Section 166. SPS 364.0802 is repealed.
Section 167. SPS 364.1500 (1m), (2m), and (Note) are repealed.
Section 168. SPS 364.1500 (3) is amended to read:
SPS 364.1500 (3) NFPA 45−2015 45-2019, Standard on Fire Protection for Laboratories Using Chemicals.
Section 169. SPS 364.1500 (4) is created to read:
SPS 364.1500 (4) ANSI/ASHRAE/ASHE Standard 170-2017, Ventilation of Health Care Facilities.
Section 170. SPS 365.0501 (4) is created to read:
SPS 365.0501 (4) Plastic venting systems associated with gas-fired appliances shall meet the requirements of UL 1738, inclusive of specific testing and marking requirements for pipe, fittings, and cement.
­Section 171. SPS 365.0800 is amended to read:
SPS 365.0800Referenced standards. This is a department rule in addition to the requirements in IFGC chapter ch. 8: The following standard is incorporated by reference into chs. SPS 361 to 366: ANSI Z223.1/NFPA 54-2015 54-2021 , National Fuel Gas Code.
­Section 172. SPS 365.0900 is amended to read:
SPS 365.0900 IFGC Appendices A to D E are not included as part of this chapter.
Section 173. SPS 366.0101 (4) (b) and (c) are amended to read:
SPS 366.0101 (4) (b) Repairs, alterations, additions, changes in occupancy, and relocated buildings complying with the applicable requirements of IEBC chapters 5 through 13 chs. 3, 4, 6 to 12, and 14 shall be considered in compliance with the provisions of chs. SPS 361 to 366.
(c) Repairs, alterations, additions, changes in occupancy, and relocated buildings complying with IEBC chapter 14 ch. 13 shall be considered in compliance with the provisions of chs. SPS 361 to 366.
Section 174. SPS 366.0303 is created to read:
SPS 366.0303 The requirements in IEBC s. 303 are not included as part of chs. SPS 361 to 366.
Section 175. SPS 366.0306 is created to read:
SPS 366.0306 This is a department informational note to be used under IBEC s. 306. Note: See s. 101.132, Stats., for additional accessibility requirements.
Section 176. SPS 366.0400 is renumbered to 366.0500 and amended to read:
SPS 366.0500 The requirements in IEBC chapter chs. 4 5 are not included as part of chs. SPS 361 to 366, except for the requirements in IEBC section 410 when applied by IEBC section 1401.2.5.
Section 177. SPS 366.0600 is renumbered to SPS 366.0308, and SPS 366.0308 (intro.), as renumbered, is amended to read:
SPS 366.0308 These are department rules in addition to the requirements in IEBC chapter 6 s. 308 and are established under the authority of s. 101.127, Stats.:
Section 178. SPS 366.0603 is renumbered to SPS 366.0307.
Section 179. SPS 366.0605 is repealed.
Section 180. SPS 366.0606 is renumbered to SPS 366.0405 and amended to read:
SPS 366.0405 The requirements in IEBC sections 606.2 to 606.2.5 ss. 405.2 to 405.2.6 are not included as part of chs. SPS 361 to 366.
Section 181. SPS 366.0609 is renumbered to SPS 366.0408 and amended to read:
SPS 366.0408 The requirements in IEBC section 609 s. 408 are not included as part of chs. SPS 361 to 366.
Section 182. SPS 366.0701 is amended to read:
SPS 366.0701 Substitute the following wording for the requirements in IEBC section s. 701.2 but not the exception: Conformance. An existing building or portion thereof may not be altered such that the building becomes less safe than was required in its existing condition.
Section 183. SPS 366.0702 (1) and (2) are amended to read:
SPS 366.0702 (1) Substitute the following wording for the requirements in IEBC section 702.4 s. 702.7: All new work shall comply with materials and methods requirements in the IBC, IECC, IFGC, IMC, and IPC, as applicable, that specify material standards, detail of installation and connection, joints, penetrations, and continuity of any element, component, or system in the building.
(2) The requirements in IEBC section 702.4.1 s. 702.7.1 are not included as part of chs. SPS 361 to 366.
Section 184. SPS 366.0804 is renumbered SPS 366.0803 and amended to read:
SPS 366.0803 This is a department exception to the requirement in IEBC section 804.2 s. 803.2: The installation or extension of an automatic sprinkler system may exclude the protection of combustible concealed spaces that are not accessible in existing buildings. This exclusion is also applicable to sprinkler systems triggered by changes of use or additions.
Section 185. SPS 366.0809 is renumbered to SPS 366.0807 and amended to read:
SPS 366.0807 The exception to the requirements in IEBC section 809.1 s. 807.1 and the requirements in IEBC section 809.2 s. 807.2 are not included as part of chs. SPS 361 to 366.
Section 186. SPS 366.0810 is renumbered to SPS 366.0808 and amended to read:
SPS 366.0808 This is a department requirement in addition to IEBC s. 808. Substitute the following wording for the requirements in IEBC section 810.1: Where the occupant load of a story is increased by more than 20 percent, plumbing fixtures for the story shall be provided in quantities specified in the IBC based on the increased occupant load.
Section 187. SPS 366.0902 (1) is amended to read:
SPS 366.0902 (1) Boiler and furnace equipment rooms. Substitute the following wording for the requirements, but not the exceptions, in IEBC section 902.1.2 s. 902.2: Boiler and furnace equipment rooms. Boiler and furnace equipment rooms adjacent to or within Groups I-1, I-2, I-4, R-1, R-2, and R-4 occupancies shall be enclosed in compliance with IBC 509 heating equipment enclosure requirements.
Section 188. SPS 366.0902 (2) is repealed.
Section 189. SPS 366.0903 is repealed.