SPS 321.27(7)(a)(a) Metal plate connected wood roof trusses shall be designed in accordance with TPI 1 and the NDS adopted under s. SPS 320.24.
SPS 321.27(7)(b) (b) Truss members shall not be cut, bored or notched, except as allowed under sub. (8) (d).
SPS 321.27(7)(c) (c) If connection is provided to stabilize a non-load bearing wall, a slotted expansion joint or clip shall be used.
SPS 321.27(8) (8) Notching and boring.
SPS 321.27(8)(a)(a) General.
SPS 321.27(8)(a)1.1. Notching and boring of beams or girders is prohibited unless determined through structural analysis.
SPS 321.27(8)(a)2. 2. Notching and boring of ceiling joists and rafters shall comply with pars. (b) and (c).
SPS 321.27(8)(b) (b) Notching.
SPS 321.27(8)(b)1.1. Notches located in the top or bottom of ceiling joists and rafters are prohibited from all of the following:
SPS 321.27(8)(b)1.a. a. Having a depth exceeding 1/6 the depth of the member.
SPS 321.27(8)(b)1.b. b. Having a length exceeding 1/3 the depth of the member.
SPS 321.27(8)(b)1.c. c. Being located in the middle 1/3 of the span of the member.
SPS 321.27(8)(b)2. 2. Where ceiling joists or rafters are notched at the ends, the notch may not exceed ¼ the depth of the member.
SPS 321.27(8)(b)3. 3. Bird mouth cuts may not exceed 1/3 the depth of the rafter unless the seat cut bears fully on the wall plate.
SPS 321.27(8)(c) (c) Boring.
SPS 321.27(8)(c)1.1. Holes bored within 2 inches of the top or bottom of ceiling joists or rafters may not be located in the middle 1/3 of the span of the member.
SPS 321.27(8)(c)2. 2. The diameter of a hole may not exceed 1/3 the depth of the member.
SPS 321.27(8)(c)3. 3. A hole may not be bored within 2 inches of a notch or another hole.
SPS 321.27(8)(c)4. 4. The distance between adjacent holes may not be less than the diameter of the larger hole.
SPS 321.27(8)(d) (d) Engineered wood products. Notching or boring of engineered wood products shall be done in accordance with the manufacturer's instructions provided those instructions were developed through structural analysis or product testing.
SPS 321.27(9) (9) Roof sheathing, boards and planking.
SPS 321.27(9)(a) (a) Structural sheathing. The allowable loads and spans for structural sheathing shall be in accordance with the grade stamp on the panel.
SPS 321.27(9)(b) (b) Roof boards.
SPS 321.27(9)(b)1.1. Where the rafter spacing is 24 inches on center or less, roof boards may be used that have a minimum thickness of 5/8-inch for solid sheathing and 3/4-inch for spaced sheathing.
SPS 321.27(9)(b)2. 2. Where the rafter spacing is greater than 24 inches on center, roof boards shall be tongue and groove, at least 1.5 inches thick.
SPS 321.27(9)(c) (c) Roof planks.
SPS 321.27(9)(c)1.1. Roof planks shall be tongue and groove or splined and at least 2 inches, nominal, in thickness.
SPS 321.27(9)(c)2. 2. Planks shall terminate over beams unless the joints are end matched.
SPS 321.27(9)(c)3. 3. The planks shall be laid so that no continuous line of joints will occur except at points of support.
SPS 321.27(9)(c)4. 4. Planks shall be nailed or fastened to each beam.
SPS 321.27 History History: Cr. Register, November, 1979, No. 287, eff. 6-1-80; am (3) (a), Register, January, 1989, No. 397, eff. 2-1-89; r. and recr. (1), am. (3) (a), Register, March, 1992, No. 435, eff. 4-1-92; r. and recr. (3) (a), Register, November, 1995, No. 479, eff. 12-1-95; r. and recr. (3) (a) 1. and 2. c., Register, January, 1999, No. 517, eff. 2-1-99; am. (3) (a) 1. a., Register, March, 2001, No. 543, eff. 4-1-01; CR 02-077: r. and recr. (3) (b) Register May 2003 No. 569, eff. 8-1-03; CR 08-043: r. and recr. Register March 2009 No. 639, eff. 4-1-09; correction in (1) (a), (c), (4) (d), (5) (b), (7) (a) made under s. 13.92 (4) (b) 7., Stats., Register December 2011 No. 672; CR 15-041: am. (4) (d) Register December 2015 No. 720, eff. 1-1-16.
SPS 321.28 SPS 321.28Weather protection for roofs.
SPS 321.28(1)(1)General.
SPS 321.28(1)(a)(a) All roofs shall be designed and constructed to assure drainage of water.
SPS 321.28(1)(b) (b) All fasteners shall be corrosion resistant.
SPS 321.28(2) (2) Underlayment for shingles. Underlayment consisting of number 15 asphalt-impregnated felt paper or equivalent or other type I material that shows no water transmission when tested in accordance with ASTM D 226 or ASTM D 4869 shall be provided under shingles.
SPS 321.28 Note Note: Underlayment materials meeting the requirements of ASTM D 1970 meet the performance requirements of this section.
SPS 321.28(3) (3) Asphalt shingles.
SPS 321.28(3)(a)(a) General.
SPS 321.28(3)(a)1.1. Shingles that have a self-sealing adhesive strip shall include a sealant which has an average bond strength of at least 1.5 pounds per 3.75 inches of shingle width, at 32°F.
SPS 321.28 Note Note: The department will accept results of testing conducted in accordance with an approved test method for verifying compliance with the sealant uplift resistance required in this paragraph. Information on the applicable test method may be obtained from the department.
SPS 321.28(3)(a)2. 2. Each shingle package shall be labeled by the manufacturer to indicate conformance to the applicable ASTM standard for each type of shingle or the exception in par. (c).
SPS 321.28(3)(a)3. 3. Shingles shall be installed in accordance with the manufacturer's recommendations.
SPS 321.28(3)(a)4. 4. Shingles shall have at least 4 fasteners per strip shingle or 2 fasteners per interlocking shingle, unless the manufacturer has other specifications.
SPS 321.28(3)(a)5. 5. Shingle head lap shall be at least 2 inches, unless the manufacturer has other specifications.
SPS 321.28(3)(a)6. 6. All fasteners for shingles shall be corrosion-resistant.
SPS 321.28 Note Note: See s. SPS 320.07 (62) for definitions of shingle terms.
SPS 321.28 Note Note: Section SPS 320.04 (2) requires compliance with all parts of this code, including these roofing provisions, for an alteration to any dwelling that is regulated under this code.
SPS 321.28(3)(c) (c) Fiberglass shingles. Fiberglass asphalt shingles shall conform to ASTM D 3462 except that laminated shingles shall have a tear strength of at least 1450 grams in each ply.
SPS 321.28(4) (4) Ice dam protection.
SPS 321.28(4)(a)(a) Shingled or shake roofs that extend over a heated area of a dwelling or attached garage and that have a slope of 4:12 or less shall be provided with ice dam protection in the form of sheet metal or a product labeled as meeting the requirements of ASTM D 1970.
SPS 321.28(4)(b) (b) The ice dam protection shall extend at least 30 inches up the roof slope from the roof edge and at least 12 inches up the roof slope beyond the inner face of the exterior wall.
SPS 321.28(5) (5) Other roof coverings. All roof coverings not otherwise addressed in this section shall be installed in accordance with the manufacturer's instructions or a national standard recognized by the department.
SPS 321.28(6) (6) Reroofing. New roof coverings may not be installed over existing roof coverings where any of the following conditions exist:
SPS 321.28(6)(a) (a) The existing roof or roof covering is water-soaked or has deteriorated such that it is inadequate as a base for additional roofing.
SPS 321.28(6)(b) (b) The existing roof is wood shake, slate, clay, cement or asbestos-cement tile.
SPS 321.28(6)(c) (c) The existing roof has 2 or more applications of any type of permanent roof covering.
SPS 321.28(7) (7) Flashing.
SPS 321.28(7)(a)(a) General. Flashing shall be installed at the junction of chimneys and roofs, in all valleys, and around all roof openings.
SPS 321.28(7)(b) (b) Flashing of open valleys.
SPS 321.28(7)(b)1.1. Open valleys shall be flashed with at least No. 28 gauge corrosion-resistant sheet metal, 16 inches wide, or a layer of at least 50-pound roll roofing, 16 inches wide, placed over a layer of number 15 roofing underlayment.
SPS 321.28(7)(b)2. 2. Flashing sections shall be overlapped by at least 4 inches.
SPS 321.28(7)(c) (c) Flashing of closed valleys. Where shingles are laced or woven over the valley, the valley shall be flashed with one of the following:
SPS 321.28(7)(c)1. 1. At least one layer of 50-pound roofing, at least 20 inches wide, over a layer of number 15 roofing underlayment.
SPS 321.28(7)(c)2. 2. A product labeled as meeting the requirements of ASTM D1970.
SPS 321.28(7)(d) (d) Chimney flashing.
SPS 321.28(7)(d)1.1. Chimneys shall be flashed and counter-flashed to a height of at least 6 inches.
SPS 321.28(7)(d)2. 2. Chimney crickets or saddles shall be installed where the upper side of a chimney is more than 30 inches wide on a sloping roof.
SPS 321.28(7)(d)3. 3. The intersection of the cricket and the chimney shall be flashed and counter-flashed to a height of at least 6 inches.
SPS 321.28 History History: Cr. Register, November, 1979, No. 287, eff. 6-1-80; am. (7) (a), r. and recr. Table 321.28-A, Register, January, 1989, No. 397, eff. 2-1-89; am. (1), (5) and (6), cr. (2m) and (6) (a) 3., r. and recr. (4) (c), Register, March, 1992, No. 435, eff. 4-1-92; cr. (6) (c), Register, November, 1995, No. 479, eff. 12-1-95; CR 02-077: r. and recr. (1) (a), renum. (6) (intro) to (c) to be (6) (a) to (d) and am. (6) (a) to (c) Register May 2003 No. 569, eff. 8-1-03; CR 08-043: r. and recr. Register March 2009 No. 639, eff. 4-1-09; CR 15-041: am. (3) (a) 2., cr. (3) (a) 6., r. (3) (b), renum. (7) (c) to (7) (c) (intro.) and 1. and am., cr. (7) (c) 2. Register December 2015 No. 720, eff. 1-1-16; correction in (3) (a) 2. under s. 13.92 (4) (b) 7., Stats., Register December 2015 No. 720.
subch. IX of ch. SPS 321 Subchapter IX — Fireplace Requirements
SPS 321.29 SPS 321.29Masonry fireplaces. Masonry fireplaces shall be constructed of masonry, stone or concrete. Masonry fireplaces shall be supported on foundations of concrete or masonry. Structural walls shall be at least 8 inches thick. Masonry fireplaces shall conform to the following requirements:
SPS 321.29(1) (1) Flue size. The fireplace flue size shall be based on the type of flue and the fireplace opening indicated in Table 321.29. - See PDF for table PDF
SPS 321.29(2) (2) Termination of chimney. Masonry fireplace chimneys shall extend at least 3 feet above the highest point where the chimney passes through the roof and at least 2 feet higher than any portion of the dwelling within 10 feet of the chimney.
SPS 321.29(3) (3) Firebox materials. The firebox shall be of the preformed metal type, at least ¼-inch thick, or listed by a nationally recognized laboratory; or shall be lined with firebrick, at least 2 inches thick and laid in thin joints of refractory cement. The back and sidewalls of the firebox, including the lining, shall be at least 8 inches nominally thick masonry, at least 4 inches of which shall be solid.
SPS 321.29(4) (4) Lintel. Masonry over the fireplace opening shall be supported by a lintel of steel or masonry.
SPS 321.29(5) (5) Ducts. Warm-air circulating ducts shall be constructed of masonry or metal.
SPS 321.29(5m) (5m) Return air grilles. Return air grilles shall not be located in bathrooms, kitchens, garages, utility spaces or in a confined space defined under s. SPS 323.06 in which a draft diverter or draft regulator is located.
SPS 321.29(6) (6) Hearth extension.
SPS 321.29(6)(a)(a) Masonry fireplaces shall have a hearth extension made of noncombustible material.
SPS 321.29(6)(b) (b) The structural support for the hearth and hearth extension shall be a minimum of 4 inches of reinforced concrete.
SPS 321.29(6)(c) (c) There shall be no structural framing material within 1 inch of the hearth or hearth extension in any direction. Any wooden forms or supports used during construction shall be removed.
SPS 321.29(6)(d) (d) The minimum dimensions of the hearth extension shall be in accordance with Table 321.29-1. - See PDF for table PDF
SPS 321.29(7) (7) Dampers. Dampers shall be made of cast iron or at least No. 12 gauge sheet metal. The area of the damper opening shall be at least 90% of the required flue area when in the open position.
SPS 321.29(8) (8) Hoods. Metal hoods, used in lieu of a masonry smoke chamber, shall be constructed of at least No. 19 gauge corrosion-resistant metal with all seams and connections of smokeproof construction. The hood shall be sloped at an angle of 45° or less from the vertical and shall extend horizontally at least 6 inches beyond the firebox limits. Metal hoods shall be kept a minimum of 18 inches from the combustible materials unless approved for reduced clearances.
SPS 321.29 Note Note: The department will accept dampers and hoods listed by nationally recognized laboratories.
SPS 321.29(9) (9) Flue liners.
SPS 321.29(9)(a)(a) Flue liners shall be installed in accordance with s. SPS 321.30 (7) and this section.
SPS 321.29(9)(b) (b) Flue liners shall start at the top of the fireplace throat and extend to a point at least 4 inches above the top of the chimney cap.
Loading...
Loading...
Published under s. 35.93, Stats. Updated on the first day of each month. Entire code is always current. The Register date on each page is the date the chapter was last published.