(c) Substitute the following wording for NEC 210.8 (B): All 125-volt, single-phase, 15- and 20-ampre receptacles installed in the following locations shall have ground-fault circuit interrupter protection for personnel.
(d) The requirements in NEC 210.8 (B) (9) and (10) are not included as part of this chapter.
(e) This is a department exception to the requirements in NEC 210.8 (A) and (B).
Exception: Ground−fault circuit−interrupter protection shall not be required for a single receptacle providing power for sump, sewage, or condensate pumps where an accessible ground−fault circuit−interrupter protected receptacle is located within 900 mm (3 ft) of the non−GFCI protected receptacle.
(f) The requirements in NEC 210.8 (D) are not included as part of this chapter.
(2) Branch circuits required. The requirements in NEC 210.11 (C) (4) are not included as part of this chapter.
(3) Arc-fault circuit-interrupter protection. (a) The requirements in NEC 210.12 (A) do not apply to kitchens and laundry areas.
(b) The requirements in NEC 210.12 (B) and (C) are not included as part of this chapter.
SECTION 33. SPS 316.210 (4) is amended to read:
SPS 316.210 (4) Branch circuit extensions or modifications — dwelling units and dormitory units. The requirements in NEC 210.12 (B) (D) are not included as part of this chapter.
SECTION 34. SPS 316.210 (5) is repealed.
SECTION 35. SPS 316.210 (6) is renumbered SPS 316.210 (5).
SECTION 36. SPS 316.210 (6) and (7) are created to read:
SPS 316.210 (6) Garages. Substitute the following wording for NEC 210.52 (G) (1): In each attached garage and in each detached garage with electric power.
(7) Meeting rooms. The requirements in NEC 210.71 do not apply to this chapter.
SECTION 37. SPS 316.220 (1) and (2) (title) are repealed.
SECTION 38. SPS 316.220 (2) is renumbered SPS 316.220.
SECTION 39. SPS 316.225 (1) is repealed.
SECTION 40. SPS 316.225 (2), (3), (4), and (6) are renumbered SPS 316.225 (1), (2), (3), and (4).
SECTION 41. SPS 316.230 (1) (a) (intro.) is amended to read:
SPS 316.230 (1) (a) (intro.) These are This is a department informational notes note to be used under NEC 230.2 (intro.):
SECTION 42. SPS 316.230 (1) (a) (Note 1) and (c) are repealed.
SECTION 43. SPS 316.230 (4) (intro.) and (a) are consolidated, renumbered SPS 316.230 (4) and amended to read:
SPS 316.230 (4) Rating of service disconnecting means. This is a department rule in addition to the requirements of NEC 230.79: (a) Two- or multi-family dwellings. Except as provided in par. (b), for For 2-family or multi-family dwellings, the service equipment shall have a rating of not less than 150 amperes, 3-wire or 4-wire. Where the combined rating of all service disconnecting means is 150 amperes or larger, the service or feeder equipment rating for each dwelling unit shall have a rating of not less than 60 amperes.
SECTION 44. SPS 316.230 (4) (b) is repealed.
SECTION 45. SPS 316.240 is created to read:
SPS 316.240 Overcurrent protection. The requirements in NEC 240.67 do not apply to this chapter.
SECTION 46. SPS 316.250 (3) is created to read:
SPS 316.250 (3) Types of equipment grounding conductors. This is a department rule in addition to the requirements of NEC 250.118: A metallic raceway installed in direct contact with earth, in concrete slabs or floors poured on earth, or in exterior concrete walls below grade shall be augmented with a supplemental equipment grounding conductor identified in NEC 250.118 (1). This supplemental conductor shall be sized in accordance with NEC 250.122. An aluminum equipment grounding conductor used for this purpose shall be insulated.
SECTION 47. SPS 316.300 (2) is repealed and recreated to read:
SPS 316.300 (2) Protection against physical damage. This is a department exception in addition to the exceptions under NEC 300.4 (D):
Exception No. 4: This distance does not need to be maintained within 8 inches of a device, junction box, splice, or termination point.
SECTION 48. SPS 316.310 (intro.) is renumbered SPS 316.310 and amended to read:
SPS 316.310 Conductors for general wiring. This is a department rule in addition to the requirements in NEC 310.15 (B) (3) (a): The derating factors shown in NEC Table 310.15 (B) (3) (a) do not apply to branch circuits supplying an individual dwelling unit except under the following conditions:
Exception No. 6: The derating factors shown in NEC Table 310.15 (B) (3) (a) do not apply to branch circuits supplying an individual dwelling unit except under the following conditions:.
SECTION 49. SPS 316.310 (1) and (2) are repealed.
SECTION 50. SPS 316.312 (2) and (3) are amended to read:
SPS 316.312 (2) Omission. The requirements specified in NEC 312.5 (C) Exception paragraph (b) number 2 are not included as part of this chapter.
(3) Fitting. Substitute the following wording for NEC 312.5 (C) Exception paragraph (c) number 3: A fitting is provided on each end of the raceway to protect the cable from abrasion.
SECTION 51. SPS 316.314 (1) (title) and (2) are repealed.
SECTION 52. SPS 316.314 (1) is renumbered SPS 316.314.
SECTION 53. SPS 316.400 is amended to read:
SPS 316.400 Flexible cords and cables. This is a department exception in addition to the exception in NEC 400.8 400.12 (4):
Exception No. 2: Flexible cords and cables permitted by NEC 400.7 400.10 (A) that are connected to sources other than busways may be attached to adequately supported equipment or building surfaces provided the type of cord or cable, the attachment to the building and equipment, and the support comply with the provisions of NEC 368.56 (B).
SECTION 54. SPS 316.404 is created to read:
SPS 316.404 Switches controlling lighting loads. The requirements in NEC 404.2 (C) do not apply to dwelling units.
SECTION 55. SPS 316.406 is renumbered SPS 316.406 (1).
SECTION 56. SPS 316.406 (2) is created to read:
SPS 316.406 (2) Substitute the following wording for NEC 406.9 (B) (1): Receptacles of 15 and 20 amperes, 125 and 250 volts installed in a wet location shall have an enclosure that is weatherproof whether or not the attachment plug cap is inserted.
SECTION 57. SPS 316.511 is repealed and recreated to read:
SPS 316.511 Commercial garages, repair and storage. (1) Substitute the following wording for “Extent of Classified Location” in NEC Table 511.3 (C) under which the floor area of a major repair garage is considered unclassified: Up to 450 mm (18 in.) above floor level of the room where the room is provided with ventilation from a point not more than 300 mm (12 in.) from the lowest point of the floor area and the ventilation conforms to chs. SPS 361 to 366. (2) Substitute the following wording for “Extent of Classified Location” in NEC Table 511.3 (D) under which the ceiling area of a major repair garage is considered unclassified: Within 450 mm (18 in.) of ceiling where ventilation is provided from a point not more than 450 mm (18 in.) from the highest point in the ceiling and the ventilation conforms to chs. SPS 361 to 366. Note: The Commercial Building Code, chapters SPS 361 to 366, adopts and references the International Mechanical Code, IMC, for the design of ventilation systems. The adopted provisions of the International Mechanical Code under section 502.16 prescribe provisions for repair garages for natural gas- and hydrogen- fueled vehicles.
SECTION 58. SPS 316.551 is created to read: