SPS 366.0202 Note Note: Section 101.121 (2) (c) of the Statutes reads as follows: “Qualified historic building" means a historic building which:
  1. Is listed on, or has been nominated by the state historical society for listing on, the national register of historic places in Wisconsin or the state register of historic places;
  2. Is included in a district which is listed on, or has been nominated by the state historical society for listing on, the national register of historic places in Wisconsin or the state register of historic places, and has been determined by the state historical society to contribute to the historic significance of the district;
  2m. Is determined by the state historical society to be eligible for listing on the national register of historic places in Wisconsin or the state register of historic places;
  3. Is listed on a certified local register of historic property; or
  4. Is included in a district which is listed on a certified local register of historic property, and has been determined by the city, village, town or county to contribute to the historic significance of the district.
SPS 366.0202 Note Note: Form SBD-7728 may be utilized to provide the status on a historic commercial building. This form is available on the department's website at dsps.wi.gov, or by request from the Department of Safety and Professional Services, P. O. Box 7302, Madison, Wisconsin 53707-7302, or call (608) 266-2112.
SPS 366.0202(2)(b) (b) Substitute the following definition for the corresponding definition in IEBC section 202: “Unsafe" means buildings, structures or equipment that are unsanitary, or that are deficient due to inadequate means of egress facilities, inadequate light and ventilation, or that constitute a fire hazard, or in which the structure or individual structural members meet the definition of “dangerous," or that are otherwise dangerous to human life or the public welfare, or that involve illegal or improper occupancy or inadequate maintenance shall be deemed unsafe.
SPS 366.0202(2)(c) (c) Substitute the following definition for the corresponding definition in IEBC section 202: “Work area” means that portion or portions of a building consisting of all reconfigured spaces as indicated on the construction documents. Work area excludes other portions of the building where incidental work entailed by the intended work must be performed and portions of the building where work not initially intended by the owner is specifically required by chs. SPS 361 to 366. The work area is the area reconfigured with full height walls or the area that has its required egress reconfigured.
SPS 366.0202 History History: CR 06-120: cr. Register February 2008 No. 626, eff. 3-1-08; correction in (2) made under s. 13.92 (4) (b) 7., Stats., Register February 2008 No. 626; CR 10-103: am. (2), cr. (2) (b) Register August 2011 No. 668, eff. 9-1-11; CR 16-094: cr. (2) (c) Register April 2018 No. 748, eff. 5-1-18.
SPS 366.0400 SPS 366.0400Prescriptive compliance method. The requirements in IEBC chapter 4 are not included as part of chs. SPS 361 to 366, except for the requirements in IEBC section 410 when applied by IEBC section 1401.2.5.
SPS 366.0400 History History: CR 06-120: cr. Register February 2008 No. 626, eff. 3-1-08; CR 10-103: am. Register August 2011 No. 668, eff. 9-1-11; CR 16-094: renum. from 366.0300 and am. Register April 2018 No. 748, eff. 5-1-18.
SPS 366.0600 SPS 366.0600Carbon monoxide alarms for CBRF's accommodating fewer than 20 residents. These are department rules in addition to the requirements in IEBC chapter 6 and are established under the authority of s. 101.127, Stats.:
SPS 366.0600(1)(a)(a) Existing buildings converted to be community-based residential facilities accommodating fewer than 20 residents shall be provided with carbon monoxide alarms by July 1, 2013, when either one of the following conditions exists:
SPS 366.0600(1)(a)1. 1. The building contains fuel-burning appliances.
SPS 366.0600(1)(a)2. 2. The building has an attached garage.
SPS 366.0600(1)(b) (b) This section applies to community-based residential facilities described under par. (a) in existence prior to January 1, 2005.
SPS 366.0600 Note Note: Pursuant to s. 101.01 (12), Stats., an existing building converted to be community-based residential facility accommodating fewer than 20 residents is not defined to be a “public building." See also s. SPS 361.02 (4).
SPS 366.0600(2) (2)Carbon monoxide alarms shall be listed and labeled to be in conformance with one of the following standards:
SPS 366.0600(2)(a) (a) UL 2034.
SPS 366.0600(2)(b) (b) UL 2075.
SPS 366.0600(3)(a)(a) A carbon monoxide alarm shall be installed in accordance with the instructions of its manufacturer.
SPS 366.0600(3)(b) (b) A carbon monoxide alarm shall be provided on each floor level of an existing building accommodating a community-based residential facility described under sub. (1) (a), if the building contains fuel-burning appliances.
SPS 366.0600(3)(c) (c) A carbon monoxide alarm shall be provided on each floor level where sleeping units are located in an existing building accommodating a community-based residential facility described under sub. (1) (a), if the building has an attached garage and no fuel-burning appliances.
SPS 366.0600 History History: CR 10-103: cr. Register August 2011 No. 668, eff. 9-1-11; CR 16-094: renum. from 366.0500 and am. (intro.) Register April 2018 No. 748, eff. 5-1-18.
SPS 366.0603 SPS 366.0603Smoke alarms. These are department rules in addition to the requirements in IEBC section 603:
SPS 366.0603(1) (1)No smoke alarm, including an alarm that exists on September 1, 2011, may remain in service for more than that specified by the manufacturer.
SPS 366.0603(2) (2)The replacement of a smoke alarm that uses a battery as its primary power source shall be a new smoke alarm that complies with UL 217 and either of the following:
SPS 366.0603(2)(a) (a) The alarm is hardwired in accordance with IBC section 907.2.11.4 and has backup power in accordance with that section.
SPS 366.0603(2)(b) (b) The alarm uses, as its primary power source, a non-replaceable, non-removable battery that is capable of powering the alarm for at least 10 years.
SPS 366.0603 History History: CR 10-103: cr. Register August 2011 No. 668, eff. 9-1-11; CR 16-094: renum. from 366.0503 and am. (intro.) Register April 2018 No. 748, eff. 5-1-18.
SPS 366.0605 SPS 366.0605Accessibility. Substitute the following wording for the requirements in IEBC section 605.1: General. Repairs shall maintain accessibility in accordance with IEBC section 705.1.13.
SPS 366.0605 History History: CR 16-094: cr. Register April 2018 No. 748, eff. 5-1-18; correction made under s. 13.92 (4) (b) 1., Stats., Register October 2018 No. 754.
SPS 366.0606 SPS 366.0606Structural evaluation. The requirements in IEBC sections 606.2 to 606.2.5 are not included as part of chs. SPS 361 to 366.
SPS 366.0606 History History: CR 06-120: cr. Register February 2008 No. 626, eff. 3-1-08; CR 16-094: renum. from 366.0506 and am. Register April 2018 No. 748, eff. 5-1-18.
SPS 366.0609 SPS 366.0609Repairs — plumbing. The requirements in IEBC section 609 are not included as part of chs. SPS 361 to 366.
SPS 366.0609 Note Note: See the Wisconsin Uniform Plumbing Code, chs. SPS 382 to 387, for plumbing and water conservation provisions.
SPS 366.0609 History History: CR 06-120: cr. Register February 2008 No. 626, eff. 3-1-08; CR 16-094: renum. from 366.0509 and am. Register April 2018 No. 748, eff. 5-1-18; correction in (title) made under s. 13.92 (4) (b) 2., Stats., Register April 2018 No. 748.
SPS 366.0701 SPS 366.0701Alterations. Substitute the following wording for the requirements in IEBC section 701.2: Conformance. An existing building or portion thereof may not be altered such that the building becomes less safe than was required in its existing condition.
SPS 366.0701 History History: CR 16-094: cr. Register April 2018 No. 748, eff. 5-1-18.
SPS 366.0702 SPS 366.0702Building elements and materials.
SPS 366.0702(1)(1)Materials and methods. Substitute the following wording for the requirements in IEBC section 702.4: All new work shall comply with materials and methods requirements in the IBC, IECC, IFGC, IMC, and IPC, as applicable, that specify material standards, detail of installation and connection, joints, penetrations, and continuity of any element, component, or system in the building.
SPS 366.0702(2) (2) International fuel gas code. The requirements in IEBC section 702.4.1 are not included as part of chs. SPS 361 to 366.
SPS 366.0702 History History: CR 06-120: cr. Register February 2008 No. 626, eff. 3-1-08; CR 10-103: am. Register August 2011 No. 668, eff. 9-1-11; CR 16-094: renum. from 366.0602 and am. Register April 2018 No. 748, eff. 5-1-18.
SPS 366.0704 SPS 366.0704Means of egress.
SPS 366.0704(1)(1)Alterations. Substitute the following wording for the requirements in IEBC section 704.1: Alterations shall be done in a manner that maintains the level of protection required for the means of egress prior to the alteration.
SPS 366.0704(2) (2) Stairway width. This is a department rule in addition to the requirements in IEBC section 704: Where installing an inclined platform lift or stairway chairlift, the clear-passage width shall be provided with the lift in the unfolded, usable position—except where an existing, previously approved lift is being replaced, the clear-passage width may remain as it was with the original lift in place, but it may not be reduced by the replacement.
SPS 366.0704 History History: CR 14-020: cr. Register August 2014 No. 704, eff. 9-1-14; CR 16-094: cr. (title), (1), renum. (2) from 366.0604 and am. Register April 2018 No. 748, eff. 5-1-18.
SPS 366.0804 SPS 366.0804Automatic sprinkler systems. This is a department exception to the requirement in IEBC section 804.2: The installation or extension of an automatic sprinkler system may exclude the protection of combustible concealed spaces that are not accessible in existing buildings. This exclusion is also applicable to sprinkler systems triggered by changes of use or additions.
SPS 366.0804 History History: CR 10-103: renum. from Comm 66.0701 and am. Register August 2011 No. 668, eff. 9-1-11; CR 16-094: renum. from 366.0704 and am. Register April 2018 No. 748, eff. 5-1-18.
SPS 366.0809 SPS 366.0809Altered existing mechanical systems. The exception to the requirements in IEBC section 809.1 and the requirements in IEBC section 809.2 are not included as part of chs. SPS 361 to 366.
SPS 366.0809 History History: CR 06-120: cr. Register February 2008 No. 626, eff. 3-1-08; CR 16-094: renum. from 366.0709 and am. Register April 2018 No. 748, eff. 5-1-18.
SPS 366.0810 SPS 366.0810Minimum plumbing fixtures. Substitute the following wording for the requirements in IEBC section 810.1: Where the occupant load of a story is increased by more than 20 percent, plumbing fixtures for the story shall be provided in quantities specified in the IBC based on the increased occupant load.
SPS 366.0810 History History: CR 06-120: cr. Register February 2008 No. 626, eff. 3-1-08; CR 16-094: renum. from 366.07010 and am. Register April 2018 No. 748, eff. 5-1-18.
SPS 366.0902 SPS 366.0902Special use and occupancy.
SPS 366.0902(1)(1)Boiler and furnace equipment rooms. Substitute the following wording for the requirements, but not the exceptions, in IEBC section 902.1.2: Boiler and furnace equipment rooms. Boiler and furnace equipment rooms adjacent to or within Groups I-1, I-2, I-4, R-1, R-2, and R-4 occupancies shall be enclosed in compliance with IBC 509 heating equipment enclosure requirements.
SPS 366.0902(2) (2) Emergency controls. The requirements in IEBC section 902.2.1 are not included as part of chs. SPS 361 to 366.
SPS 366.0902 History History: CR 06-120: cr. Register February 2008 No. 626, eff. 3-1-08; CR 16-094: cr. (title), (1), renum. (2) from 366.0802 and am. Register April 2018 No. 748, eff. 5-1-18; correction in (1) made under s. 13.92 (4) (b) 7., Stats., Register October 2018 No. 754.
SPS 366.0903 SPS 366.0903Building elements and materials. Substitute the following wording for the requirements in IEBC section 803.2.1: All existing interior vertical openings in the work area connecting two or more floors shall be enclosed with approved assemblies having a fire resistance rating of not less than one hour with approved opening protectives.
SPS 366.0903 History History: CR 16-094: cr. Register April 2018 No. 748, eff. 5-1-18.
SPS 366.0904 SPS 366.0904Level 3 alterations fire protection.
SPS 366.0904(1)(1)Upholstered furniture. The requirement in IEBC section 904.1.3 condition 3 is not included as part of chs. SPS 361 to 366.
SPS 366.0904(2) (2) Fire alarm and detection systems. Substitute the requirements from 2009 IEBC section 804.2 for the requirements in IEBC section 904.2.
SPS 366.0904 History History: CR 16-094: cr. Register April 2018 No. 748, eff. 5-1-18.
SPS 366.0909 SPS 366.0909Level 3 alterations plumbing. These are department rules in addition to the requirements in IEBC chapter 9:
SPS 366.0909(1) (1)Pursuant to s. 101.128, Stats., level 3 alterations within an existing facility where the public congregates shall necessitate that plumbing fixtures serving the work area be provided in a ratio of at least 2 water closets for females as to each water closet and urinal for the males.
SPS 366.0909(2)(a)(a) Under this section “facility where the public congregates" has the meaning has given in s. 101.128 (1) (b), Stats.
SPS 366.0909 Note Note: Section 101.128 (1) (b), Stats., reads: “Facility where the public congregates" means any of the following that has a general capacity or a seating capacity of 500 or more persons:
SPS 366.0909 Note 1. An amusement facility.
SPS 366.0909 Note 2. A convention or trade hall or center.
SPS 366.0909 Note 3. A specialty event center.
SPS 366.0909 Note 4. A sports or entertainment arena, center or building.
SPS 366.0909 Note 5. A stadium.
SPS 366.0909 Note 6. An airport, bus terminal, train station or other transportation center.
SPS 366.0909(2)(b) (b) Under this section “alterations" has the meaning has given in s. 101.128 (1) (d), Stats., for “renovation".
SPS 366.0909 Note Note: Section 101.128 (1) (d), Stats., reads: “Renovation" means any structural remodeling, improvement or alteration of an existing facility where the public congregates. “Renovation" does not include any of the following:
SPS 366.0909 Note 1. Reroofing.
SPS 366.0909 Note 2. Cosmetic remodeling, including painting or the installation of wall covering, of paneling, of floor covering or of suspended ceilings.
SPS 366.0909 Note 3. An alteration to an electrical or mechanical system.
SPS 366.0909 History History: CR 06-120: cr. Register February 2008 No. 626, eff. 3-1-08; CR 16-094: renum. from 366.0809 and am. (intro.) REgister April 2018 No. 748, eff. 5-1-18; correction in (title) made under s. 13.92 (4) (b) 2., Stats., Register April 2018 No. 748.
SPS 366.1001 SPS 366.1001Change of occupancy.
SPS 366.1001(1)(1)change of occupancy approval. Substitute the following wording for the requirements in IEBC section 1001.2: A change of occupancy or a change of occupancy within a space where there is a different fire protection system threshold requirement in IBC chapter 9 may not be made to any structure without the approval of the code official. An increased occupant load may trigger additional means of egress or fire protection requirements.
SPS 366.1001(2) (2) Change of occupancy classification. This is a department rule in addition to the requirements in IEBC section 1001.2.2: Buildings undergoing a change in occupancy that would result in an increase in demand for either fossil fuel or electrical energy shall comply with the IECC.
SPS 366.1001(3) (3) Certification of occupancy required. The requirements in IEBC section 1001.3 are not included as part of chs. SPS 361 to 366.
SPS 366.1001 History History: CR 06-120: cr. Register February 2008 No. 626, eff. 3-1-08; CR 10-103: am. (1) Register August 2011 No. 668, eff. 9-1-11; CR 16-094: renum. (title), (1) to (3) from 366.0901 (title), (1) to (3) and am., renum. (4) to SPS 366.1012 Register April 2018 No. 748, eff. 5-1-18.
SPS 366.1010 SPS 366.1010Change of occupancy plumbing. Substitute the following wording for the requirements in IEBC section 1010: Where the occupant load of a story is increased by more than 20 percent, plumbing fixtures for the story shall be provided in quantities specified in the IBC based on the increased occupant load.
SPS 366.1010 History History: CR 06-120: cr. Register February 2008 No. 626, eff. 3-1-08; CR 10-103: renum. from Comm 66.0910 Register August 2011 No. 668, eff. 9-1-11; CR 16-094: renum. from 366.0912 and am. Register April 2018 No. 748, eff. 5-1-18; correction in (title) made under s. 13.92 (4) (b) 2., Stats., Register April 2018 No. 748.
SPS 366.1011 SPS 366.1011Other requirements.
SPS 366.1011(1)(1)Elevator recall. This is a department rule in addition to the requirements in IEBC section 1011: At least one existing elevator shall be provided with emergency recall operation and emergency in-car operation complying with ch. SPS 318 when an existing building or structure that is greater than 60 feet in height is changed to include a Group R-1 or R-2 occupancy.
SPS 366.1011(2) (2) Carbon monoxide alarms. This is a department rule in addition to the requirements in IEBC section 1011: A building or a portion of a building changed to be or include a residential building as defined under s. 101.149 (1) (b), Stats., shall be provided with carbon monoxide alarms or detectors in accordance with s. SPS 362.0915.
SPS 366.1011 History History: CR 06-120: cr. Register February 2008 No. 626, eff. 3-1-08; EmR0826: emerg. renum. to be (1), cr. (1) (title) and (2), eff. 10-1-08; CR 08-085: renum. to be (1), cr. (1) (title) and (2) Register May 2009 No. 641, eff. 6-1-09; correction in (1), (2) made under s. 13.92 (4) (b) 7., Stats., Register December 2011 No. 672; CR 16-094: renum. from 366.0911 and am. Register April 2018 No. 748, eff. 5-1-18; correction in (2) under s. 13.92 (4) (b) 7., Stats., Register April 2018 No. 748.