subch. VI of ch. SPS 345 Subchapter VI — Changes, Additions or Omissions to ANSI/IIAR 2
SPS 345.600 SPS 345.600General. Changes, additions or omissions to ANSI/IIAR 2 are specified in this subchapter and are rules of the department and are not requirements of ANSI/IIAR 2.
SPS 345.600 Note Note: Under section SPS 345.40 (2) (b), closed-circuit ammonia mechanical refrigeration systems may be designed, constructed, installed and tested in accordance with ANSI/IIAR 2 and this subchapter, in combination with ANSI/ASHRAE standard 15 sections 10.2 and 11.
SPS 345.600 History History: CR 10-011: cr. Register August 2010 No. 656, eff. 9-1-10.
SPS 345.601 SPS 345.601Scope. The requirements of ANSI/IIAR 2 sections 1 and 2 are not included as part of this chapter.
SPS 345.601 Note Note: The sections in this subchapter are generally numbered to correspond with both the numbering of the subchapter and the section numbering in ANSI/IIAR 2. For example, section SPS 345.613 corresponds to subchapter 6 and to section 13 in ANSI/IIAR 2.
SPS 345.601 History History: CR 10-011: cr. Register August 2010 No. 656, eff. 9-1-10.
SPS 345.611 SPS 345.611Overpressure protection.
SPS 345.611(1) (1)Discharge capacity of plate heat exchangers. This is a department alternative to the requirements in ANSI/IIAR 2 section 11.2.7: The minimum required relief device capacity for a plate heat exchanger based on an external heat addition scenario may be calculated in accordance with the following equation:
where:
Cr,plate HX   =   minimum required relief device capacity for the
    plate heat exchanger (lbm/min of air)
f   =   relief device capacity factor
L   =   length of the plate pack (ft)
W   =   width of the plate pack (ft)
H   =   height of the plate pack (ft)
SPS 345.611(2) (2)Discharge piping for atmospheric pressure relief. This is a department rule in addition to the requirements in ANSI/IIAR 2 section 11.3.6.1: Appendix A Tables A-3 may not be used for schedule 80 piping.
SPS 345.611 History History: CR 10-011: cr. Register August 2010 No. 656, eff. 9-1-10.
SPS 345.613 SPS 345.613Machinery room.
SPS 345.613(1) (1)Emergency remote controls.
SPS 345.613(1)(a)(a) Ventilation. Substitute the following wording for the requirements in ANSI/IIAR 2 section 13.2.1.4: Emergency remote controls for the mechanical means of ventilation shall be provided and be located immediately outside the machinery room, at the principal entrance to the room.
SPS 345.613(1)(b) (b) Compressors. Substitute the following wording for the requirements in ANSI/IIAR 2 section 13.3.1.6: Emergency remote controls to stop the action of the refrigeration compressors shall be provided and be located immediately outside the machinery room, at the principal entrance to the room.
SPS 345.613(2) (2)Signage. This is a department rule in addition to the requirements in ANSI/IIAR-2 section 13.3: A legible, easily accessible, permanent sign shall be securely attached to the mechanical refrigeration system, showing that the system was designed in accordance with ANSI/IIAR-2.
SPS 345.613 History History: CR 10-011: cr. Register August 2010 No. 656, eff. 9-1-10.
subch. VII of ch. SPS 345 Subchapter VII — Ozone-Depleting Refrigerants
SPS 345.70 SPS 345.70Ozone-depleting refrigerants.
SPS 345.70(1)(1)Cleaning of equipment. Ozone-depleting refrigerant may not be used for cleaning purposes, including the cleaning of interior or exterior surfaces of refrigeration equipment.
SPS 345.70(2) (2)Transferring refrigerant. Whenever ozone-depleting refrigerant is removed from refrigeration equipment, the ozone-depleting refrigerant shall be transferred to storage containers using equipment that is approved by the department. The department shall approve any transfer equipment if an approved nationally recognized testing laboratory has certified the equipment.
SPS 345.70 Note Note: The Department will accept equipment that has been tested and certified in accordance with the Air-Conditioning and Refrigeration Institute (ARI) standard ARI 740.
SPS 345.70(3) (3)Releasing refrigerant. Ozone-depleting refrigerant may not be knowingly or negligently released to the environment, except for minimal releases that occur as a result of efforts to recover, reclaim or recycle ozone-depleting refrigerant removed from refrigeration equipment.
SPS 345.70(4) (4)Adding refrigerant. Before putting additional ozone-depleting refrigerant into refrigeration equipment, the refrigeration equipment shall be inspected and repaired if a leak is found or suspected. A yearly leak rate identified by the federal environmental protection agency shall be used to determine whether repairs are necessary.
SPS 345.70 Note Note: See subpart F of part 82 in title 40 of the Code of Federal Regulations for further requirements relating to ozone-depleting refrigerants.
SPS 345.70 History History: CR 03-012: cr. Register October 2003 No. 574, eff. 11-1-03; CR 10-011: renum. from Comm 45.21 and am. (2) and (4) Register August 2010 No. 656, eff. 9-1-10; correction in (1) made under s. 13.92 (4) (b) 7., Stats., Register December 2011 No. 672; CR 13-014: r. (1), renum. (2) to (5) to (1) to (4) Register September 2013 No. 693, eff. 10-1-13.
Loading...
Loading...
Published under s. 35.93, Stats. Updated on the first day of each month. Entire code is always current. The Register date on each page is the date the chapter was last published.