SPS 362.1020 Corridor continuity. This is a department exception to the requirements in IBC section 1018.6 1020.6: Other spaces or rooms constructed as required for corridors, and that are adjacent to a fire-resistance-rated corridor, shall may not be construed as intervening rooms; and may be open to the corridor when all of the following are satisfied:
SECTION 126.
SPS 362.1021 (title) and (1) are repealed.
SECTION 127.
SPS 362.1021 (2) is renumbered SPS 362.1006 (3) and amended to read:
SPS 362.1006 (3) Exits from stories. This is a department exception to the requirements in IBC section 1021.1 1006.3: Buildings of Group I-3 occupancy that are used as guard towers, provided the towers are no higher than 2 stories above grade, accommodate no more than 10 occupants, and have a travel distance of no more than 75 feet.
SECTION 128.
SPS 362.1022 is repealed.
SECTION 129.
SPS 362.1029 is created to read:
SPS 362.1029 The requirements in IBC section 1029.1.1.1 are not included as part of chs. SPS 361 to 366.
 
SECTION 130.
SPS 362.1101 (title) is amended to read:
SPS 362.1101 (title) Design of Type A and B units.
SECTION 131.
SPS 362.1101 (1) (title) is repealed.
SECTION 132.
SPS 362.1101 (1) (a) and (b) are renumbered SPS 362.1101 (1m) and (2m).
SECTION 133.
SPS 362.1101 (2) is repealed.
SECTION 134.
SPS 362.1103 (intro.) is amended to read:
SPS 362.1103 (intro.) Scoping requirement­­s limited access spaces. Substitute the following wording for the requirements in IBC section 1103.2.8 1103.2.7:
SECTION 135.
SPS 362.1104 (1) (title) is repealed.
SECTION 136.
SPS 362.1104 (1) is renumbered SPS 362.1104.
SECTION 137.
SPS 362.1104 (2) is repealed.
SECTION 138.
SPS 362.1107 (4) is created to read:
SPS 362.1107 (4) Multistory units. Substitute the following wording for IBC section 1107.7.2: A multistory dwelling or sleeping unit that is not provided with elevator service is not required to be a Type B unit. Where a multistory unit is provided with external elevator service to only one floor, the floor provided with elevator service shall be the primary entry to the unit, shall comply with the requirements for a Type B unit and a toilet facility shall be provided on that floor.
SECTION 139.
SPS 362.1109 is repealed.
SECTION 140.
SPS 362.1110 is renumbered SPS 362.1111 and SPS 361.1111 (1) (a) and (2) (a) and (b) and, as renumbered, are amended to read:
SPS 362.1111 (1) (a) General. Substitute the following wording for the requirements for location 1 in IBC section 1110.1 1111.1: Except as specified par. (b), accessible parking spaces required in IBC section 1106 for the general public shall be identified with a sign complying with the accessible parking sign requirements specified in s. Trans 200.07.
(2) (a) Substitute the following wording for the introductory paragraph of IBC section 1110.2 1111.2: Signage indicating directional information or information about functional spaces or signage indicating special accessibility provisions shall comply with ICC A117.1 and be provided at the following locations:
(b) This is a department informational note to be used under IBC section 1110.31111.3.
SECTION 141.
SPS 362.1200 is renumbered SPS 362.0915 and SPS 362.0915 (title), (intro.), and (1) (b) and (d) and, as renumbered, are amended to read:
SPS 362.0915 (title) Carbon monoxide alarms detection. (intro.) These are department rules in addition to Substitute the following wording for the requirements in IBC chapter 12 section 915:
(1) (b) “Fuel-burning appliance” means a device that is installed in a building and burns fossil−fuel or carbon based fuel where carbon monoxide is a combustion by−product, including stoves, ovens, grills, clothes dryers, furnaces, boilers, water heaters, heaters, fireplaces and stoves has the meaning given in s. SPS 362.0202 (2) (f).
(d) “Sealed combustion appliance” means a listed appliance that acquires all air for combustion through a dedicated sealed passage from the outside to a sealed combustion chamber and all combustion products are vented to the outside through a separate dedicated sealed vent has the meaning given in s. SPS 362.0202 (2) (i).
SECTION 142.
SPS 362.1200 (2) (a) 5. b. is amended to read:
SPS 362.1200 (2) (a) 5. b. All of the fuel-burning appliances in the building are of sealed-combustion type that are inspected in accordance with sub. (3) or rules promulgated by the department of health services agriculture, trade and consumer protection under 254.74 (1) (am) s. 97.625 (1) (am), Stats.
SECTION 143.
SPS 362.1203 is created to read:
SPS 362.1203 Natural ventilation. This is a department rule in addition to the requirements in IBC section 1203.5: The use of natural ventilation shall be permitted in any of the following:
(1)
Occupancies specified in s. SPS Table 364.0402.
(2)
Any occupancy with an engineered design, approved by the department, that satisfies the ventilation needs of the occupancy.
SECTION 144.
SPS 362.1210 (intro.) is repealed.
SECTION 145.
SPS 362.1210 (1) is renumbered SPS 362.1210 (1m) (intro.) and, as renumbered, is amended to read:
SPS 362.1210 (1m) (intro.) Privacy and access. This is a department rule in addition to the requirements in IBC section 1210: Every toilet room shall be enclosed and separated from other areas of the building in a manner that will ensure privacy of the users of the toilet rooms. Restriction of access to toilet rooms, such as by use of key locks or other similar devices, is prohibited, except as provided in sub. (2). this subsection does not apply to the following:
SECTION 146.
SPS 362.1210 (2) (title) is repealed.
SECTION 147.
SPS 362.1210 (2) (a), (b), and (c) are renumbered SPS 362.1210 (1m) (a), (b), and (c).
SECTION 148.
SPS 362.1210 (2m) is created to read:
SPS 362.1210 (2m) Urinals separation. Substitute the following wording for the requirements in IBC section 1210.3.2: Urinals shall be arranged individually with or without partitions.
SECTION 149.
SPS 362.1405 (1) and (2) are renumbered SPS 362.1405 (2m) and (3m), and SPS 362.1405 (2m), as renumbered, is amended to read:
SPS 362.1405 (2m) This is a department exception in addition to the exceptions in IBC section 1405.3.1 1405.3.1: Where other approved means to avoid condensation in unventilated framed wall, floor, roof and ceiling cavities, and box sills are provided.
SECTION 150.
SPS 362.1405 (1m) is created to read:
SPS 362.1405 (1m) Substitute the following wording for the requirements, but not the exceptions, in IBC section 1405.3.1: Class I and II vapor retarders. Class I or II vapor retarders shall be provided on the interior side of frame walls and ceiling assemblies.