12. Agency Contact Person: Adam DeWeese; 101 S. Webster Street, Madison, WI 53703; Adam.DeWeese@wisconsin.gov; (608) 264-9229
13. Place where comments are to be submitted and deadline for submission:
Written comments may be submitted at the public hearings, by regular mail, or email to:
Adam DeWeese – DG/5
Department of Natural Resources
101 S. Webster Street
PO Box 7921
Madison, WI 53707
Comments may be submitted to the department contact person listed above or to DNRAdministrativeRulesComments@wisconsin.gov until the deadline given in the upcoming notice of public hearing. The notice of public hearing and deadline for submitting comments will be published in the Wisconsin Administrative Register and on the department’s website, at https://dnr.wi.gov/calendar/hearings/. Comments may also be submitted through the Wisconsin Administrative Rules Website at https://docs.legis.wisconsin.gov/code/chr/active.
RULE TEXT
Section 1   NR 809.04 (59h) is created to read:
NR 809.04 (59h) “Perfluoroalkyl and polyfluoroalkyl substances” or “PFAS” means a large group of human-made chemicals that are part of the synthetic organic contaminants classification.
Section   NR 809.20 (1) Table is amended to read:
NR 809.20 (1) Table
Contaminant
MCL (mg/L)
Alachlor
0.002
Atrazine
0.003
Benzo[a]pyrene
0.0002
Carbofuran
0.04
Chlordane
0.002
2,4-D
0.07
Dalapon
0.2
Dibromochloropropane
0.0002
Di(2-ethylhexyl)adipate
0.4
Di(2-ethylhexyl)phthalate
0.006
Dinoseb
0.007
Diquat
0.02
Endothall
0.1
Endrin
0.002
Ethylene Dibromide
0.00005
Glyphosate
0.7
Heptachlor
0.0004
Heptachlor epoxide
0.0002
Hexachlorobenzene
0.001
Hexachlorocyclopentadiene
0.05
Lindane
0.0002
Methoxychlor
0.04
Oxamyl
0.2
Pentachlorophenol
PFOS and PFOA
0.001
0.000020
Picloram
0.5
Polychlorinated biphenyls (PCBs)
0.0005
Simazine
0.004
2,3,7,8-TCDD (Dioxin)
3x10-8
Toxaphene
0.003
2,4,5-TP
0.05
Section 2   NR 809.20 (2) (d) is created to read:
NR 809.20 (2) (d) Granular activated carbon, powdered activated carbon, ion exchange resins, nanofiltration, and reverse osmosis for PFOS and PFOA.
Section 3   NR 809.203 (1) Table is amended to read:
NR 809.203 (1) Table
Contaminant
Detection Limit (mg/L)
1. Alachlor
0.0002
2. Aldicarb
0.0005
3. Aldicarb sulfoxide
0.0005
4. Aldicarb sulfone
0.0008
5. Atrazine
0.0001
6. Benzo[a]pyrene
0.00002
7. Carbofuran
0.0009
8. Chlordane
0.0002
9. 2,4-D
0.0001
10. Dalapon
0.001
11. Dibromochloropropane
0.00002
12. Di(2-ethylhexyl)adipate
0.0006
13. Di(2-ethylhexyl)phthalate
0.0006
14. Dinoseb
0.0002
15. Diquat
0.0004
16. Endothall
0.009
17. Endrin
0.00001
18. Ethylene dibromide
0.00001
19. Glyphosate
0.006
20. Heptachlor
0.00004
21. Heptachlor epoxide
0.00002
22. Hexachlorobenzene
0.0001
23. Hexachlorocyclopentadiene
0.0001
24. Lindane
0.00002
25. Methoxychlor
0.0001
26. Oxamyl
0.002
27. Picloram
0.0001
28. Polychlorinated biphenyls  
(PCBs as
decchlorobiphenyls)
0.0001
29. Pentachlorophenol
0.00004
30. Simazine
0.00007
31. Toxaphene
0.001
32. 2,3,7,8-TCDD (Dioxin)
0.000000005
33. 2,4,5-TP (Silvex)
0.0002
30. Perfluorooctane Sulfonic Acid (PFOS)
0.000002
31. Perfluorooctanoic Acid (PFOA)
0.000002
32. Simazine
0.00007
33. Toxaphene
0.001
34. 2,3,7,8-TCDD (Dioxin)
0.000000005
35. 2,4,5-TP (Silvex)
0.0002
Section 4   NR 809.203 (2) Table CM and (4) Table D are amended to read:
NR 809.203 (2) Table CM
Table CM
SDWA Approved Methodology for Synthetic Organic Contaminants
Contaminant
EPA Methods1
SM9
SM Online10
ASTM
Other
Regulated Parameters:
Synthetic Organic Chemicals
2,3,7,8-TCDD (dioxin)
1613
2,4-D 2 (as acids, salts and esters)
515.2, 555, 515.1, 515.3, 515.4
D5317-93, 98
(Reapproved 2003)
2,4,5-TP 2 (Silvex)
515.2, 555, 515.1, 515.3, 515.4
6640 B,
6640 B-01, B-0611
D5317-93, 98
(Reapproved 2003)
Alachlor
507, 525.2,
525.32
508.1, 5058, 551.1
Atrazine 3
507, 525.2, 525.3 508.1, 5058, 551.1, 536
Syngenta4
AG-625
Benzo(a)pyrene
525.2, 525.3, 550, 550.1
Carbofuran
531.1, 531.2
66105
6610 B
6610 B-04
Chlordane
508, 525.2, 525.3, 508.1, 505
Dalapon
552.1 515.1, 552.2, 515.3, 515.4, 552.3, 557
6640 B
6640 B-01, 06
Di(2-ethylhexyl)adipate
506, 525.2, 525.3
Di(2-ethylhexyl)phthalate
506, 525.2, 525.3
Dibromochloropropane (DBCP)
504.1, 551.1, 524.39
Dinoseb
515.2, 555, 515.1, 515.3, 515.4
6640 B
6640 B-01, 06
Diquat
549.2
Endothall
548.1
Endrin
508, 525.2, 525.3, 508.1, 505, 551.1
Ethylene dibromide (EDB)
504.1, 551.1, 524.3
Glyphosate
547
66516
6651 B
6651 B-01, B-06
Heptachlor
508, 525.2, 525.3, 508.1, 505, 551.1
Heptachlor Epoxide
508, 525.2, 525.3, 508.1, 505, 551.1
Hexachlorobenzene
508, 525.2, 525.3, 508.1, 505, 551.1
Hexachlorocyclopentadiene
508, 525.2, 525.3, 508.1, 505, 551.1
Lindane
508, 525.2, 525.3, 508.1, 505, 551.1
Methoxychlor
508, 525.2, 525.3, 508.1, 505, 551.1
Oxamyl
531.1, 531.2
66105
6610 B
6610 B-04
PCBs (as decachlorobiphenyl)
508A7
(as Aroclors)
508.1, 508, 525.2, 525.3, 505
Pentachlorophenol
515.2, 525.2, 525.3, 555, 515.1, 515.3, 515.4
D5317-93, 98 (Reapproved 2003)
Picloram 2
515.2, 555, 515.1, 515.3, 515.4
6640 B
6640 B-01
D5317-93, 98 s
(Reapproved 2003)
Perfluorooctane Sulfonic Acid (PFOS)
537, 537.1,
533
Wis. PFAS
Method
Perfluorooctanoic Acid (PFOA)
537, 537.1
533
Wis. PFAS
Method
Simazine
507, 525.2, 525.3, 523, 536, 508.1, 5058, 551.1
Toxaphene
508, 508.1, 525.2, 525.3, 505
Unregulated Parameters: 
Aldicarb  
531.1, 531.2
66105
6610 B
6610 B-04
Aldicarb sulfone  
531.1, 531.2
66105
6610 B
6610 B-04
Aldicarb Sulfoxide  
531.1 , 531.2
66105
6610 B
6610 B-04
Aldrin  
505, 508, 525.2, 525.3, 508.1  
Butachlor  
507, 525.2, 525.3  
Carbaryl  
531.1, 531.2
66105
6610 B
6610 B-04
Dicamba  
515.1, 555, 515.2, 515.3, 515.4
6640 B
6640 B-01, B-06
Dieldrin  
505, 508, 525.2, 525.3, 508.1  
3-Hydroxcarbofuran  
531.1, 531.2
66105
6610 B
6610 B-04
Methomyl  
531.1, 531.2
66105
6610 B
6610 B-04
Metolachlor  
507, 525.2, 525.3, 508.1  
Metribuzin  
507, 525.2, 525.3, 508.1  
Propachlor  
507, 525.2, 525.3, 508.1  
(4) Table D
Table D
Sample Preservation, Holding Times, and Sampling Containers for Organic Parameters
Method
Preservative2
Sample Holding Time
Extract Holding Time and Storage Conditions
Suggested Sample Size
Type of Container
502.22
Sodium Thiosulfate or Ascorbic Acid, 4C, HCl pH<2
14 days
NA
40 – 120 mL
Glass with PTFE1 Lined Septum
504.1
Sodium Thiosulfate,
Cool, 4
C
14 days
4C, 24 hours
40 mL
Glass with PTFE1 Lined Septum
505
Sodium Thiosulfate,
Cool, 4
C
14 days
(7 days for Heptachlor)
4C, 24 hours
40 mL
Glass with PTFE1 Lined Septum
506
Sodium Thiosulfate,
Cool, 4
C, Dark
14 days
4C, Dark
14 days
1 L
Amber Glass with PTFE1 Lined Septum
507
Sodium Thiosulfate,
Cool, 4
C, Dark
14 days (See method for exceptions.)
4C, Dark
14 days
I L
Amber Glass with PTFE1 Lined Cap
508
Sodium Thiosulfate,
Cool, 4
C, Dark
7 days (See method for exceptions.)
4C, Dark
14 days
I L
Glass with PTFE1 Lined Cap
508A
Cool, 4C
14 days
30 days
I L
Amber Glass with PTFE1 Lined Cap
508.1
Sodium Sulfite, HCl pH<2,
Cool, 4
C
14 days (See method for exceptions.)
30 days
I L
Glass with PTFE Lined Cap
515.1
Sodium Thiosulfate,
Cool, 4
C, Dark
14 days
4C, Dark
28 days
I L
Amber Glass with PTFE1 Lined Cap
515.2
Sodium Thiosulfate or Sodium Sulfite,
HCl pH<2
Cool, 4
C, Dark
14 Days
4C, Dark
14 Days
I L
Amber Glass with PTFE1 Lined Cap
515.3
Sodium Thiosulfate,
Cool, 4
C, Dark
14 days
4C, Dark
14 Days
50 mL
Amber Glass with PTFE1 Lined Cap
515.4
Sodium Sulfite, Dark, Cool 10C for First 48 hrs, 6C thereafter
14 days
0C
21 days
40 mL
Amber Glass with PTFE1 Lined Cap
524.22
Ascorbic Acid or Sodium Thiosulfate,
HCl pH<2, Cool 4C
14 days
NA
40 – 120 mL
Glass with PTFE1 Lined Septum
524.32
Maleic and Ascorbic Acids pH<2, 10C for first 48 hrs., 6 thereafter.
If only analyzing TTHM: Sodium Thiosulfate pH<2,
10C for first 48 hrs., 6 thereafter
14 days
NA
40 – 120 mL
Amber Glass with PTFE1 Lined Septum
525.2
Sodium Sulfite, Dark, Cool, 4C, HCl pH<2
14 days (See method for exceptions)
4C
30 days
1 L
Amber Glass with PTFE1 Lined Cap
531.1, 6610
Sodium Thiosulfate, Monochloroacetic Acid pH<3, Cool, 4ºC
Cool 4C from collection until storage at laboratory;
<-10C at the laboratory;
28 days
NA
60 mL
Glass with PTFE1 Lined Septum
531.2
Sodium Thiosulfate, Potassium Dihydrogen Citrate Buffer pH<4, Dark
10C for first 48 hrs., 6ºC thereafter
28 days
NA
40 mL
Glass with PTFE1 Lined Septum
537, 537.1
Trizma – 5.0 g/L
Cool < 10° during first 48 hours after collection. 28 days
< 6° at the laboratory until extraction. 28 days
250 mL
250- mL polypropylene bottle
533
Ammonium acetate
1.0 g/L
Cool < 10° during first 48 hours after collection. 28 days
< 6° at the laboratory until extraction. 28 days
250 mL
250- mL polypropylene bottle
Wis.
PFAS
Trizma – 5.0 g/L
Cool < 10° during first 48 hours after collection. 28 days
< 6° at the laboratory until extraction. 28 days
250 mL
250- mL polypropylene bottle
547
Sodium Thiosulfate,
Cool, 4
C
14 days; 18 mos. Frozen
NA
60 mL
Glass with PTFE1 Lined Septum
548.1
Sodium Thiosulfate, HCl pH 1.5 -2 if High Biological Activity,
Cool, 4
C, Dark
7 days
4C
14 days
250 mL
Amber Glass with PTFE1 Lined
Septum
549.2
Sodium Thiosulfate, H2SO4 pH<2, if Biologically Active,
Cool 4
C, Dark
7 days
21 days
250 mL
High Density Amber Plastic or Silanized Amber Glass
550
Sodium Thiosulfate,
Cool, 4C, HCl pH<2
7 days
4C, Dark
30 days
1 L
Amber Glass with PTFE1 Lined Septum
550.1
Sodium Thiosulfate,
Cool, 4C, HCl pH<2
7 days
4C, Dark
40 days
1 L
Amber Glass with PTFE1 Lined Septum
551.1
Sodium Sulfite, Ammonium Chloride, pH 4.5-5.0 with Phosphate Buffer,
Cool, 4C
14 days
14 days
<-10C
40 mL
Glass with PTFE1 Lined Septum
552.1
Ammonium
Chloride,
Cool, 4C, Dark
28 days
4C, Dark
48 hrs.
250 mL
Amber Glass with PTFE1 Lined Cap
552.2
Ammonium
Chloride,

Cool, 4
C, Dark
14 days
4C, Dark,
7 days
-10C, 14 days
50 mL
Amber Glass with PTFE1 Lined Cap
555
Sodium Sulfite,HCl pH 2,Dark, Cool, 4C
14 days
NA
100 mL
Glass wit PTFE1 Lined Cap
1613
Sodium
Thiosulfate,Cool,
0 - 4
C, Dark
1 year
40 days recommended
1 L
Amber Glass with PTFE1 Lined Cap
Section 5   NR 809.205 (1g) and (1r) are created to read:
NR 809.205 (1g) Schedule for perfluorooctane sulfonic acid and perfluorooctanoic acid monitoring. Community and non-transient non-community public water systems shall comply with initial monitoring requirements under sub. (1r) (a) for perfluorooctane sulfonic acid and perfluorooctanoic acid beginning on the following dates:
(a) Public water systems serving a population greater or equal to 50,000 [3 months after the rule becomes effective – LRB inserts date].
(b) Public water systems serving a population 10,000 to 49,999 [6 months after the rule becomes effective – LRB inserts date].
(c) Public water systems serving a population less than 10,000 [9 months after the rule becomes effective – LRB inserts date].
(1r)Monitoring frequency for perfluorooctane sulfonic acid and perfluorooctanoic acid. Water suppliers shall monitor to determine compliance with the maximum contaminant level for perfluorooctane sulfonic acid and perfluorooctanoic acid at the following frequencies:
(a) Initial monitoring. Water suppliers for new community public water systems or for community public water systems with new sources shall demonstrate compliance with the MCLs prior to initiating water service. Water suppliers for each community and non-transient, non-community water system shall take 4 consecutive quarterly samples for perfluorooctane sulfonic acid and perfluorooctanoic acid beginning on the dates specified under sub. (1g) or beginning with the year the public water system initiates water service, or a new source is put into service, and every compliance period thereafter unless the requirements of pars. (b) and (c) are met.
(b) Initial Waiver Evaluation For perfluorooctane sulfonic acid and perfluorooctanoic acid the department may waive the final 2 quarters of initial monitoring for a sampling point if the results of the samples from the previous 2 quarters are below the detection limit.
(c) Routine monitoring. Sampling may be reduced to routine monitoring after the initial monitoring period as follows:
1. ‘Public water systems serving greater than 3,300.’ Public water systems serving more than 3,300 persons that do not detect a contaminant in the initial compliance period or during 3 consecutive years of annual monitoring may reduce the sampling frequency to a minimum of 2 quarterly samples in one year during each repeat compliance period.
2. ‘Public water systems serving 3,300 or less.’ Public water systems serving 3,300 persons or less that do not detect a contaminant in the initial compliance period or during 3 consecutive years of annual monitoring may reduce the sampling frequency to a minimum of one sample during each repeat compliance period.
(d)Waiver Request. Water suppliers for community and non-transient non-community system may apply to the department for a waiver from the requirements under pars. (a) and (c) for perfluorooctane sulfonic acid and perfluorooctanoic acid. A water supplier shall reapply for a waiver for each compliance period. The waiver period shall not exceed 2 compliance periods.
(e) Waiver Evaluation. The department may grant a waiver from the requirements under par. (c) after evaluating all of the following factors:
1. ‘Waiver evaluation when the department determines a contaminant has not been used.’ The department may grant a waiver when the department determines a contaminant has not been used based on a system’s previous use information, including transport, storage, or disposal of the contaminant within the watershed or zone of influence of the public water system, or the results of analysis of a system’s water source.
2. ‘Waiver evaluation when a contaminant has been used or its use is unknown.’ If previous use of the contaminant is unknown or it has been used previously, all of the following factors shall be used to determine whether a waiver is granted:
a. Previous analytical results.
b. The proximity of the public water system to a potential point source of contamination. Point sources include spills and leaks of chemicals at or near a water treatment facility or at manufacturing, distribution, or storage facilities, or from hazardous and municipal waste landfills and other waste handling or treatment facilities; or at airports, military bases, and fire training facilities.
(f) Waiver conditions and monitoring assessments. As a condition of the waiver under par. (e), the water supplier for a groundwater system shall update the monitoring assessment considering the factors listed under par. (e). Based on this updated monitoring assessment, the department shall reconfirm that the public water system is non-vulnerable. If the department does not make this reconfirmation within 3 years of the initial determination or each subsequent determination, then the waiver is invalidated, and the public water system is required to sample during each compliance period as specified under par. (c).
Section 6   NR 809.205 (2) (title), (intro.), (a), (b) and 1. are amended to read:
NR 809.205 (2) Monitoring frequency for synthetic organic contaminants other than perfluorooctane sulfonic acid and perfluorooctanoic acid. Water suppliers shall monitor to determine compliance with the maximum contaminant level for synthetic organic contaminants specified in other than perfluorooctane sulfonic acid and perfluorooctanoic acid listed under s. NR 809.20 at the following frequencies:
(a) Initial monitoring. Water suppliers for new community public water systems or for community public water systems with new sources shall demonstrate compliance with the MCLs listed under s. NR 809.20 for synthetic organic contaminants other than perfluorooctane sulfonic acid and perfluorooctanoic acid prior to initiating water service. Water suppliers for each community and non-transient, non-community water system shall take 4 consecutive quarterly samples for each contaminant listed inunder s. NR 809.20, other than perfluorooctane sulfonic acid and perfluorooctanoic acid, beginning with the year the public water system initiates water service, or a new source is put into service, and every compliance period after that unless they meet the requirements ofunder par. (b).
(b) Routine monitoring. SamplingInitial quarterly sampling under sub. (4) (a) may be reduced to routine monitoring after the initial monitoring period as follows:
1. Public water systems serving greater than 3,330. Public water systems serving more than 3,300 persons whichthat do not detect a contaminant in the initial compliance period or during 3 consecutive years of annual monitoring may reduce the sampling frequency to a minimum of 2 quarterly samples in one year during each repeat compliance period.
Loading...
Loading...
Links to Admin. Code and Statutes in this Register are to current versions, which may not be the version that was referred to in the original published document.