3 Requires backflow protection even if there is a plain end spout.
4 Requires separate water supply terminating without a hose thread, or the manufacturer must provide a bleed device to connect to the janitor sink faucet spout.
5 Or, provide bottled water conversion unit.
6 For outlets other than the required ASSE 1019 hydrants.
7 If provided with hose threads or serrated nipple.
8 Faucet meeting ASME A112.18.1M that includes backflow protection requirements.
9 Hydrants that bleed into the ground and hydrants that are flush with the grade are prohibited.
A-382.41 (5) (f)-1. CROSS CONNECTION CONTROL ASSEMBLY INSTALLATION.
A-382.41 (5) (f)-2. CROSS CONNECTION CONTROL ASSEMBLY INSTALLATION.
A-382.41 (5) (f)-3. CROSS CONNECTION CONTROL ASSEMBLY INSTALLATION.
A-382.41 (5) (f)-4. CROSS CONNECTION CONTROL ASSEMBLY INSTALLATION.
A-382.41 (5) (f)-5. CROSS CONNECTION CONTROL ASSEMBLY INSTALLATION.
A-382.50 (3) (b) 5. OPTIONS FOR TEMPERATURE CONTROL IN HEALTH CARE FACILITIES. The following sketches provide options for fail safe installations at the bathing and shower fixture and temperature control at handwashing fixtures.
Option 1. Fail safe solenoid provided at main mixer meeting ASSE 1017, pressure balanced tub/shower valve meeting ASSE 1016 and limit stop faucets at lavatory and kitchen sink.
Circulated temperature initiated at 140° F
180° F. maximum water heater
Limit stop faucet
Lavatory
Tub/shower
Pressure balance valve with limit stop (ASSE 1016)
Kitchen sink
Limit stop faucet
Fail safe solenoid
Sensor
ASSE 1017 main mixer
  Option 2. Fail safe solenoid provided at main mixer meeting ASSE 1017, pressure balanced tub/shower valve meeting ASSE 1016 and thermostatic mixer meeting ASSE 1016 at lavatory and kitchen sink faucets.
180° F. maximum water heater
ASSE 1017 main mixer
ASSE 1016
thermostatic mixer in supply lines to faucet
Lavatory
Tub/shower
Pressure balance valve with limit stop (ASSE 1016)
Kitchen sink
ASSE 1016
thermostatic mixer in supply lines to faucet
Fail safe solenoid
Sensor
Circulated temperature initiated at 140° F
Option 3. Fail safe solenoid provided at main mixer meeting ASSE 1017, thermostatic tub/shower valve meeting ASSE 1016 and limit stop faucets at lavatory and kitchen sink.
Limit stop faucet
Lavatory
Tub/shower
Thermostatic mixing valve (ASSE 1016)
Kitchen sink
Limit stop faucet
Fail safe solenoid
Sensor
Circulated temperature initiated at 140° F
ASSE 1017 main mixer
180° F. maximum water heater
Option 4. Fail safe solenoid provided at main mixer meeting ASSE 1017, combination thermostatic/pressure balance mixing valve meeting ASSE 1016 and limit stop faucets at lavatory and kitchen sink.
180o F. maximum water heater
Limit stop faucet
Lavatory
Tub/shower
Pressure balance/thermostatic mixing valve (ASSE 1016)
Kitchen sink
Limit stop faucet
Fail safe solenoid
Sensor
ASSE 1017 main mixer
Circulated temperature initiated at 140° F
Option 5. Fail safe solenoid, combination pressure balanced/thermostatic tub/shower valve meeting ASSE 1016 and thermostatic mixer meeting ASSE 1016 at lavatory and kitchen sink faucets.
180o F. maximum water heater
ASSE 1016
thermostatic mixer in supply lines to faucet
Lavatory
Tub/shower
Thermostatic/pressure balance mixing valve (ASSE 1016)
Kitchen sink
ASSE 1016
thermostatic mixer in supply lines to faucet
Sensor
Circulated temperature initiated at 140oF
A-382.51 (3) MOBILE HOME SITES AND PARKS. Mobile home building sewer and water service connections.
Sewer
Water
Frost sleeve
4 inches minimum
6 inches minimum
42 inches minimum
Grade
Frost sleeves terminate 2 inches above grade
Loading...
Loading...
Published under s. 35.93, Stats. Updated on the first day of each month. Entire code is always current. The Register date on each page is the date the chapter was last published.