SECTION 225.
SPS 364.0001 (2) and (3), SPS 364.0101, and SPS 364.0202 (1) (b) are created to read:
SPS 364.0001 (2) Notwithstanding any other provision of this chapter, the department may not adopt or enforce minimum ventilation standards for indoor drive-through self-service storage facilities described in Table 364.0403 that are more restrictive than the standards under this chapter applicable to warehouses.
(3)
Notwithstanding any other provision of this chapter, the department may not adopt or enforce minimum ventilation standards for a building in which a boat that is not a motorized vehicle under s. SPS 364.0202 (1) (f) is or may be stored that are more restrictive than the standards under this chapter that would otherwise apply.
SPS 364.0101 Administration. Except for IMC section 102.8, the requirements in IMC chapter 1 are not included as part of this chapter.
SPS 364.0202 (1) (b) “Enclosed parking garage” means an enclosed building where motorized vehicles are stored or parked.
SECTION 226.
SPS 364.0202 (1) (c) is renumbered SPS 364.0202 (1) (am).
SECTION 227.
SPS 364.0202 (1) (d) is amended to read:
SPS 364.0202 (1) (d) “Health care facility” means a hospital, nursing home, or outpatient surgical facility, or community-based residential facility.
SECTION 228.
SPS 364.0202 (1) (e), (f), and (Note) are created to read:
SPS 364.0202 (1) (e) “Living area” means those areas within a dwelling unit involving living rooms, bedrooms, dens, family rooms, and recreation rooms, but not rooms used for cooking, bathing, washing, and sanitation purposes.
(f) “Motorized vehicle” means a self-propelled motor-driven vehicle that is used for moving people or products on land, water, or air. “Motorized vehicle” does not include a boat that is dry stored and not operated in the building in which it is stored.
Note: "Motorized vehicle" in this definition is intended to apply to motorized equipment transporting people and goods for pleasure, construction or commerce, rather than equipment dedicated to warehousing and yard operations, such as forklifts; or for grounds and facility maintenance, such as lawnmowers; or for amusement facilities, such as go-carts.
SECTION 229.
SPS 364.0300 (1) is amended to read:
SPS 364.0300 (1)This is a department rule in addition to the requirements in IMC chapter 3: In addition to the requirements in this code chs. SPS 361 to 366, the heating and ventilation systems for health care facilities only shall conform to the applicable provisions of The Facility Guidelines Institute (FGI) FGI Guidelines for Design and Construction of Health Care Hospitals and Outpatient Facilities 2014, except as provided in sub. (2).
SECTION 230.
SPS 364.0301 (1) to (3) are amended to read:
(1)Scope. Substitute the following wording for the requirements in IMC section 301.1: This chapter shall govern the approval and installation of all equipment and appliances that comprise parts of the building mechanical systems regulated by this code chs. SPS 361 to 366 in accordance with subch. 1I.
(2)Energy utilization. This is a department informational note to be used under IMC section 301.2 301.7.
(3)Listed and labeled. Substitute the following wording for the requirements in IMC section 301.4 301.7:
SECTION 231.
SPS 364.0306 is repealed.
SECTION 232.
SPS 364.0309 (1) and Table 364.0309 are amended to read:
SPS 364.0309 (1)Alternate minimums. For those interior spaces intended for human occupancy listed in Table 364.0309, the heating system shall be capable of maintaining an inside indoor temperature of not less than that shown in the table at 3 feet above the floor.
Table 364.0309
Alternate Minimum Inside Indoor Temperature
Occupancy Type
Minimum Inside Indoor Temperature (degrees F)
Dry cleaners, laundries, laundry
rooms
60
Educational training shops
60
Commercial kitchens
60
Health care facilities, hospitals,
nursing homes, ambulatory surgery
centers
Footnote a.
Factories and machine shops
60
Foundries
NMR
Sawmills
NMR
Garages at private dwellings
NMR
Automotive service and repair
garages
60
Car washes, enclosed:
Self−serve
NMR
All other types
60
Ice skating rinks (indoor)
NMR
Natatoriums
76
Roller skating rinks (indoors)
60
Storage
NMR
Elevator cars
NMR
Janitor closets
NMR
Locker and dressing rooms
70
Shower rooms
70
Food processing
NMR
Printing
60
NMR = No minimum requirement
a. For inside indoor temperature requirements in health care facilities, use American Institute of Architects (AIA) FGI Guidelines for Design and Construction of Hospital Hospitals and Health Care Outpatient Facilities, 2014.
SECTION 233.
SPS 364.0309 (3) is created to read:
SPS 364.0309 (3) Spot heating. Spot heating may be used to heat individual workstations in industrial buildings in lieu of heating the entire space specified in IMC section 309, provided the design temperature at the fixed workstation is at least 60° F.
SECTION 234.
SPS 364.0312 (Note) is amended to read:
SPS 364.0312 (Note) Note: For design parameters in the IECC refer to ch. SPS 363 or IECC section 503 C403.
SECTION 235.
SPS 364.0401 (2) (c) is created to read:
SPS 364.0401 (2) (c) In addition to the criteria under s. 101.025 (1), Stats., the area that may be occupied by motorized vehicles shall be considered when establishing minimum quantities of outside air that must be supplied.
SECTION 236.
SPS 364.0401 (4) (b) is amended to read:
SPS 364.0401 (4) (b) Substitute the following wording for the requirements in IMC section 401.4 item 2: Intake openings shall be located not less than 10 feet horizontally from any hazardous or noxious contaminant source except as specified in IMC section 401.4, item 3 and section 501.3.1.
SECTION 237.
SPS 364.0401 (4) (e) is created to read:
SPS 364.0401 (4) (e) Substitute the following wording for the wording in IMC section 401.4, item 1: Intake openings shall be located a minimum of 10 feet (3048 mm) from lot lines or buildings on the same lot. Where openings front on a street or public way, the distance shall be measured to the centerline of the street or public way.
SECTION 238.
SPS Table 364.0402 is amended to read:
Table 364.0402
Natural Ventilation
Allowed for Specific Occupancies
Occupancy Classification
Correctional Facilities
Cells without plumbing features
Dining halls < 100 persons
Guard stations
Day room
Booking/waiting
Dry cleaners, laundries
Coin-operated dry cleaners
Coin-operated laundries
Storage, pick up
Education
Auditoriums < 100 persons
Media center
Music/theatre/dance
Day care facilities < 20 children
(through age 4)
Lecture < 100 persons
Multiuse assembly < 100 persons
Food and beverage service
Bars, cocktail lounges < 100 persons
Dining rooms < 100 persons
Kitchens (cooking)
Hotels, motels, resorts and dormitories
Multipurpose assembly < 100 persons
Bedroom/living room
Conference/meeting < 100 persons
Dormitory sleeping areas
Gambling casinos < 100 persons
Lobbies/pre-function
Business areas
Conference rooms < 100 persons
Reception areas < 100 persons
Main entry lobbies < 100 persons
Lecture < 100 persons
Public spaces
Places of religious worship
< 100 persons
Courtrooms < 100 persons
Legislative chambers < 100 persons
Libraries < 100 persons
Museums < 100 persons
Dwellings
Garages
Kitchens
Living areas
Retail stores, sales floors, and showroom floors
Sales
Dressing rooms
Mall common areas
Storage rooms
Specialty shops
Pet shops (animal areas)
Supermarkets
Car Washes washes
Enclosed parking garages 850 S.F. or less in area and storing 5 or fewer vehicles
Sports and amusement
Discos/dance floors < 100 persons
Bowling alleys (seating areas) < 100 persons
Game arcades < 100 persons
Ice arenas without combustion
Places of religious worship engines < 100 persons
Gym, stadium, arena (play area)
Spectator areas < 100 persons
Swimming pools (pool and deck area) < 100 persons
Health club/aerobics room < 100 persons
Health club/weight room < 100 persons
Theaters
Auditoriums < 100 persons
Lobbies < 100 persons
Stages, studios < 100 persons
Transportation
Platforms < 100 persons
Waiting rooms < 100 persons
Aircraft hangars (with single aircraft and no adjacent occupancies)
Workrooms
Meat processing
Pharmacy (prep. area)
Photo studios
Copy, printing rooms
SECTION 239.
SPS 364.0403 (5) (d) 1. is amended to read:
SPS 364.0403 (5) (d) 1. Substitute the following wording for the requirements in IMC sections 403.3.1 403.1.1.1 through 403.3.2.3.4 403.3.1.1.2.3.4: Where multiple spaces having different ventilation rate requirements are served by a common ventilation system, the minimum amount of outdoor airflow supplied by the ventilation system shall equal the total outdoor airflow required for each space if each space is provided with minimum air changes in accordance with this paragraph.
SECTION 240.
SPS 364.0403 (5) (d) 2. d. is renumbered to SPS 364.0403 (5) (d) 3. and, as renumbered, is amended to read:
SPS 364.0403 (5) (d) 3. Air change rate of less than 6 air changes per hour is permitted where mechanical cooling is provided to maintain an interior design temperature of 78° F 75 degrees F or lower. The air change rate may not be less than the alternative minimum air change rate per hour specified in Table 364.0403. Air changes are not required to be provided for spaces required to be mechanically exhausted.
SECTION 241.
SPS 364.0403 (5) (d) 4. is created to read:
SPS 364.0403 (5) (d) 4. The air change requirement for 6 air changes per hour may be omitted in any of the following applications:
a.
Buildings or rooms utilizing spot heating as the only source of heat.