SECTION 283.
SPS 366.0605 and SPS 366.0607 are repealed.SECTION 284.
SPS 366.0701 is created to read: SPS 366.0701 Alterations. Substitute the following wording for the requirements in IEBC section 701.2: Conformance. An existing building or portion thereof may not be altered such that the building becomes less safe than was required in its existing condition.
SECTION 285.
SPS 366.0704 is renumbered SPS 366.0804 and, as renumbered, is amended to read:SPS 366.0804 Automatic sprinkler systems. This is a department exception to the requirement in IEBC section 704.2 804.2: The installation or extension of an automatic sprinkler system may exclude the protection of combustible concealed spaces that are not accessible in existing buildings. This exclusion is also applicable to sprinkler systems triggered by changes of use or additions.
SECTION 286.
SPS 366.0704 is created to read:SPS 366.0704 Means of Egress. (1) alterations. Substitute the following wording for the requirements in IEBC section 704.1: Alterations shall be done in a manner that maintains the level of protection required for the means of egress prior to the alteration.
SECTION 287.
SPS 366.0705 is created to read:SPS 366.0705 Accessibility. Substitute the following wording for the requirements in IEBC section 605.1: General. Repairs shall maintain accessibility in accordance with IEBC section 705.1.13.
SECTION 288.
SPS 366.0709 is renumbered SPS 366.0809 and, as renumbered, is amended to read:SPS 366.0809 Altered existing mechanical systems. The exception to the requirements in IEBC section 709.1 809.1 and the requirements in IEBC section 709.2 809.2 are not included as part of this code chs. SPS 361 to 366. SECTION 289.
SPS 366.0710 is renumbered SPS 366.0810 and, as renumbered, is amended to read:SPS 366.0810 Minimum plumbing fixtures. Substitute the following wording for the requirements in IEBC section 710.1 810.1: Where the occupant load of a story is increased by more than 20 percent, plumbing fixtures for the story shall be provided in quantities specified in the IBC based on the increased occupant load.
SECTION 290.
SPS 366.0711 is repealed.SECTION 291.
SPS 366.0802 is renumbered SPS 366.0902 (2) and, as renumbered, is amended to read:SPS 366.0902 (2) Emergency Controls. Emergency controls. The requirements in IEBC section 802.2.1 902.2.1 are not included as part of this code chs. SPS 361 to 366. SECTION 292.
SPS 366.0808 is repealed. SECTION 293.
SPS 366.0809 is renumbered SPS 366.0909, and SPS 366.0909 (intro.), as renumbered, is amended to read:SPS 366.0909 Plumbing. (intro.) These are department rules in addition to the requirements in IEBC chapter 8 9:
SECTION 294.
SPS 366.0901 (title) and (1) to (3) are renumbered SPS 366.1001 (title) and (1) to (3) and, as renumbered, are amended to read:SPS 366.1001 (title) Change of occupancy. (1) change in of occupancy with no occupancy classification approval. Substitute the following wording for the requirements in IEBC section 901.2 1001.2: A change in of occupancy, as defined in IEBC section 202, with no or a change of occupancy classification within a space where there is a different fire protection system threshold requirement in IBC chapter 9 may not be made to any structure that will subject the structure to any special provisions of this code, including the provisions of IEBC sections 902 through 911, without the approval of the code official. An increased occupant load may trigger additional means of egress or fire protection requirements.
(2) Change of occupancy classification. This is a department rule in addition to the requirements in IEBC section 901.3 1001.2.2: Buildings undergoing a change in occupancy that would result in an increase in demand for either fossil fuel or electrical energy shall comply with the IECC.
(3) Certification of occupancy required. The requirements in IEBC section 901.4 1001.3 are not included as part of this code chs. SPS 361 to 366. SECTION 295.
SPS 366.0901 (4) is renumbered SPS 366.1012 and, as renumbered, is amended to read:SPS 366.1012 Standpipe systems. This is a department rule in addition to the requirements in IEBC section 912.2 1012.2: Standpipe systems shall be provided in existing buildings and structures or portions of existing buildings and structures in accordance with IBC chapter 9 of the IBC when existing buildings or structures that are greater than 60 feet in height are changed to include a Group R−1 or R−2 occupancy.
SECTION 296.
SPS 366.0902 is created to read:SPS 366.0902 Special use and occupancy. (1) Boiler and furnace equipment rooms. Substitute the following wording for the requirements, but not the exceptions, in IEBC section 902.2: Boiler and furnace equipment rooms. Boiler and furnace equipment rooms adjacent to or within Groups I-1, I-2, I-4, R-1, R-2, and R-4 occupancies shall be enclosed in compliance with IBC 509 heating equipment enclosure requirements.
SECTION 297.
SPS 366.0903 is created to read:SPS 366.0903 Building elements and materials. Substitute the following wording for the requirements in IEBC section 803.2.1: All existing interior vertical openings in the work area connecting two or more floors shall be enclosed with approved assemblies having a fire resistance rating of not less than one hour with approved opening protectives.
SECTION 298.
SPS 366.0904 is created to read:SPS 366.0904 Level 3 alterations fire protection. (1) Upholstered furniture. The requirement in IEBC section 904.1.3 condition 3 is not included as part of chs. SPS 361 to 366. (2) Fire alarm and detection systems. Substitute the requirements from 2009 IEBC section 804.2 for the requirements in IEBC section 904.2.
SECTION 299.
SPS 366.0911 is renumbered SPS 366.1011 and, as renumbered, is amended to read:SPS 366.1011 Other requirements. (1) Elevator recall. This is a department rule in addition to the requirements in IEBC section 911 1011: At least one existing elevator shall be provided with emergency recall operation and emergency in-−car operation complying with ch. SPS 318 when an existing building or structure that is greater than 60 feet in height is changed to include a Group R-−1 or R-−2 occupancy. (2) Carbon monoxide alarms. This is a department rule in addition to the requirements in IEBC section 911 1011: A building or a portion of a building changed to be or include a residential building as defined under s. 101.149 (1) (b), Stats., shall be provided with carbon monoxide alarms or detectors in accordance with s. SPS 362.1200. SECTION 300.
SPS 366.0912 is renumbered SPS 366.1010 and, as renumbered, is amended to read:SPS 366.1010 Substitute the following wording for the requirements in IEBC section 910 1010: Where the occupant load of a story is increased by more than 20 percent, plumbing fixtures for the story shall be provided in quantities specified in the IBC based on the increased occupant load.
SECTION 301.
SPS 366.1002 is renumbered SPS 366.1102 (2) and, as renumbered, is amended to read:SPS 366.1102 (2) Fire protection systems. This is a department exception to the requirements in IEBC section 1002.3 1102.3: An automatic sprinkler system is not required for additions to individual dwelling units within existing townhouses that are not already protected with an automatic sprinkler system.
SECTION 302.
SPS 366.1101 is renumbered SPS 366.1201 and, as renumbered, is amended to read:SPS 366.1201 (1) Scope. This is a department rule in addition to the requirements in IEBC section 1101.1 1201.1: Any historic building is exempt from the energy requirements of this code chs. SPS 361 to 366. (2) Report. The requirements in IEBC section 1101.2 1202.2 are not included as part of this code chs. SPS 361 to 366. SECTION 303.
SPS 366.1102 (title) and (1) are created to read:SPS 366.1102 (title) Heights and areas. (1) Area limitations. This is a department exception in addition to the exception in IEBC section 1102.2: Buildings meeting the legacy Wisconsin unlimited area provisions are allowed to have unlimited area additions per the current code without a separating firewall.