SPS 365.0301(1)
(1)
Scope. Substitute the following wording for the requirements in IFGC section 301.1: This chapter shall govern the approval and installation of all equipment and appliances that comprise parts of the installations regulated by this code.
SPS 365.0301(2)
(2) listed and labeled. Substitute the following wording for the requirements in IFGC section 301.3: The requirements as specified in
s. SPS 364.0301 (3) shall apply.
SPS 365.0303(1)
(1)
General. This is a department rule in addition to the requirements in IFGC section 303.1: If the air entering the heat exchanger of all gas–fired equipment is 30
oF or lower, the heat exchanger and burners shall be constructed of corrosion–resistive materials.
SPS 365.0303(2)
(2) Prohibited locations. The exceptions 3. and 4. in IFGC section 303.3 are not included as a part of this code.
SPS 365.0304
SPS 365.0304 Combustible air. Barometric dampers may not be used for combustion air.
SPS 365.0304 History
History: CR 16-094: cr. Register April 2018 No. 748, eff. 5-1-18. SPS 365.0400
SPS 365.0400 Gas piping installations. Substitute the following wording for the requirements and exceptions in IFGC chapter 4: All gas piping and gas piping installations shall comply with NFPA 54, National Fuel Gas Code.
SPS 365.0400 History
History: CR 00-179: cr.
Register December 2001 No. 552, eff. 7-1-02.
SPS 365.0501(1)
(1) This is a department informational note to be used under IFGC chapter 5: Note: For DHS licensed healthcare facilities as specified in chs.
DHS 124,
132, and
134, also refer to NFPA 211 as adopted in these chapters.
SPS 365.0501(2)
(2) The requirements in
section IFGC 501.8 item 8 are not included as a part of this chapter.
SPS 365.0501(3)
(3) Substitute the following wording for the requirements in
section IFGC 501.8 item 10: Infrared radiant heaters listed for unvented use and not provided with flue collars.
SPS 365.0501 History
History: CR 00-179: cr.
Register December 2001 No. 552, eff. 7-1-02.
SPS 365.0502
SPS 365.0502 Door swing. The requirements in IFGC section 502.7.1 are not included as part of
chs. SPS 361 to
366.
SPS 365.0502 History
History: CR 16-094: cr. Register April 2018 No. 748, eff. 5-1-18. SPS 365.0621
SPS 365.0621 Unvented heaters. Substitute the following wording for the requirements in IFGC section 621: Portable or permanently installed, gas-fired, unvented heating appliances may not be installed, except during construction or demolition of a building if the appliances are provided in accordance with
ch. SPS 314.
SPS 365.0621 Note
Note: See s.
SPS 364.0801 (2) for use of portable unvented heating appliances that are fired with other fuels.
SPS 365.0630
SPS 365.0630 Infrared radiant heaters. This is a department rule in addition to the requirements in IFGC section 630.1: Unvented infrared radiant heaters may be used only in the following occupancies:
SPS 365.0630 History
History: CR 00-179: cr.
Register December 2001 No. 552, eff. 7-1-02;
CR 06-120: renum. from s.
Comm 65.0629 and am. (intro.)
Register February 2008 No. 626, eff. 3-1-08;
CR 10-103: r. and recr.
Register August 2011 No. 668, eff. 9-1-11.
SPS 365.0631
SPS 365.0631 Boilers. Substitute the following wording for the requirements in IFGC section 631: The provisions of
ch. SPS 341 shall govern the installation, alteration and repair of boilers and pressure vessels.
SPS 365.0631 History
History: CR 00-179: cr.
Register December 2001 No. 552, eff. 7-1-02;
CR 06-120: renum. from s.
Comm 65.0630 and am.
Register February 2008 No. 626, eff. 3-1-08; correction made under s.
13.92 (4) (b) 7., Stats.,
Register December 2011 No. 672.
SPS 365.0632
SPS 365.0632 Equipment installed in existing unlisted boilers. The requirements in IFGC section 632 are not included as part of this chapter.
SPS 365.0632 History
History: CR 06-120: cr.
Register February 2008 No. 626, eff. 3-1-08.
SPS 365.0800
SPS 365.0800 Referenced standards. This is a department rule in addition to the requirements in IFGC chapter 8: The following standard is incorporated by reference into
chs. SPS 361 to
366: ANSI Z223.1/NFPA 54-2015, National Fuel Gas Code.
SPS 365.0800 Note
Note: NFPA standards may be purchased from the National Fire Protection Association, One Batterymarch Park, P.O. Box 9101, Quincy, MA 02269-9101.
SPS 365.0800 Note
Copies of the standard adopted under this section are on file in the offices of the department and the legislative reference bureau.
SPS 365.0900
SPS 365.0900 Appendices. IFGC Appendices A to D are not included as part of this chapter.
SPS 365.0900 History
History: CR 00-179: cr.
Register December 2001 No. 552, eff. 7-1-02;
CR 06-120: renum. from s.
Comm 65.0800 Register February 2008 No. 626, eff. 3-1-08; correction made under s.
13.92 (4) (b) 1., Stats.,
Register February 2008 No. 626.