SPS 316.314(2) (2)Outlet boxes. This is a department rule in addition to the requirements of 2011 NEC 314.27 (A): In a dwelling unit, a ceiling outlet box installed for use as a lighting fixture outlet in a habitable room or kitchen and located where a ceiling fan could be installed shall be a type listed for ceiling fan support.
SPS 316.314 History History: CR 08-047: cr. Register February 2009 No. 638, eff. 3-1-09; correction in (1) made under s. 13.92 (4) (b) 7., Stats., Register December 2011 No. 672; CR 13-042: am. (title) Register November 2013 No. 695, eff. 12-1-13; CR 16-093: am. Register June 2018 No. 650, eff. 8-1-18.
SPS 316.334 SPS 316.334Nonmetallic-sheathed cable: Types NM, NMC and NMS.
SPS 316.334(1)(1) Uses permitted. Substitute the following wording for 2011 and 2017 NEC 334.10 (3): Other structures permitted to be of Types III, IV, and V construction except as prohibited in NEC 334.12.
SPS 316.334(2) (2)Types NM, NMC, and NMS. The requirements specified in 2011 and 2017 NEC 334.12 (A) (2) are not included as part of this chapter.
SPS 316.334 History History: CR 08-047: cr. Register February 2009 No. 638, eff. 3-1-09; CR 13-042: am. (2) (title) Register November 2013 No. 695, eff. 12-1-13; CR 16-093: am. Register June 2018 No. 650, eff. 8-1-18.
SPS 316.358 SPS 316.358 Uses permitted. This is a department rule in addition to the requirements of 2011 and 2017 NEC 358.12: Electrical metallic tubing may not be used in direct contact with earth, in concrete slabs or floors poured on earth, or in exterior concrete walls below grade.
SPS 316.358 History History: CR 08-047: cr. Register February 2009 No. 638, eff. 3-1-09; CR 16-093: am. Register June 2018 No. 650, eff. 8-1-18.
SPS 316.400 SPS 316.400 Flexible cords and cables.
SPS 316.400(1) (1) This is a department exception in addition to the exception in 2011 NEC 400.8 (4): Exception No. 2: Flexible cords and cables permitted by NEC 400.7 (A) that are connected to sources other than busways may be attached to adequately supported equipment or building surfaces provided the type of cord or cable, the attachment to the building and equipment, and the support comply with the provisions of NEC 368.56 (B).
SPS 316.400(2) (2) This is a department exception in addition to the exception in 2017 NEC 400.12 (4): Exception No. 2: Flexible cords and cables permitted by NEC 400.10 (A) that are connected to sources other than busways may be attached to adequately supported equipment or building surfaces provided the type of cord or cable, the attachment to the building and equipment, and the support comply with the provisions of NEC 368.56 (B).
SPS 316.400 History History: CR 08-047: cr. Register February 2009 No. 638, eff. 3-1-09; CR 13-042: am. (title) Register November 2013 No. 695, eff. 12-1-13; CR 16-093: renum. SPS 316.400 to (1) and am., cr. (2) Register June 2018 No. 650, eff. 8-1-18.
SPS 316.404 SPS 316.404 Switches controlling lighting loads. The requirements in 2017 NEC 404.2 (C) do not apply to dwelling units.
SPS 316.404 History History: CR 16-093: cr. Register June 2018 No. 650, eff. 8-1-18.
SPS 316.406 SPS 316.406 Receptacles, cord connectors and attachment plugs (caps).
SPS 316.406(1) (1) The requirements in 2011 and 2017 NEC 406.4 (D) (4) are not included as part of this chapter.
SPS 316.406(2) (2) Substitute the following wording for 2017 NEC 406.9 (B) (1): Receptacles of 15 and 20 amperes, 125 and 250 volts installed in a wet location shall have an enclosure that is weatherproof whether or not the attachment plug cap is inserted.
SPS 316.406 History History: CR 08-047: cr. Register February 2009 No. 638, eff. 3-1-09; CR 13-042: Register November 2013 No. 695, eff. 12-1-13; CR 16-093: renum. SPS 316.406 to (1) and am., cr. (2) Register June 2018 No. 650, eff. 8-1-18.
SPS 316.450 SPS 316.450 Transformers and transformer vaults (including secondary ties).
SPS 316.450(1) (1) Overcurrent protection. This is a department rule in addition to the requirements in 2011 and 2017 NEC Table 450.3 (A) Note 3: The qualified person shall be either an employee at that location or an employee contracted for this purpose who is readily available.
SPS 316.450(2) (2)Location. Substitute the following wording for 2011 and 2017 NEC 450.41: Vaults containing oil-insulated transformers shall be located where the vaults can be ventilated to the outside air without using flues or ducts, except where a petition for variance is approved.
SPS 316.450 History History: CR 08-047: cr. Register February 2009 No. 638, eff. 3-1-09; CR 13-042: am. (title), (1) Register November 2013 No. 695, eff. 12-1-13; CR 16-093: am. Register June 2018 No. 650, eff. 8-1-18.
SPS 316.511 SPS 316.511 Commercial garages, repair and storage.
SPS 316.511(1)(1) The requirements specified in 2011 NEC 511.3 (C) (1) (a) are not included as part of this chapter.
SPS 316.511(2) (2) Substitute the following wording for 2011 NEC 511.3 (C) (2) (a): The ceiling area shall be unclassified where ventilation is provided from a point not more than 18 inches from the highest point in the ceiling. The ventilation shall conform to chs. SPS 361 to 366.
SPS 316.511 Note Note: The Commercial Building Code, chapters SPS 361 to 366, adopts and references the International Mechanical Code, IMC, for the design of ventilation systems. The adopted provisions of the International Mechanical Code under section 502.16 prescribe provisions for repair garages for natural gas- and hydrogen- fueled vehicles.
SPS 316.511(3) (3) Substitute the following wording for “Extent of Classified Location” in 2017 NEC Table 511.3 (C) under which the floor area of a major repair garage is considered unclassified: Up to 450 mm (18 in.) above floor level of the room where the room is provided with ventilation from a point not more than 300 mm (12 in.) from the lowest point of the floor area and the ventilation conforms to chs. SPS 361 to 366.
SPS 316.511(4) (4) Substitute the following wording for “Extent of Classified Location” in 2017 NEC Table 511.3 (D) under which the ceiling area of a major repair garage is considered unclassified: Within 450 mm (18 in.) of ceiling where ventilation is provided from a point not more than 450 mm (18 in.) from the highest point in the ceiling and the ventilation conforms to chs. SPS 361 to 366.
SPS 316.511 History History: CR 08-047: cr. Register February 2009 No. 638, eff. 3-1-09; CR 13-042: renum. SPS 316.511 to (1) and am. (title) and (1), cr. (2) Register November 2013 No. 695, eff. 12-1-13; correction in (1) made under s. 13.92 (4) (b) 7., Stats., Register November 2013 No. 695; CR 16-093: am. (1), (2), cr. (3), (4) Register June 2018 No. 650, eff 8-1-18.
SPS 316.547 SPS 316.547 Agricultural buildings. This is a department exception to the requirements in 2011 and 2017 NEC 547.5 (G): Exception: Ground-fault circuit-interrupter protection is not required for a single receptacle providing power for an electric fence controller used for livestock containment where an accessible ground-fault circuit-interrupter protected receptacle is located within 900 mm (3 ft) of the non-GFCI protected receptacle.
SPS 316.547 History History: CR 13-042: cr. Register November 2013 No. 695, eff. 12-1-13; CR 16-03: am. Register June 2018 No. 650, eff. 8-1-18.
SPS 316.551 SPS 316.551 Recreational vehicles and recreational vehicle parks. Substitute the following wording for 2017 NEC 551.71 (C): A minimum of 20 percent of existing and 40 percent of all new recreational vehicle sites, with electrical supply, shall each be equipped with a 50-ampre, 125/250-volt receptacle conforming to the configuration as identified in Figure 551.46 (C) (1). These electrical supplies shall be permitted to include additional receptacles that have configurations in accordance with 551.81.
SPS 316.551 History History: CR 16-093: cr. Register June 2018 No. 650, eff. 8-1-18.
SPS 316.620 SPS 316.620 Elevators, dumbwaiters, escalators, moving walks, platform lifts and stairway chairlifts. This is a department exception to the requirements in 2011 and 2017 NEC 620: Exception: Wherever NEC 620 requires disconnecting means with overcurrent protection to be located in an elevator machine room, control room, machinery space or control space and the elevator does not have such a room or space directly accessible from a building floor level, such devices shall be located instead in lockable cabinets or electrical rooms accessible only to qualified persons.
SPS 316.620 History History: CR 08-047: cr. Register February 2009 No. 638, eff. 3-1-09; CR 13-042: am. (title) Register November 2013 No. 695, eff. 12-1-13; CR 14-020: renum. 316.620 to (2), cr. (1) Register August 2014 No. 704, eff. 9-1-14; CR 16-093: renum. (1) to SPS 316.620 and am., r. (2) Register June 2018 No. 650, eff. 8-1-18.
SPS 316.675 SPS 316.675 Electrically driven or controlled irrigation machines.
SPS 316.675(1)(1) This is a department rule in addition to the requirements in 2011 NEC 675.8: A service disconnecting means with overcurrent protection shall be provided at the service point in accordance with NEC 230 subchapter VI.
SPS 316.675(2) (2) This is a department rule in addition to the requirements in 2017 NEC 675.8: A service disconnecting means with overcurrent protection shall be provided at the service point in accordance with NEC 230 Part VI.
SPS 316.675 History History: CR 08-047: cr. Register February 2009 No. 638, eff. 3-1-09; CR 13-042: am. Register November 2013 No. 695, eff. 12-1-13; CR 16-093: renum. SPS 316.675 to (1) and am., cr. (2) Register June 2018 No. 650, eff. 8-1-18.
SPS 316.680 SPS 316.680 Swimming pools, fountains and similar installations.
SPS 316.680(1)(1) Perimeter surfaces. This is a department rule in addition to the requirements of 2011 NEC 680.26 (B) (2): The requirements specified in NEC 680.26 (B) (2) do not apply to a listed self-contained spa or hot tub constructed with nonmetallic walls.
SPS 316.680(2) (2)Pool water. This is a department rule in addition to the requirements of 2011 NEC 680.26 (C): The requirements specified in NEC 680.26 (C) do not apply to a listed self-contained spa or hot tub constructed with nonmetallic walls.
SPS 316.680 History History: CR 08-047: cr. Register February 2009 No. 638, eff. 3-1-09; CR 13-042: am. (title) Register November 2013 No. 695, eff. 12-1-13; CR 16-093: am. Register June 2018 No. 650, eff. 8-1-18.
SPS 316.700 SPS 316.700 Emergency systems.
SPS 316.700(1)(1) Wiring, emergency system. This is a department rule in addition to the requirements of 2011 and 2017 NEC 700.10 (B):
SPS 316.700(1)(a) (a) Except as provided in par. (b), emergency circuit wiring shall be listed raceways, Type AC cable or Type MC cable.
SPS 316.700(1)(b) (b) Emergency lighting fixtures may use flexible cord connections in compliance with NEC 410.62 (C) for electric discharge luminaries.
SPS 316.700(2) (2)General requirements. This is a department rule in addition to the requirements in 2011 and 2017 NEC 700.12 (intro.): The enclosure of the alternate source of power located outdoors for emergency systems shall be located at least 10 feet horizontally from any combustible portion of a Type III, Type IV, or Type V building and at least 20 feet from an outdoor electrical transformer, electrical metering, service equipment, or normal power distribution equipment. These dimensions may be reduced where a noncombustible barrier is installed that extends at least 3 feet beyond each side of the alternate power source and transformer. The height of the barrier shall be at least one foot above the top of the transformer, electrical metering, service equipment, or alternate power source, whichever is higher.
SPS 316.700(3) (3)General requirements, dual supplies. The requirements in 2011 and 2017 NEC 700.12 (B) (3) are not included as part of this chapter.
SPS 316.700 Note Note: See chs. SPS 361 to 366 for further requirements.
SPS 316.700 History History: CR 08-047: cr. Register February 2009 No. 638, eff. 3-1-09; CR 13-042: am. (1) (intro.), (3) Register November 2013 No. 695, eff. 12-1-13; CR 16-093: am. (1) (intro.), (2), (3) Register June 2018 No. 650, eff. 8-1-18.
SPS 316.701 SPS 316.701 Legally required standby systems.
SPS 316.701(1)(1) Addition. This is a department rule in addition to the requirements in 2011 and 2017 NEC 701.12 (intro.): The enclosure of the alternate source of power located outdoors for legally required standby systems shall be located at least 10 feet horizontally from any combustible portion of a Type III, Type IV, or Type V building and at least 20 feet from an outdoor electrical transformer, electrical metering, service equipment, or normal power distribution equipment. These dimensions may be reduced where a noncombustible barrier is installed that extends at least 3 feet beyond each side of the alternate power source and transformer. The height of the barrier shall be at least one foot above the top of the transformer, electrical metering, service equipment, or alternate power source, whichever is higher.
SPS 316.701(2) (2)Deletion. The requirements specified in 2011 and 2017 NEC 701.12 (B) (3) are not included as part of this chapter.
SPS 316.701 Note Note: See chs. SPS 361 to 366 for further requirements.
SPS 316.701 History History: CR 08-047: cr. Register February 2009 No. 638, eff. 3-1-09; correction in (1) made under s. 13.92 (4) (b) 7., Stats., Register February 2009 No. 638; corrections in (1), (2) made under s. 13.92 (4) (b) 7., Stats., Register November 2013 No. 695; CR 16-093: am. Register June 2018 No. 650, eff. 8-1-18.
subch. V of ch. SPS 316 Subchapter V — Electrical Inspection
SPS 316.900 SPS 316.900 Purpose. Pursuant to s. 101.82, Stats., the purpose of this subchapter is to establish rules for the inspection of electrical construction of farms, public buildings and places of employment.
SPS 316.900 Note Note: This section is repealed eff. 1-1-20 by CR 16-093.
SPS 316.900 History History: Cr. Register, September, 1999, No. 525, eff. 10-1-99; CR 08-047: renum. from Comm 16.60 Register February 2009 No. 638, eff. 3-1-09; r. CR 16-093: am. Register June 2018 No. 650, eff. 1-1-20.
SPS 316.905 SPS 316.905 Scope. This subchapter specifies the electrical construction to be inspected, the inspection procedures to be followed and the procedures for connection of electric service.
SPS 316.905 Note Note: This section is repealed eff. 1-1-20 by CR 16-093.
SPS 316.905 History History: Cr. Register, September, 1999, No. 525, eff. 10-1-99; CR 08-047: renum. from Comm 16.61 Register February 2009 No. 638, eff. 3-1-09; r. CR 16-093: am. Register June 2018 No. 650, eff. 1-1-20.
SPS 316.910 SPS 316.910 Application. This subchapter applies to persons, independent inspection agencies, municipalities and state governmental agencies engaged in the inspection of electrical construction for the purposes of administering and enforcing this chapter on farms and in public buildings and places of employment, and to companies or utilities providing connection of electric service.
SPS 316.910 Note Note: This section is repealed eff. 1-1-20 by CR 16-093.
SPS 316.910 History History: Cr. Register, September, 1999, No. 525, eff. 10-1-99; CR 08-047: renum. from Comm 16.62 Register February 2009 No. 638, eff. 3-1-09; r. CR 16-093: am. Register June 2018 No. 650, eff. 1-1-20.
SPS 316.915 SPS 316.915 Definitions. In this subchapter:
SPS 316.915(1) (1) “Certified inspector" means a certified commercial electrical inspector.
SPS 316.915(2) (2) “Commercial electrical inspector" means a person who conducts inspections of electrical construction of farms, public buildings and places of employment.
SPS 316.915(4) (4) “Electrical construction" means the installation of electrical wiring.
SPS 316.915(5) (5) “Electrical contractor" means any person, firm or corporation engaged in the business of erecting, installing, altering, repairing, servicing or maintaining electrical wiring.
SPS 316.915(9) (9) “Independent inspection agency" means any corporation, partnership or sole proprietor, other than a municipal corporation, that performs inspections of buildings.
SPS 316.915(11) (11) “Person" includes all partnerships, associations, and bodies politic or corporate.
SPS 316.915 Note Note: This section is repealed eff. 1-1-20 by CR 16-093.
SPS 316.915 History History: Cr. Register, September, 1999, No. 525, eff. 10-1-99; CR 08-047: renum. from Comm 16.63 Register February 2009 No. 638, eff. 3-1-09; correction in (3) made under s. 13.92 (4) (b) 6., Stats., Register December 2011 No. 672; CR 16-093: r. (3), (6) to (8), (10), (12), (13) Register June 2018 No. 650, eff. 8-1-18; r. CR 16-093: am. Register June 2018 No. 650, eff. 1-1-20.
SPS 316.920 SPS 316.920 Authority.
SPS 316.920(1)(1) Departmental authority. Pursuant to ss. 101.82 and 101.84, Stats., the department is granted the authority and jurisdiction over the inspection of electrical construction of farms, public buildings and places of employment.
SPS 316.920(2) (2)Municipal authority.
SPS 316.920(2)(a)(a) Jurisdiction conditions. Pursuant to s. 101.86 (1), Stats., municipalities may exercise jurisdiction over inspection of electrical construction in public buildings and places of employment by passage of ordinances, providing all of the following conditions are complied with:
SPS 316.920(2)(a)1. 1. The municipality's ordinances meet the minimum requirements of this subchapter.
SPS 316.920(2)(a)2. 2. The municipality notifies the department at least 30 days prior to the date upon which the municipality intends to assume the jurisdiction.
SPS 316.920(2)(a)3. 3. The municipality provides the department with a copy of its electrical ordinances and subsequent revisions to the ordinances.
SPS 316.920(2)(a)4. 4. The municipality's ordinances adopt this chapter in its entirety.
SPS 316.920(2)(a)5. 5. The municipality employs or contracts with certified inspectors or independent inspection agencies to perform electrical inspection functions.
SPS 316.920(2)(a)6. 6. The municipality provides the department with the names of its certified inspectors or independent inspection agencies employed or contracted by the municipality.
SPS 316.920(2)(a)7. 7. The municipality provides the department with any information requested by the department relative to the electrical inspection of public buildings and places of employment.
SPS 316.920 Note Note: Section 13.48 (13), Stats., exempts state buildings from local ordinances or regulations relating to building construction, permits and similar restrictions.
SPS 316.920(2)(b) (b) Joint jurisdiction. Municipalities may jointly exercise the jurisdiction granted in par. (a).
SPS 316.920(2)(c) (c) Municipal contracts. A municipality may contract with a certified inspector, independent inspection agency or the department for those inspection services that the municipality does not perform under par. (a) or (b).