SECTION 146.
SPS 362.2303 and 362.2304 are amended to read: SPS 362.2303 Trusses spanning 60 feet or greater. The requirements in IBC section 2303.4.1.3 are not included as part of this code chs. SPS 361 to 366. SPS 362.2304 Girder ends. This is a department rule in addition to the requirements in IBC section 2304.11.2.5 2304.12.2.1: A moisture barrier shall be provided between an untreated or nondurable wood girder and an exterior masonry or concrete bearing surface.
SECTION 147.
SPS 362.2510 is created to read:SPS 362.2510 Water-resistive barriers. This is a department rule in addition to the requirements in IBC section 2510.6: The vertical leg of flashing at the base of a wall with two layers of a water-resistive barrier shall be installed behind both layers of the water-resistive barrier.
SECTION 148.
SPS 362.2900 (3) (a) is renumbered SPS 362.2900 (3) and, as renumbered, is amended to read:SPS 362.2900 (3) Enclosure of fixtures Urinals. Water closets and urinals within a toilet room shall be arranged to ensure privacy. Except as provided in par. (b), each water closet shall occupy a separate compartment with walls or partitions and a door enclosing the fixtures to ensure privacy. Urinals shall be placed against walls at least 6 feet 8 inches high and arranged individually with or without partitions.
SECTION 149.
SPS 362.2900 (3) (b) 1. and 2. are repealed.SECTION 150.
SPS 362.2900 (3) (b) 3. is renumbered SPS 362.1210 (1m) (a) 4.SECTION 151.
SPS 362.2902 (1) (a) 1. and 2. are amended to read:SPS 362.2902 (1) (a) 1. Where more than one water closet is required for males, urinals may be substituted for up to 50 percent of the required number of water closets, except that urinals may be substituted for up to 67 percent of the required number of water closets in Group A and E occupancies .
2. Where water is served in restaurants or where other acceptable arrangements are made to provide drinking water, drinking fountains are not required, other reasonable alternatives are acceptable, as approved by the department.
SECTION 152.
SPS 362.2902 (1) (e) is created to read:SPS 362.2902 (1) (e) Alternative to IBC Table 2902.1 This is a department alternative to the minimum fixture requirements of IBC Table 2902.1: The required number of toilet fixtures may be based on the actual occupancy load rather than the load determined by square footage per IBC Table 1004.1.1. The actual occupancy load shall be based on justification found acceptable to the department.
SECTION 153.
SPS 362.2902 (2) is renumbered SPS 362.2902 (2) (a).SECTION 154.
SPS 362.2902 (2) (b) is created to read:SPS 362.2902 (2) (b) These are department exceptions to the requirements in IBC section 2902.2: Separate facilities shall may not be required in all occupancies when the number of fixtures is provided as required under IBC Table 2902.1 in individual user toilet rooms.
SECTION 155.
SPS 362.3001 (1) is amended to read:SPS 362.3001 (1) Referenced standards. Substitute the following wording for the requirements in IBC section 3001.2: Except as otherwise provided for in this code chs. SPS 361 to 366, the design, construction, installation, alteration, repair, and maintenance of conveyances and their components shall comply with ch. SPS 318. SECTION 156.
SPS 362.3002 (title) is repealed and recreated to read:SPS 362.3002 (title) Hoistway enclosures.
SECTION 157.
SPS 362.3002 is renumbered SPS 362.3002 (1).SECTION 158.
SPS 362.3002 (1) (title) is created to read:SPS 362.3002 (1) (title) Elevator car to accommodate ambulance stretcher.
SECTION 159.
SPS 362.3004 (title) is repealed. SECTION 160.
SPS 362.3004 (1) to (3) are renumbered SPS 362.3002 (2) to (4) and, as renumbered, SPS 362.3002 (2), (3), and (4) (intro.) are amended to read:SPS 362.3002 (2) Venting. This is a department rule in addition to the requirements in IBC section 3004.3 3002: A ventilation opening in a hoistway wall, where provided, shall have guards securely anchored to the supporting structure inside the hoistway. The guards shall consist of a wire−mesh screen of at least 0.0915−inch diameter steel wire with openings that will reject a ball one_-inch in diameter, or expanded metal screen of equivalent strength and open area.
(3) Area of vents. This is a department rule in addition to the requirements in the exception under IBC 3004.3 section 3002: The Where vent openings automatically open upon detection of smoke in the elevator lobbies or hoistway, upon power failure and upon activation of a manual override control, the manual override control shall comply with all of the following:
(4) Plumbing and mechanical systems. Substitute the following wording for the requirements and the exception in IBC section 3004.4 3002.9:
SECTION 161.
SPS 362.3006 is renumbered SPS 362.3005 and, as renumbered, is amended to read:SPS 362.3005 Machine rooms. (1) Scope. This is a department rule in addition to the requirements in IBC section 3006 3005: This section applies to elevator machine rooms, machinery spaces, control rooms, and control spaces not within the hoistway.
(2) Access. This is a department informational note to be used under IBC section 3006.1 3005.1:
(3) Temperature and humidity. Substitute the following wording for the requirements in IBC section 3006.2 3005.2: Elevator machine rooms that contain solid−state equipment for elevator operation shall be provided with an independent means to control the temperature and humidity in the machine room.
(4) Pressurization. This is a department exception to the requirements in IBC section 3006.3 3005.3: An elevator machine room which serves a pressurized elevator hoistway and which is not directly connected to the pressurized elevator shaft is not required to be pressurized.
(5) Plumbing systems. Substitute the following wording for the requirements in IBC section 3006.6 3005.6: Plumbing systems not used in connection with the operation of the elevator may not be located in elevator equipment rooms.
SECTION 162.
SPS 362.3100 is amended to read:SPS 362.3100 Special construction. These are department rules in addition to the requirements in IBC chapter 31: Public mausoleum structures shall be designed, constructed, and maintained in accordance with this code chs. SPS 361 to 366. Mausoleums shall be classified as a Group S-1 storage occupancy and shall be constructed of reinforced concrete or other materials of similar durability. SECTION 163.
SPS 362.3103 is amended read: SPS 362.3103 Temporary structures. This is a department rule in addition to the requirements in IBC section 3103: Under IBC sections 3103.1.1 3103.1.2 and 3103.2, the requirements for permits and construction documents for temporary structures are at the option of the local code official.
SECTION 164.
SPS 362.3200 is amended to read:SPS 362.3200 Encroachments into the public right-of-way. The requirements in IBC chapter 32 are not included as part of this code chs. SPS 361 to 366. SECTION 165.
SPS 362.3400 is repealed. SECTION 166.
SPS 362.3500 (3) (intro.) is amended to read:SPS 362.3500 (3) (intro.) Additions. This is a department rule in addition to the requirements in IBC chapter 35: The following standards are hereby incorporated by reference into this code chs. SPS 361 to 366: SECTION 167.
SPS 362.3500 (3) (b) and (c) are repealed.