2.   At least 4 ties must be installed, at the end joist and first inside joist at each end of the deck as shown in Figure 19. A set of tension-ties must be installed for each structurally independent section of a multi-level deck.
3.   Approved tension-ties include the LTS19-TZ from USP or DTT1Z from Simpson Strong-Tie.
4.   The minimum capacity of each tension-tie is 750 pounds.
5.   Tension ties which are not available in a G-185 zinc coating require a barrier membrane separating the tension tie and the preservative-treated joist. The barrier membrane must be recommended for this location by its manufacturer.
6.   Tension-ties must be attached to the underside of the joists in accordance with the manufacturer's instructions. Tension-ties must be attached to the exterior wall with lag screws as shown in Figure 19. Lag screws must penetrate a minimum of 3 inches into the sill plate or top plate of a wood-framed wall.
7.   Where attaching to a concrete wall, lags screws may be replaced with adhesive or expansion anchors and a 1/2 inch threaded rod, with a withdrawal capacity of at least 750 pounds. The anchor must be installed in accordance with the manufacturer's instructions.
Figure 20
HOLD-DOWN TENSION DEVICE, WITH LEDGER BOARD
Hold-down tension devices. Hold-down tension devices, if used instead of perpendicular bracing as described above, must be provided in at least 2 locations per deck, and each device must have an allowable-stress-design capacity of at least 1,500 pounds.
Free-standing deck – attachment to house. Attach the deck's rim joist to the existing house exterior wall as shown in Figure 21 for a free-standing deck, if diagonal bracing parallel to the house is omitted, as described above. The wall must be sheathed with minimum 3/8 inch wood structural panel sheathing. Use lag screws or through-bolts if fastening to an existing band joist or wall stud; and use expansion or adhesive anchors if fastening to concrete or masonry. Do not attach to brick veneers. Verify this condition in the field prior to utilizing this method. Fasteners must be 16 inches on center and staggered in 2 rows. Flashing over the rim joist is required and must be installed in accordance with the flashing provisions in section 8.
Figure 21
ATTACHMENT OF FREE-STANDING DECK TO HOUSE FOR LATERAL SUPPORT
SECTION 12: DECKING
All decking materials must be wood or a wood-plastic composite and must comply with all of the following:
1.   Wood decking must be 2x4s, 2x6s, or five-quarter span-rated decking boards. Wood-plastic-composite sizes must be in accordance with the manufacturer's instructions. Plastic decking may be used if it is approved by a professional testing organization for supporting a live load of 40 psf and is installed according to the manufacturer's instructions.
2.   Decking must be attached in accordance with Figure 22, and may be placed at an angle of 45 to 90 degrees to the joists unless disallowed in the manufacturer's instructions. If the decking is wet, place it with no gap so that after drying, a ?-inch gap is created.
3.   Decking may overhang a joist by up to 3 inches unless disallowed in the manufacturer's instructions.
4.   The center-to-center joist spacing may be up to 24 inches for wood decking, but may not exceed 16 inches for wood-plastic-composite decking unless specified otherwise by the manufacturer.
5.   Each wood decking member must bear on a minimum of 4 joists or intermediate blocking between joists.
6.   Placement and attachment of wood-plastic composites must be in accordance with the manufacturer's instructions.
7.   Attach the decking to the rim joist in accordance with Figure 23.
Figure 22
TYPICAL DECKING
Figure 23
RIM JOIST CONNECTION
SECTION 13: GUARD AND POSTS
All open sides of a deck area that is more than 24 inches above grade – at any point within 36 inches beyond the edge of the deck – must have a guard that complies with Figure 24 and with all of the following:
1.   Required horizontal guards shall not have openings from the walking surface to the required guard height which allow passage of a sphere 4 inches in diameter, when applying a force of 4 pounds.
2.   Required guards at stairs shall not have openings which allow passage of a sphere 4 3/8 inches in diameter, when applying a force of 4 pounds, other than the triangular opening at the side of an open stair formed by the riser, tread, and bottom rail of a guard, which shall not allow passage of a 6 inch sphere, when applying a force of 4 pounds.
3.   Wet lumber must be spaced such that when shrinkage due to drying occurs, a compliant opening is maintained.
4.   Rope, cable, or a similar non-rigid material may be used instead of balusters if it is strung with maximum openings of 3 1/2 inches and with vertical supports no more than 4 feet apart.
5.   The guard and posts must withstand a 200-pound load applied in any direction.
6.   Guard-infill components, such as balusters and panel fillers, must withstand a horizontally applied, perpendicular load of 50 pounds on any one-foot-square area.
7.   Wood-plastic composites of equivalent dimensions may be substituted for the guard cap and infill elements shown in Figure 24 if the manufacturer's instructions permit this use.
Figure 24
GUARDS
Guard posts. Guard posts must be attached to the deck structure in accordance with all of the following:
Notching guard posts, as shown in Figure 25, is prohibited.
1.   Notching guard posts, as shown in Figure 25, is prohibited.
2.   Hold-down anchors must have a minimum capacity of 1,800 pounds.
3.   Guard posts may be attached to either side of the end joist or rim joist.
4.   Bolt holes for a post must be at least 2 inches from the wood edge, at least 2½ inches apart, and no more than 5 inches apart.
5.   Hold-down anchors, as shown in Figures 26 and 27, must be used to attach the guard post to the end joist and rim joist, respectively.
Figure 25
POST NOTCHING PROHIBITED
Figure 26
GUARD POST TO END JOIST
Figure 26
GUARD POST TO RIM JOIST
SECTION 14: STAIRS
Stair dimensions. Stair dimensions must comply with all of the following:
1.   The minimum width of a stairway is 36 inches.
2.   Handrails and associated trim may project a maximum of 4 1/2 inches into the required width at each side of the stairway. The minimum clear width at and below the handrail, including at treads and landings, cannot be less than 31 1/2 inches where a handrail is installed on one side, and 27 inches where handrails are provided on both sides.
3.   Stair geometry and openings must be as shown in Figure 27.
Figure 27
TREADS AND RISERS
4.   Within a stairway flight, the largest tread depth may not exceed the smallest tread depth by more than 3/8 inch, and the largest riser height may not exceed the smallest riser height by more than 3/8 inch.
5.   If the total vertical height of a stairway exceeds 12 feet, an intermediate landing is required and must be constructed as a free-standing deck with flush beams and with posts.
6.   Any landing width must equal or exceed the total width of the stairway it serves.
Stair stringers. Stringers must comply with all of the following:
1.   Stringers must be sawn or solid 2”x12”s complying with the above tread and riser dimensions.
2.   Cut stringers must be spaced no more than 18 inches on center.
3.   Stringers must bear on a solid surface, a minimum of 3 1/2 inches thick and 8 inches in diameter, and attach to the deck or a landing in accordance with Figure 28. Prior to placement of solid surface, all loose or organic material shall be removed.
4.   Stringer-span length is measured using the horizontally projected distance between the centerlines of bearing at each end.
5.   The span length of a cut stringer must not exceed 6 feet-0 inches, and the throat size of cut stringers must not be less than 5 inches, as shown in Figure 29.
Solid-stringer exception: Stringers for a stairway that has a width of 36 inches may have a horizontally projected span of up to 13 feet 3 inches if the stairway is framed solely with 2 solid stringers.
Intermediate-supported stringers: If the total stringer length exceeds the above dimensions, a 4”x4” post may be provided to support the stringer and shorten its span length. The 4”x4” post must be notched and bolted to the stringer in accordance with Figure 2. The post must bear over the middle one-third of a footing that is constructed in accordance with Figure 29 and must be attached as shown in Figure 2. An intermediate landing as described above may also be provided to shorten the stringer span.
Figure 28
STRINGER BEARING
Loading...
Loading...
Published under s. 35.93, Stats. Updated on the first day of each month. Entire code is always current. The Register date on each page is the date the chapter was last published.