. 2: Flexible cords and cables permitted by NEC 400.7 (A) that are connected to sources other than busways may be attached to adequately supported equipment or building surfaces provided the type of cord or cable, the attachment to the building and equipment, and the support comply with the provisions of NEC 368.56 (B).
SPS 316.400(2)
(2) This is a department exception in addition to the exception in 2017 NEC 400.12 (4): Exception No. 2: Flexible cords and cables permitted by NEC 400.10 (A) that are connected to sources other than busways may be attached to adequately supported equipment or building surfaces provided the type of cord or cable, the attachment to the building and equipment, and the support comply with the provisions of NEC 368.56 (B).
SPS 316.400 History
History: CR 08-047: cr.
Register February 2009 No. 638, eff. 3-1-09;
CR 13-042: am. (title)
Register November 2013 No. 695, eff. 12-1-13;
CR 16-093: renum. SPS 316.400 to (1) and am., cr. (2)
Register June 2018 No. 750, eff. 8-1-18.
SPS 316.404
SPS 316.404 Switches controlling lighting loads. The requirements in 2017 NEC 404.2 (C) do not apply to dwelling units.
SPS 316.404 History
History: CR 16-093: cr.
Register June 2018 No. 750, eff. 8-1-18.
SPS 316.406
SPS 316.406 Receptacles, cord connectors and attachment plugs (caps). SPS 316.406(1)(1)
The requirements in 2011 and 2017 NEC 406.4 (D) (4) are not included as part of this chapter.
SPS 316.406(2)
(2) Substitute the following wording for 2017 NEC 406.9 (B) (1): Receptacles of 15 and 20 amperes, 125 and 250 volts installed in a wet location shall have an enclosure that is weatherproof whether or not the attachment plug cap is inserted.
SPS 316.406 History
History: CR 08-047: cr.
Register February 2009 No. 638, eff. 3-1-09;
CR 13-042:
Register November 2013 No. 695, eff. 12-1-13;
CR 16-093: renum. SPS 316.406 to (1) and am., cr. (2)
Register June 2018 No. 750, eff. 8-1-18.
SPS 316.450
SPS 316.450 Transformers and transformer vaults (including secondary ties). SPS 316.450(1)(1)
Overcurrent protection. This is a department rule in addition to the requirements in 2011 and 2017 NEC Table 450.3 (A) Note 3: The qualified person shall be either an employee at that location or an employee contracted for this purpose who is readily available.
SPS 316.450(2)
(2)
Location. Substitute the following wording for 2011 and 2017 NEC 450.41: Vaults containing oil-insulated transformers shall be located where the vaults can be ventilated to the outside air without using flues or ducts, except where a petition for variance is approved.
SPS 316.511
SPS 316.511 Commercial garages, repair and storage. SPS 316.511(1)(1)
The requirements specified in 2011 NEC 511.3 (C) (1) (a) are not included as part of this chapter.
SPS 316.511(2)
(2) Substitute the following wording for 2011 NEC 511.3 (C) (2) (a): The ceiling area shall be unclassified where ventilation is provided from a point not more than 18 inches from the highest point in the ceiling. The ventilation shall conform to chs.
SPS 361 to
366.
SPS 316.511 Note
Note: The Commercial Building Code, chapters SPS 361 to 366, adopts and references the International Mechanical Code, IMC, for the design of ventilation systems. The adopted provisions of the International Mechanical Code under section 502.16 prescribe provisions for repair garages for natural gas- and hydrogen- fueled vehicles.
SPS 316.511(3)
(3) Substitute the following wording for “Extent of Classified Location” in 2017 NEC Table 511.3 (C) under which the floor area of a major repair garage is considered unclassified: Up to 450 mm (18 in.) above floor level of the room where the room is provided with ventilation from a point not more than 300 mm (12 in.) from the lowest point of the floor area and the ventilation conforms to chs.
SPS 361 to
366.
SPS 316.511(4)
(4) Substitute the following wording for “Extent of Classified Location” in 2017 NEC Table 511.3 (D) under which the ceiling area of a major repair garage is considered unclassified: Within 450 mm (18 in.) of ceiling where ventilation is provided from a point not more than 450 mm (18 in.) from the highest point in the ceiling and the ventilation conforms to chs.
SPS 361 to
366.
SPS 316.511 History
History: CR 08-047: cr.
Register February 2009 No. 638, eff. 3-1-09;
CR 13-042: renum. SPS 316.511 to (1) and am. (title) and (1), cr. (2)
Register November 2013 No. 695, eff. 12-1-13; correction in (1) made under s.
13.92 (4) (b) 7., Stats.,
Register November 2013 No. 695;
CR 16-093: am. (1), (2), cr. (3), (4)
Register June 2018 No. 750, eff 8-1-18.
SPS 316.547
SPS 316.547 Agricultural buildings. This is a department exception to the requirements in 2011 and 2017 NEC 547.5 (G): Exception: Ground-fault circuit-interrupter protection is not required for a single receptacle providing power for an electric fence controller used for livestock containment where an accessible ground-fault circuit-interrupter protected receptacle is located within 900 mm (3 ft) of the non-GFCI protected receptacle.
SPS 316.551
SPS 316.551 Recreational vehicles and recreational vehicle parks. Substitute the following wording for 2017 NEC 551.71 (C): A minimum of 20 percent of existing and 40 percent of all new recreational vehicle sites, with electrical supply, shall each be equipped with a 50-ampre, 125/250-volt receptacle conforming to the configuration as identified in Figure 551.46 (C) (1). These electrical supplies shall be permitted to include additional receptacles that have configurations in accordance with 551.81.