4.   The distance then, between this established “spill level” and the end of the lowest water supply pipe/spout, is the air-gap.
5.   The minimum air-gap (“Y”) is the distance between the supply pipe/spout and the “spill level” established in the receptacle/fixture.
6.   The “spill level” shall be a distance no greater that one half of the distance measured as “Y,” (½ “Y”) above the discharge opening in the receptacle/fixture. Therefore, the air-gap between the supply pipe/spout and the highest portion of the opening that discharges to the atmosphere shall be a distance no greater than one and one half “Y” (1 ½ “Y”).
Note: In any case, regardless if the end of the pipe/spout is cut square or at an angle, the air-gap is the distance between the lowest end of the pipe/spout and the “spill level” of the receptacle/fixture.
The measurement for this air-gap, however, could be as much as 3 times the diameter of the pipe/spout depending upon the number of near walls. The distance of a near wall is a relationship to the diameter of the pipe/spout and the measurement from the wall to the closest side of the pipe/spout:
1.   If there is one near wall, and the distance between that near wall and the closest edge of the supply pipe/spout is greater than 3 times the diameter of the supply pipe/spout, then the minimum air-gap is 2 times the diameter of the supply pipe/spout.
2.   If there is one near wall, and the distance to the closest edge of the supply pipe/spout is less than 3 times the diameter of the pipe/spout, then the minimum air-gap is 3 times the diameter of the supply pipe/spout.
3.   If there are 2 near walls, and the distance between the near wall(s) and closest edge of the supply pipe/spout is greater than 4 times the diameter of the supply pipe/spout, then the minimum air-gap is 2 times the diameter of the supply pipe/spout.
4.   If there are 2 near walls, and the distance to the closest edge of the supply pipe/spout is less than 4 times the diameter of the supply pipe/spout, then the minimum air-gap is 3 times the diameter of the supply pipe/spout.
It has been determined that 2 or more near walls generally have little effect on the need to increase the air-gap to more than 3 times the diameter of the supply pipe/spout.
Note: See the following sketches as examples of an air-gap with pipe/spouts terminating above the flood level rim of the receptacle/fixture, of an air-gap with pipe/spouts terminating below the flood level rim of the receptacle/fixture and of an air-gap with pipe/spouts when terminating by one near wall.
A-382.41 (5)-1. AIR-GAP WITH PIPE/SPOUT(S) ABOVE FLOOD LEVEL RIM OF RECEPTACLE/FIXTURE.
Minimum 1 inch
or
two times the pipe diameter, whichever is greater
WATER SUPPLY AIR-GAP ASME 112.1.2
A-382.41 (5)-2. AIR-GAP WITH PIPE/SPOUT(S) BELOW FLOOD LEVEL RIM OF RECEPTACLE/FIXTURE.
Spill level
Air-gap
Flood level
Water supply
1½ “Y”
“Y”
½ “Y”
One near wall
2 inch diameter water supply
If distance is 3 times or greater than the diameter of water supply (2 inch), then the air-gap is 2 times the diameter of the water supply, (i.e., 2 X 2 = 4 inches)
Flood level
Minimum 6 inches
Less than 3 inches
If the distance is less than 3 times the diameter of the water supply (2 inch), then the air-gap is 3 times the diameter of the water supply, (i.e., 3 X 2 = 6 inches)
A PARTIAL TABLE FOR THE SELECTION OF BACKFLOW PROTECTION *
*Any situation may be subject to an alternate approval.
1 If less than 15 pounds steam or 30 pounds water and nontoxic chemicals.
2 If greater than 15 pounds steam or 30 pounds water and toxic chemicals.
3 Requires backflow protection even if there is a plain end spout.
4 Requires separate water supply terminating without a hose thread, or the manufacturer must provide a bleed device to connect to the janitor sink faucet spout.
5 Or, provide bottled water conversion unit.
6 For outlets other than the required ASSE 1019 hydrants.
7 If provided with hose threads or serrated nipple.
8 Faucet meeting ASME A112.18.1M that includes backflow protection requirements.
9 Hydrants that bleed into the ground and hydrants that are flush with the grade are prohibited.
A-382.41 (5) (f)-1. CROSS CONNECTION CONTROL ASSEMBLY INSTALLATION.
A-382.41 (5) (f)-2. CROSS CONNECTION CONTROL ASSEMBLY INSTALLATION.
A-382.41 (5) (f)-3. CROSS CONNECTION CONTROL ASSEMBLY INSTALLATION.
A-382.41 (5) (f)-4. CROSS CONNECTION CONTROL ASSEMBLY INSTALLATION.
A-382.41 (5) (f)-5. CROSS CONNECTION CONTROL ASSEMBLY INSTALLATION.
A-382.50 (3) (b) 5. OPTIONS FOR TEMPERATURE CONTROL IN HEALTH CARE FACILITIES. The following sketches provide options for fail safe installations at the bathing and shower fixture and temperature control at handwashing fixtures.
Option 1. Fail safe solenoid provided at main mixer meeting ASSE 1017, pressure balanced tub/shower valve meeting ASSE 1016 and limit stop faucets at lavatory and kitchen sink.
Circulated temperature initiated at 140° F
180° F. maximum water heater
Limit stop faucet
Lavatory
Tub/shower
Pressure balance valve with limit stop (ASSE 1016)
Kitchen sink
Limit stop faucet
Fail safe solenoid
Sensor
ASSE 1017 main mixer
  Option 2. Fail safe solenoid provided at main mixer meeting ASSE 1017, pressure balanced tub/shower valve meeting ASSE 1016 and thermostatic mixer meeting ASSE 1016 at lavatory and kitchen sink faucets.
180° F. maximum water heater
ASSE 1017 main mixer
ASSE 1016
thermostatic mixer in supply lines to faucet
Lavatory
Tub/shower
Pressure balance valve with limit stop (ASSE 1016)
Kitchen sink
ASSE 1016
thermostatic mixer in supply lines to faucet
Fail safe solenoid
Sensor
Circulated temperature initiated at 140° F
Option 3. Fail safe solenoid provided at main mixer meeting ASSE 1017, thermostatic tub/shower valve meeting ASSE 1016 and limit stop faucets at lavatory and kitchen sink.
Limit stop faucet
Lavatory
Tub/shower
Thermostatic mixing valve (ASSE 1016)
Kitchen sink
Limit stop faucet
Fail safe solenoid
Sensor
Circulated temperature initiated at 140° F
ASSE 1017 main mixer
180° F. maximum water heater
Option 4. Fail safe solenoid provided at main mixer meeting ASSE 1017, combination thermostatic/pressure balance mixing valve meeting ASSE 1016 and limit stop faucets at lavatory and kitchen sink.
180o F. maximum water heater
Limit stop faucet
Lavatory
Tub/shower
Pressure balance/thermostatic mixing valve (ASSE 1016)
Kitchen sink
Limit stop faucet
Fail safe solenoid
Sensor
ASSE 1017 main mixer
Circulated temperature initiated at 140° F
Option 5. Fail safe solenoid, combination pressure balanced/thermostatic tub/shower valve meeting ASSE 1016 and thermostatic mixer meeting ASSE 1016 at lavatory and kitchen sink faucets.
180o F. maximum water heater
ASSE 1016
thermostatic mixer in supply lines to faucet
Lavatory
Tub/shower
Thermostatic/pressure balance mixing valve (ASSE 1016)
Kitchen sink
ASSE 1016
thermostatic mixer in supply lines to faucet
Sensor
Circulated temperature initiated at 140oF
A-382.51 (3) MOBILE HOME SITES AND PARKS. Mobile home building sewer and water service connections.
Sewer
Water
Frost sleeve
4 inches minimum
6 inches minimum
42 inches minimum
Grade
Frost sleeves terminate 2 inches above grade
Loading...
Loading...
Published under s. 35.93, Stats. Updated on the first day of each month. Entire code is always current. The Register date on each page is the date the chapter was last published.